Thomas & Betts RENZOR FT 30 Скачать руководство пользователя страница 13

Form RZ-NA-I-FT, Mfg No. 173473 Rev  8, Page 13

DANGER: Safe operation of this unit requires
proper venting flow. NEVER bypass combustion
air proving switch or attempt to operate the unit
without the venter running and the proper flow
in the vent system. Hazardous conditions could
result. See Hazard Levels, page 1.

17. Gas Valve

The main operating gas valve is powered by the 24-volt control circuit
through the thermostat and safety controls. The main control valve is
of the diaphragm type providing regulated gas flow preset at the fac-
tory.

WARNING: The operating valve is the prime safety
shutoff. All gas supply lines must be free of dirt or
scale before connecting the unit to ensure positive
closure. See Hazard Levels, page 1.

Model S izes

Star

t-U

Co

ld

Equilibr

ium

Set Po

int 

"O

FF"

Set Po

int 

"O

N

"

30

Units mfgd p rior to 11/97 

-1.2

-0.70

-0.55

-0.65

45

 (verify  on rating p late; 11/97

-1.2

-0.70

-0.55

-0.65

60

is Serial No. Date Code AWK)

-1.2

-0.75

-0.55

-0.65

30

Units mfgd beginning 11/97 

-0.9

-0.60

-0.42

-0.52

45

 (verify  on rating p late; 11/97

-1.1

-0.67

-0.55

-0.65

60

is Serial No. Date Code AWK)

-1.1

-0.66

-0.50

-0.60

30

Units mfgd beginning 8/98 

-1.4

-0.60

-0.15

-0.25

45

 (verify on rating p late; 8/98

-1.1

-0.60

-0.22

-0.32

60

is Serial No. Date Code AXH)

-1.1

-0.63

-0.22

-0.32

-1.3

-0.78

-0.55

-0.65

-1.4

-1.25

-0.80

-0.90

75, 100, 125, 150, 200

250, 300

18. Ignition System

This heater is equipped with a direct spark integrated control system.
The system monitors the safety devices and controls the operation of
the fan and venter motors and the gas valve between heat cycles.

Ignition System Operating Sequence

 -- On a call for heat from the

thermostat, the system energizes the venter motor and goes through a
10-second prepurge. The system verifies that both the pressure switch
and the high limit are in the closed state. The gas valve is then ener-
gized and the ignition system provides the high voltage spark to the
electrode to ignite the main burner gas. Burner flame is electronically
sensed by the control upon carryover of all burners. (A separate solid
metal probe is used as the flame sensing function. A low voltage elec-
trical signal is imposed on the metal probe which is electrically iso-
lated from ground. When the flame impinges on the flame sensing probe,
the flame acts as a conduction path to ground. The flame rectifies and
completes the DC circuit, and the ignition system acknowledges the
flame.) The fan motor is energized by the system after 30 seconds of
flame sensing.

After the thermostat has been satisfied, the system de-energizes the gas
valve, the venter motor goes through a 45-second post-purge, and the
fan motor remains energized for an additional 180 seconds.

NOTE:

 This is a three trial system, should the unit not sense burner

flame, the unit will lockout for one hour before initiating another trial
for ignition. To initiate another trial for ignition before the one hour,
requires that either the thermostat be reset or the power to the unit be
interrupted for 30 seconds.

19. Burners

This unit heater has inshot burners designed to provide controlled flame
stability without lifting or flashback with either natural or propane gas.
The burners are lightweight and factory mounted in an assembly which
permits them to be removed as a unit for inspection or service.

20. Burner Air Restrictor

Sizes 250 and 300 burning propane gas are equipped with a two-piece
burner air restrictor. The air restrictor is attached to the burner assem-
bly and is not field adjustable.

16. Combustion Air Proving

Switch

The combustion air proving switch is a pressure sensitive switch that
monitors air pressure to ensure that proper combustion air flow is avail-
able. The switch is a single pole - normally open - device which closes
when a decreasing pressure is sensed in the venter housing.

On start-up when the heater is cold, the sensing pressure is at the most
negative level, and as the heater and flue system warm up, the sensing
pressure becomes less negative. After the system has reached equilib-
rium (about 20 minutes), the sensing pressure levels off.

If a restriction or excessive flue length or turns cause the sensing pres-
sure to be outside the switch setpoint, the pressure switch will function
to shut off the main burners. The main burners will remain off until the
system has cooled and/or the flue system resistance is reduced. The
Table below lists the approximate water column negative pressure read-
ings and switch setpoints for sea level operating conditions.

Содержание RENZOR FT 30

Страница 1: ...Follow the gas supplier s instructions If you cannot reach your gas sup plier call your fire department WARNING Improper installation adjustment alteration service or maintenance can cause property da...

Страница 2: ...be protected from damage by aircraft or other objects such as cranes and movable scaffolding In addition the heat ers must be located so as to be accessible for servicing adjustment etc 2 Warranty Re...

Страница 3: ...100 square inches free area for each opening See 1 in Figure 2 2 Air from outside through duct openings 1 square inch free area per 2000 BTUH See 2 in Figure 2 3 Air direct from outside openings 1 squ...

Страница 4: ...2 pt suspension Follow the illustrated instructions in Figure 3B Sizes 30 45 60 and 75 may be suspended with an optional ceiling sus pension kit Refer to Figure 3C Step by step instructions are includ...

Страница 5: ...Composite drawings are not proportional for all sizes Field Wiring K 115V 60Hz 1Ph Connections L Thermostat Wires 24V Figure 4 Dimensions inches Size 30 45 60 75 100 125 150 200 250 300 A 28 5 8 28 5...

Страница 6: ...ure that the vent is sized properly for the heater being installed A properly sized vent system is required for safe operation of the heater An improperly sized vent system can cause unsafe conditions...

Страница 7: ...t system it is necessary to use 4 pipe only on a Size 30 and 5 pipe only on Sizes 45 and 60 Sizes 45 and 60 will require an increaser collar at the venter outlet The maximum horizontal vent length for...

Страница 8: ...blems or unsafe conditions See the illustrations in Figures 7A and 7B for requirements of vertical and horizontal vent termination The vent terminal pipe may be either single wall or double wall Type...

Страница 9: ...above a gas meter or service regulator Single Wall Vent Run and Single Wall Terminal End Single Wall Vent Run and Double Wall Terminal End 12 Gas Piping and Pressures WARNING This appliance is equippe...

Страница 10: ...to correct settings by turning the regulator screw IN clockwise to increase pressure Turn regulator screw OUT counterclockwise to decrease pressure Derating by Manifold Pressure Adjustment for High A...

Страница 11: ...Failed to Detect or Sustain Flame 3 Flashes Pressure Switch Open or Closed 4 Flashes High Limit or Flame Rollout Switch Open 5 Flashes Flame Sensed and Gas Valve Not Energized Steady On Internal Failu...

Страница 12: ...OPEN CIRCUIT TO HIGH LIMIT OR FLAME ROLLOUT TERMINAL 5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED STEADY ON INTERNAL FAILURE MICRO CONTROLLER FAILURE SELF CHECK NOTES 1 THE FOLLOWING CONTROLS A...

Страница 13: ...al probe which is electrically iso lated from ground When the flame impinges on the flame sensing probe the flame acts as a conduction path to ground The flame rectifies and completes the DC circuit a...

Страница 14: ...r water Immediately call a qualified ser vice technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water Operating Instructions an...

Страница 15: ...dure 1 Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 or CAN CGA B149 1and B149...

Страница 16: ...ulation Check the vent system for soundness Replace any parts that do not appear sound Check the wiring for any damaged wire Replace damaged wiring See Paragraph 13 for replacement wiring requirements...

Страница 17: ...ld cause fuel gas to spill out of the back of the burner tube Fuel gas spilling out of the back of the burner tube will cause gas odor inside the building and if not corrected could eventually cause a...

Страница 18: ...he front of the heater On Sizes 100 300 the limit control is accessible in the control compartment Sizes 250 and 300 have an auxiliary limit control To access the addi tional limit on Size 250 and 300...

Страница 19: ...unded f Make certain integrated circuit board is grounded to ignitor g Circuit board not grounded g Make certain integrated circuit board is grounded to furnace chassis h Faulty integrated circuit boa...

Страница 20: ..._____________________________ Unit Serial No __________________________________________ Date of Installation __________________________________________ PROBLEM PROBABLE CAUS E REMEDY No heat Heater 1...

Отзывы: