DANGER: The gas burner in this gas-fired equipment is designed and equipped to provide safe and
economically controlled complete combustion. However, if the installation does not permit the burner
to receive the proper supply of combustion air, complete combustion may not occur. The result is
incomplete combustion which produces carbon monoxide, a poisonous gas that can cause death. Safe
operation of indirect-fired gas burning equipment requires a properly operating vent system which
vents all flue products to the outside atmosphere. FAILURE TO PROVIDE PROPER VENTING WILL
RESULT IN A HEALTH HAZARD WHICH COULD CAUSE SERIOUS PERSONAL INJURY OR
DEATH.

Always comply with the combustion air requirements in the installation codes and in Paragraphs 6 and
7. Combustion air at the burner should be regulated only by manufacturer-provided equipment. NEVER
RESTRICT OR OTHERWISE ALTER THE SUPPLY OF COMBUSTION AIR TO ANY HEATER.
Indoor units installed in a confined space must be supplied with air for combustion as required by
Code and in Paragraph 7 of this heater installation manual. MAINTAIN THE VENT SYSTEM IN
STRUCTURALLY SOUND AND PROPERLY OPERATING CONDITION.

Check installation after start-up:

 

 

 

 

 

Vent System Testing Procedure

1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code,

ANSI Z223.1 or CAN/CGA B149.1and B149.2, Installation Code for Gas Burning Appliances and Equip-
ment, and this manual. Determine that there is no blockage or restriction, leakage, corrosion and other defi-
ciencies which could cause an unsafe condition.

3. In so far as practical, close all building doors and windows and all doors between the space where the heater

is and other spaces of the building. Turn on clothes dryers and exhaust fans, such as range hoods and bath-
room exhausts, so they shall operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace
dampers.

4. Light the heater following the lighting instructions. Adjust the thermostat for continued operation. Verify that

combustion products are venting properly.  After determining that the heater vents properly, return doors,
windows, exhaust fans, and fireplace dampers to their previous  conditions. If improper venting is observed,
the venting system must be corrected.

With the unit in operation, measure manifold gas pressure. See Paragraph 12.

Turn the unit off and on, pausing two minutes between each cycle. Observe for smooth ignition.

Place the "Owner's Envelope" containing the Limited Warranty, this booklet, and any control or optional
information in an accessible location near the heater. Follow the instructions on the envelope.

Содержание RENZOR FT 30

Страница 1: ...Follow the gas supplier s instructions If you cannot reach your gas sup plier call your fire department WARNING Improper installation adjustment alteration service or maintenance can cause property da...

Страница 2: ...be protected from damage by aircraft or other objects such as cranes and movable scaffolding In addition the heat ers must be located so as to be accessible for servicing adjustment etc 2 Warranty Re...

Страница 3: ...100 square inches free area for each opening See 1 in Figure 2 2 Air from outside through duct openings 1 square inch free area per 2000 BTUH See 2 in Figure 2 3 Air direct from outside openings 1 squ...

Страница 4: ...2 pt suspension Follow the illustrated instructions in Figure 3B Sizes 30 45 60 and 75 may be suspended with an optional ceiling sus pension kit Refer to Figure 3C Step by step instructions are includ...

Страница 5: ...Composite drawings are not proportional for all sizes Field Wiring K 115V 60Hz 1Ph Connections L Thermostat Wires 24V Figure 4 Dimensions inches Size 30 45 60 75 100 125 150 200 250 300 A 28 5 8 28 5...

Страница 6: ...ure that the vent is sized properly for the heater being installed A properly sized vent system is required for safe operation of the heater An improperly sized vent system can cause unsafe conditions...

Страница 7: ...t system it is necessary to use 4 pipe only on a Size 30 and 5 pipe only on Sizes 45 and 60 Sizes 45 and 60 will require an increaser collar at the venter outlet The maximum horizontal vent length for...

Страница 8: ...blems or unsafe conditions See the illustrations in Figures 7A and 7B for requirements of vertical and horizontal vent termination The vent terminal pipe may be either single wall or double wall Type...

Страница 9: ...above a gas meter or service regulator Single Wall Vent Run and Single Wall Terminal End Single Wall Vent Run and Double Wall Terminal End 12 Gas Piping and Pressures WARNING This appliance is equippe...

Страница 10: ...to correct settings by turning the regulator screw IN clockwise to increase pressure Turn regulator screw OUT counterclockwise to decrease pressure Derating by Manifold Pressure Adjustment for High A...

Страница 11: ...Failed to Detect or Sustain Flame 3 Flashes Pressure Switch Open or Closed 4 Flashes High Limit or Flame Rollout Switch Open 5 Flashes Flame Sensed and Gas Valve Not Energized Steady On Internal Failu...

Страница 12: ...OPEN CIRCUIT TO HIGH LIMIT OR FLAME ROLLOUT TERMINAL 5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED STEADY ON INTERNAL FAILURE MICRO CONTROLLER FAILURE SELF CHECK NOTES 1 THE FOLLOWING CONTROLS A...

Страница 13: ...al probe which is electrically iso lated from ground When the flame impinges on the flame sensing probe the flame acts as a conduction path to ground The flame rectifies and completes the DC circuit a...

Страница 14: ...r water Immediately call a qualified ser vice technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water Operating Instructions an...

Страница 15: ...dure 1 Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 or CAN CGA B149 1and B149...

Страница 16: ...ulation Check the vent system for soundness Replace any parts that do not appear sound Check the wiring for any damaged wire Replace damaged wiring See Paragraph 13 for replacement wiring requirements...

Страница 17: ...ld cause fuel gas to spill out of the back of the burner tube Fuel gas spilling out of the back of the burner tube will cause gas odor inside the building and if not corrected could eventually cause a...

Страница 18: ...he front of the heater On Sizes 100 300 the limit control is accessible in the control compartment Sizes 250 and 300 have an auxiliary limit control To access the addi tional limit on Size 250 and 300...

Страница 19: ...unded f Make certain integrated circuit board is grounded to ignitor g Circuit board not grounded g Make certain integrated circuit board is grounded to furnace chassis h Faulty integrated circuit boa...

Страница 20: ..._____________________________ Unit Serial No __________________________________________ Date of Installation __________________________________________ PROBLEM PROBABLE CAUS E REMEDY No heat Heater 1...

Отзывы: