Thomas & Betts RENZOR FT 30 Скачать руководство пользователя страница 4

Form RZ-NA-I-FT, Page 4

8. Left Side Controls

All units are factory built with controls on the right side (as
viewed when facing the heater discharge). If the installation
location requires that the controls be on the left side, follow
the steps below to change the control side.

1. Turn the heater over (180

o

)

. Turn so that the sides are

opposite but the front and rear remain the same. (Notice
that the "bottom" panel, which is now on the top of the
heater, has four suspension holes.)

2. Reverse the Louver Position

 -- Remove the screws hold-

ing the louver frame. Turn the louver assembly (180

o

). Re-

install the assembly so that the louvers will direct the air
downward with the heater in its new position.

3. Sizes 60, 75, 100, 125, 150, 200, 250 and 300; Move the

Ignitor

 -- Remove the control access panel. On the side of

the burner rack, remove the screws holding the spark igni-
tor and the flame sensor. Interchange the locations of the
ignitor and the flame sensor so that the ignitor will be to-
ward the bottom of the burner rack. 

IMPORTANT: The

brown ground wire must stay with the spark ignitor.

4.

Turn the access panel so that the labels are in an upright
position. Re-attach the panel (NOTE: Illustrations of the
control section, except for the location of the ignitor and
the flame sensor on Sizes 60-300, will appear to be upside
down.)

9. Suspending the Heater

Before suspending the heater, check the supporting structure
to be used to verify that it has sufficient load-carrying capac-
ity to support the weight of the unit.

When the heater is lifted for suspension, support the bottom of the heater with
plywood or other appropriately placed material. If the bottom is not supported,
damage could occur.

Determine the type of suspension to be used:

All Sizes

 - The heater is equipped with 4-pt suspension. Two 3/8"-16 nut

retainers are located on each side of the heater. See Dimensions in Paragraph
10 and illustration in Figure 3A.

Sizes 30, 45, 60, and 75 

may be installed with 2-pt suspension. Follow the

illustrated instructions in Figure 3B.

Sizes 30, 45, 60, and 75

 may be suspended with an optional ceiling sus-

pension kit. Refer to Figure 3C. Step-by-step instructions are included with
the option kit.

WARNING: Suspend any size of Model FT heater only
from the threaded nut retainers (Figure 3A). Or, suspend
a Size 30, 45,60, or 75 as illustrated in Figure 3B or using
the Ceiling Suspension Kit in Figure 3C. Do not suspend
from the heater cabinet panels.

WARNING: Unit must be level for proper operation. Do not
place or add additional weight to the suspended heater. Hazard
Levels, page 1.

3/8” Threaded Rod

Add a 3/8” nut

to lock the hanger

rod to the heater

Be sure that the 3/8" threaded hanger
rods are locked to the heater as
illustrated. Recommended maximum
hanger rod length is 6 feet.

Figure 3A -
Four-point
suspension on
all sizes; attach
threaded rods
to all four nut
retainers

Sizes 30/45 --

21-1/4” (540mm)

Sizes 60/75 --

23-1/4” (591mm)

17-15/16”

(456mm)

9-9/16”

(243mm)5/16” or 3/8” threaded rods

(maximum length above

the heater is 18”/457mm )

On the bottom of the heater, use a washer

and double nuts to attach each threaded

rod. Use double nuts. Lock lower nut to

upper by holding upper nut while

tightening lower nut.

Sizes 30/45

12-1/8”

(308mm)

Sizes 60/75

18-1/8”

(591mm)

L

C

L

C

Figure 3B - Two-point suspension
applies to Models FT 30, 45, 60,
and 75

Size

30

45

60

75

100 125 150 200 250 300

lbs

60

66

84

90

140 145 205 215 258 280

kg

27

30

38

41

64

66

93

98

117 127

Net Weight 

Suspension Angle, P/N 194931 - Attach by (1) removing ALL

screws across top edge of cabinet. (2) Position suspension angle,

aligning holes with same holes emptied in Step (1). (3) Using

ALL screws that were removed and the same

cabinet holes, attach suspension angle.

Suspension angle

attached to rear

of heater

Figure 3C - Ceiling Suspension Kit, Option CK22,
for Models FT 30, 45, 60, or 75

When suspending, use a minimum of two anchor points per
angle.

NOTES: Quantity of screws used to attach the suspension angles
will vary by heater size and from front to rear of cabinet. If
optional vertical louvers are being added, install louvers after
suspension angles are attached.

Содержание RENZOR FT 30

Страница 1: ...Follow the gas supplier s instructions If you cannot reach your gas sup plier call your fire department WARNING Improper installation adjustment alteration service or maintenance can cause property da...

Страница 2: ...be protected from damage by aircraft or other objects such as cranes and movable scaffolding In addition the heat ers must be located so as to be accessible for servicing adjustment etc 2 Warranty Re...

Страница 3: ...100 square inches free area for each opening See 1 in Figure 2 2 Air from outside through duct openings 1 square inch free area per 2000 BTUH See 2 in Figure 2 3 Air direct from outside openings 1 squ...

Страница 4: ...2 pt suspension Follow the illustrated instructions in Figure 3B Sizes 30 45 60 and 75 may be suspended with an optional ceiling sus pension kit Refer to Figure 3C Step by step instructions are includ...

Страница 5: ...Composite drawings are not proportional for all sizes Field Wiring K 115V 60Hz 1Ph Connections L Thermostat Wires 24V Figure 4 Dimensions inches Size 30 45 60 75 100 125 150 200 250 300 A 28 5 8 28 5...

Страница 6: ...ure that the vent is sized properly for the heater being installed A properly sized vent system is required for safe operation of the heater An improperly sized vent system can cause unsafe conditions...

Страница 7: ...t system it is necessary to use 4 pipe only on a Size 30 and 5 pipe only on Sizes 45 and 60 Sizes 45 and 60 will require an increaser collar at the venter outlet The maximum horizontal vent length for...

Страница 8: ...blems or unsafe conditions See the illustrations in Figures 7A and 7B for requirements of vertical and horizontal vent termination The vent terminal pipe may be either single wall or double wall Type...

Страница 9: ...above a gas meter or service regulator Single Wall Vent Run and Single Wall Terminal End Single Wall Vent Run and Double Wall Terminal End 12 Gas Piping and Pressures WARNING This appliance is equippe...

Страница 10: ...to correct settings by turning the regulator screw IN clockwise to increase pressure Turn regulator screw OUT counterclockwise to decrease pressure Derating by Manifold Pressure Adjustment for High A...

Страница 11: ...Failed to Detect or Sustain Flame 3 Flashes Pressure Switch Open or Closed 4 Flashes High Limit or Flame Rollout Switch Open 5 Flashes Flame Sensed and Gas Valve Not Energized Steady On Internal Failu...

Страница 12: ...OPEN CIRCUIT TO HIGH LIMIT OR FLAME ROLLOUT TERMINAL 5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED STEADY ON INTERNAL FAILURE MICRO CONTROLLER FAILURE SELF CHECK NOTES 1 THE FOLLOWING CONTROLS A...

Страница 13: ...al probe which is electrically iso lated from ground When the flame impinges on the flame sensing probe the flame acts as a conduction path to ground The flame rectifies and completes the DC circuit a...

Страница 14: ...r water Immediately call a qualified ser vice technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water Operating Instructions an...

Страница 15: ...dure 1 Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 or CAN CGA B149 1and B149...

Страница 16: ...ulation Check the vent system for soundness Replace any parts that do not appear sound Check the wiring for any damaged wire Replace damaged wiring See Paragraph 13 for replacement wiring requirements...

Страница 17: ...ld cause fuel gas to spill out of the back of the burner tube Fuel gas spilling out of the back of the burner tube will cause gas odor inside the building and if not corrected could eventually cause a...

Страница 18: ...he front of the heater On Sizes 100 300 the limit control is accessible in the control compartment Sizes 250 and 300 have an auxiliary limit control To access the addi tional limit on Size 250 and 300...

Страница 19: ...unded f Make certain integrated circuit board is grounded to ignitor g Circuit board not grounded g Make certain integrated circuit board is grounded to furnace chassis h Faulty integrated circuit boa...

Страница 20: ..._____________________________ Unit Serial No __________________________________________ Date of Installation __________________________________________ PROBLEM PROBABLE CAUS E REMEDY No heat Heater 1...

Отзывы: