Thomas & Betts RENZOR FT 30 Скачать руководство пользователя страница 8

Form RZ-NA-I-FT, Page 8

Figure 7A - Vertical Vent Terminals

11. Venting Requirements (cont'd)

6’ (2M) minimum

6’ (2M) minimum

Approved clearance thimble

 for single-wall vent pipe is

required when flue pipe

extends through

combustible materials.

Parapet or Adjoining Building

Vertical flue extension to

be 6” (152mm) higher than

anticipated snow depth but

no less than 2 feet (610mm)

above the roof.

Vertical pipe extension

must be insulated.

Roof Flashing

Roof - pitched

from 0 to 45°

Vertical flue extension

to be 6” (152mm) higher

than anticipated snow

depth but no less than

2 feet (610mm) above the

roof.

6” (152mm) minimum

Roof Flashing

Roof - pitched

from 0 to 45°

Approved clearance thimble

is required when flue pipe

extends through combustible

materials. Follow the require-

ments of the double-wall pipe

manufacturer.

Follow instructions above

to join single and double-wall

pipe and to seal the connection.

Parapet or Adjoining Building

Single-Wall Vent Run
and Single-Wall
Terminal End

Single-Wall Vent Run
and Double-Wall
Terminal End

5. Vent System Support

 - Lateral runs should be supported every six

feet using a non-combustible material, such as strap steel or chain. Do
not rely on the heater for support of either horizontal or vertical vent
pipe.

6. Condensation

 - On Model Sizes 30 and 45 only, if a single-wall vent

pipe run exceeds 15 feet (4.6 M) of straight length, it is recommended
that the pipe be insulated along its entire length with a minimum of 1/2"
foil-faced fiberglass, 1-1/2# density insulation rated for 250°F.

On all Model Sizes, any length of single-wall vent pipe exposed to cold
air or run through an unheated area or an area with an ambient tempera-
ture of 45°F or less must be insulated along its entire length with a
minimum of 1/2" foil-faced fiberglass, 1-1/2# density insulation. Model
Sizes 30 and 45 require insulation rated for 250°F; Model Sizes 60-300
require insulation rated for 400°F.

Where extreme conditions are anticipated, install a means of condensate
disposal.

7. Vent Terminal (Pipe and Vent Cap) - 

The vent system must be

terminated with the  type of vent cap approved for use with this heater.
The vent cap must be the same size as the vent pipe (vent pipe is either
3", 4", 5" or 6" diameter). Heaters must be equipped with the heater
manufacturer's vent cap, a Type L Breidert 

Air-x-hauster

®

 vent cap, or

equivalent. A different style vent cap could cause nuisance problems or
unsafe conditions.

See the illustrations in Figures 7A and 7B for requirements of vertical
and horizontal vent termination. The vent terminal pipe may be either
single-wall or double-wall (Type B). If double-wall pipe is used in the
vent terminal with a single-wall vent run, follow the instructions in
"Vent System Joints" (in the left column) to attach the vent cap and to
connect the double-wall pipe to the single-wall vent pipe run.

4. Vent System Joints

 - Vent system joints depend on the type of pipe

being used (See "Vent Pipe" requirements, No.1).

If using single wall, 26-gauge or heavier galvanized pipe, secure
slip-fit connections using sheetmetal screws or rivets. Seal pipe joints
either with tape suitable for 550°F (such as Option FA1, P/N 98266)
or high-temperature silicone sealant.

If using single-wall pipe to install a horizontal vent on a residential

application (Figure 6), make the elbow rigid by adding a light bead
of silicone sealant to the full circumference of 

all

 elbow section

joints.

If using Category III vent pipe, follow the pipe manufacturer's in-
structions for joining pipe sections. When attaching Category III
pipe to the venter outlet or the vent cap, make secure, sealed joints
following a procedure that best suits the style of Category III pipe
being used.

If using double-wall (Type B) vent pipe, follow the pipe
manufacturer's instructions for joining pipe sections.

For joining double-wall pipe to the venter outlet collar, increaser
collar, single-wall pipe, and/or the vent cap, follow the "boxed"
instructions below:

Instructions for attaching double-wall (Type B) vent pipe to the
venter outlet, a single-wall pipe run, or to the vent cap (use these
instructions for either full length double-wall or terminal only)

:

Hardware and Sealant Required: 3/4" long sheetmetal screws; and
a tube of silicone sealant

1) Look for the "flow" arrow on the vent pipe; attach according to
the arrow. Slide the pipe so that the venter outlet, the single-wall
pipe, or the vent cap is inside the double-wall pipe.

2) Drill a hole through the pipe into the outlet collar, the single-wall
pipe, or the vent cap. (Hole should be slightly smaller than the
sheetmetal screw being used.) Using a 3/4" long sheetmetal screw,
attach the pipe. Do not overtighten. Repeat, drilling and inserting
two additional screws evenly spaced (120° apart) around the pipe.

3) Use sealant to seal any gaps. If there is an annular opening, run a
large bead of sealant in the opening. The bead of sealant must be
large enough to seal the opening, but it is not necessary to fill the
full volume of the annular area.

Содержание RENZOR FT 30

Страница 1: ...Follow the gas supplier s instructions If you cannot reach your gas sup plier call your fire department WARNING Improper installation adjustment alteration service or maintenance can cause property da...

Страница 2: ...be protected from damage by aircraft or other objects such as cranes and movable scaffolding In addition the heat ers must be located so as to be accessible for servicing adjustment etc 2 Warranty Re...

Страница 3: ...100 square inches free area for each opening See 1 in Figure 2 2 Air from outside through duct openings 1 square inch free area per 2000 BTUH See 2 in Figure 2 3 Air direct from outside openings 1 squ...

Страница 4: ...2 pt suspension Follow the illustrated instructions in Figure 3B Sizes 30 45 60 and 75 may be suspended with an optional ceiling sus pension kit Refer to Figure 3C Step by step instructions are includ...

Страница 5: ...Composite drawings are not proportional for all sizes Field Wiring K 115V 60Hz 1Ph Connections L Thermostat Wires 24V Figure 4 Dimensions inches Size 30 45 60 75 100 125 150 200 250 300 A 28 5 8 28 5...

Страница 6: ...ure that the vent is sized properly for the heater being installed A properly sized vent system is required for safe operation of the heater An improperly sized vent system can cause unsafe conditions...

Страница 7: ...t system it is necessary to use 4 pipe only on a Size 30 and 5 pipe only on Sizes 45 and 60 Sizes 45 and 60 will require an increaser collar at the venter outlet The maximum horizontal vent length for...

Страница 8: ...blems or unsafe conditions See the illustrations in Figures 7A and 7B for requirements of vertical and horizontal vent termination The vent terminal pipe may be either single wall or double wall Type...

Страница 9: ...above a gas meter or service regulator Single Wall Vent Run and Single Wall Terminal End Single Wall Vent Run and Double Wall Terminal End 12 Gas Piping and Pressures WARNING This appliance is equippe...

Страница 10: ...to correct settings by turning the regulator screw IN clockwise to increase pressure Turn regulator screw OUT counterclockwise to decrease pressure Derating by Manifold Pressure Adjustment for High A...

Страница 11: ...Failed to Detect or Sustain Flame 3 Flashes Pressure Switch Open or Closed 4 Flashes High Limit or Flame Rollout Switch Open 5 Flashes Flame Sensed and Gas Valve Not Energized Steady On Internal Failu...

Страница 12: ...OPEN CIRCUIT TO HIGH LIMIT OR FLAME ROLLOUT TERMINAL 5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED STEADY ON INTERNAL FAILURE MICRO CONTROLLER FAILURE SELF CHECK NOTES 1 THE FOLLOWING CONTROLS A...

Страница 13: ...al probe which is electrically iso lated from ground When the flame impinges on the flame sensing probe the flame acts as a conduction path to ground The flame rectifies and completes the DC circuit a...

Страница 14: ...r water Immediately call a qualified ser vice technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water Operating Instructions an...

Страница 15: ...dure 1 Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 or CAN CGA B149 1and B149...

Страница 16: ...ulation Check the vent system for soundness Replace any parts that do not appear sound Check the wiring for any damaged wire Replace damaged wiring See Paragraph 13 for replacement wiring requirements...

Страница 17: ...ld cause fuel gas to spill out of the back of the burner tube Fuel gas spilling out of the back of the burner tube will cause gas odor inside the building and if not corrected could eventually cause a...

Страница 18: ...he front of the heater On Sizes 100 300 the limit control is accessible in the control compartment Sizes 250 and 300 have an auxiliary limit control To access the addi tional limit on Size 250 and 300...

Страница 19: ...unded f Make certain integrated circuit board is grounded to ignitor g Circuit board not grounded g Make certain integrated circuit board is grounded to furnace chassis h Faulty integrated circuit boa...

Страница 20: ..._____________________________ Unit Serial No __________________________________________ Date of Installation __________________________________________ PROBLEM PROBABLE CAUS E REMEDY No heat Heater 1...

Отзывы: