Thomas & Betts RENZOR FT 30 Скачать руководство пользователя страница 16

Form RZ-NA-I-FT, Page 16

MAINTENANCE AND SERVICE

WARNING: If you turn off the power
supply, turn off the gas. See Hazard
Levels, page 1.

The material contained in the MAINTENANCE AND
SERVICE Section of this manual is designed to aid a
qualified service person in maintaining and servicing
this equipment. This unit will operate with a mini-
mum of maintenance. To ensure long life and satis-
factory performance, a heater that is operated under
normal conditions should be inspected and cleaned
at the start of each heating season. If the heater is
operating in an area where an unusual amount of dust
or soot or other impurities are present in the air, more
frequent maintenance is recommended.
When any service is completed, be careful to reas-
semble correctly to ensure that no unsafe conditions
are created. When re-lighting, always follow the light-
ing instructions on the heater.

WARNING: Excessive dirt buildup on and inside the burner ports
could cause fuel gas to spill out of the back of the burner tube causing
gas odor inside the building. If uncorrected, fuel spilling out of the
back of the burner tube could cause a fire or explosion. To prevent
fuel gas from spilling from the back of the burners, clean the burner
ports at least annually.

Maintenance Schedule

 - The following procedures should be carried out at least annu-

ally (See Figure 12 and Paragraphs 22-32.):

Clean all dirt and grease from the primary and secondary combustion air openings
(vents in cabinet panels).

Clean the fan blade, fan guard, and motor.

Clean the heat exchanger both internally and externally.

Check the burners for scale, dust, or lint accumulation.

Check the vent system for soundness. Replace any parts that do not appear sound.

Check the wiring for any damaged wire. Replace damaged wiring. (See Paragraph 13
for replacement wiring requirements.)

NOTE: Use only factory-authorized replacement parts.

NOTE: If the heater has been changed so that the controls are on the left side (Paragraph 9), their locations will appear
inverted. On Sizes 60-300, the ignitor must
 still be toward the bottom of the heater with the flame sensor toward the top.

Pressure

Switch

Flue

Collar

Flame

Sensor

Limit Control

Location -

Sizes 100-300 Transformer

Limit Control Location -

Sizes 30-75 (located in the

heat exchanger compartment;

remove louvers to access)

Venter Motor

and Wheel Assy

Fan

Motor

Auxiliary Limit Control -

Sizes 250 & 300 (Remove

fan guard to access.)

Gas

Valve

Pressure Tap (for tubing

connection to the pressure switch)

Circuit Board (See LED

Codes on page 11 or 19.)

Ignitor

Burner/Manifold

Assembly

Flame

Rollout

Switch  -

Sizes

30-60

Figure 12 - Location of Controls - View of the

Control Compartment (A Size 30 is illustrated;

locations are approximately the same for other

sizes but may appear out of proportion.)

22. Burner Removal

Instructions for Burner Removal (See Figure 12)

1.

Shut the gas supply off ahead of the combination valve.

2.

Turn off electric supply.

3.

Remove the access panel; the vertical burner assembly is visible on the left side of the heater.

4.

Open the union in the gas line before the gas valve.

5.

Disconnect the flame sensor wire and the ignitor wire.

6.

Remove the screws that attach the burner assembly to the front panel and inner wall. Pull the manifold/burner assembly out of the heater.

Clean the Burners (requires a wire brush, cleaning cloth, and an automotive type aerosol
degreaser or refrigerant coil cleaner)

CAUTION: Use of eye protection is recommended.

Содержание RENZOR FT 30

Страница 1: ...Follow the gas supplier s instructions If you cannot reach your gas sup plier call your fire department WARNING Improper installation adjustment alteration service or maintenance can cause property da...

Страница 2: ...be protected from damage by aircraft or other objects such as cranes and movable scaffolding In addition the heat ers must be located so as to be accessible for servicing adjustment etc 2 Warranty Re...

Страница 3: ...100 square inches free area for each opening See 1 in Figure 2 2 Air from outside through duct openings 1 square inch free area per 2000 BTUH See 2 in Figure 2 3 Air direct from outside openings 1 squ...

Страница 4: ...2 pt suspension Follow the illustrated instructions in Figure 3B Sizes 30 45 60 and 75 may be suspended with an optional ceiling sus pension kit Refer to Figure 3C Step by step instructions are includ...

Страница 5: ...Composite drawings are not proportional for all sizes Field Wiring K 115V 60Hz 1Ph Connections L Thermostat Wires 24V Figure 4 Dimensions inches Size 30 45 60 75 100 125 150 200 250 300 A 28 5 8 28 5...

Страница 6: ...ure that the vent is sized properly for the heater being installed A properly sized vent system is required for safe operation of the heater An improperly sized vent system can cause unsafe conditions...

Страница 7: ...t system it is necessary to use 4 pipe only on a Size 30 and 5 pipe only on Sizes 45 and 60 Sizes 45 and 60 will require an increaser collar at the venter outlet The maximum horizontal vent length for...

Страница 8: ...blems or unsafe conditions See the illustrations in Figures 7A and 7B for requirements of vertical and horizontal vent termination The vent terminal pipe may be either single wall or double wall Type...

Страница 9: ...above a gas meter or service regulator Single Wall Vent Run and Single Wall Terminal End Single Wall Vent Run and Double Wall Terminal End 12 Gas Piping and Pressures WARNING This appliance is equippe...

Страница 10: ...to correct settings by turning the regulator screw IN clockwise to increase pressure Turn regulator screw OUT counterclockwise to decrease pressure Derating by Manifold Pressure Adjustment for High A...

Страница 11: ...Failed to Detect or Sustain Flame 3 Flashes Pressure Switch Open or Closed 4 Flashes High Limit or Flame Rollout Switch Open 5 Flashes Flame Sensed and Gas Valve Not Energized Steady On Internal Failu...

Страница 12: ...OPEN CIRCUIT TO HIGH LIMIT OR FLAME ROLLOUT TERMINAL 5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED STEADY ON INTERNAL FAILURE MICRO CONTROLLER FAILURE SELF CHECK NOTES 1 THE FOLLOWING CONTROLS A...

Страница 13: ...al probe which is electrically iso lated from ground When the flame impinges on the flame sensing probe the flame acts as a conduction path to ground The flame rectifies and completes the DC circuit a...

Страница 14: ...r water Immediately call a qualified ser vice technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water Operating Instructions an...

Страница 15: ...dure 1 Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 or CAN CGA B149 1and B149...

Страница 16: ...ulation Check the vent system for soundness Replace any parts that do not appear sound Check the wiring for any damaged wire Replace damaged wiring See Paragraph 13 for replacement wiring requirements...

Страница 17: ...ld cause fuel gas to spill out of the back of the burner tube Fuel gas spilling out of the back of the burner tube will cause gas odor inside the building and if not corrected could eventually cause a...

Страница 18: ...he front of the heater On Sizes 100 300 the limit control is accessible in the control compartment Sizes 250 and 300 have an auxiliary limit control To access the addi tional limit on Size 250 and 300...

Страница 19: ...unded f Make certain integrated circuit board is grounded to ignitor g Circuit board not grounded g Make certain integrated circuit board is grounded to furnace chassis h Faulty integrated circuit boa...

Страница 20: ..._____________________________ Unit Serial No __________________________________________ Date of Installation __________________________________________ PROBLEM PROBABLE CAUS E REMEDY No heat Heater 1...

Отзывы: