3.2.5.2 SENSOR-INTERFACE
SIF
In the case of model 9.1756.X0.
1
00 is a so-called sensor-interface SIF build in and is connected to
COM2 (9600Bd 8N1, RS232 mode) of the datalogger. Available are different SIF which separate
between number and type of channels. The data are requested with the command “mm”. The
command “SI2” (ref. to chap.
) can be used to send a command to the SIF.
SIF001, 6 channels: Radiation 2 + 3, Direct-radiation 1 + 2, Temperature 3 + 4
SIF002, 9 channels: 10V-input, 1V-Input 1 + 2, 20mA-Input 2 + 3 + 4, Temperature 3 + 4 + 5
3.2.6 SWITCH OUTPUT TIMER
The timer activates up to 6 daily time slots for an externally connected GSM-modem.
By setting small time slots (for ex. 5 min) the average current consumption of the modem per day
(operating current approx. 200 mA) can be kept down.
During a data transmission via a timer-controlled modem, the remaining power-on-time is fixed on 5
min, thus a re-logging-in in case of a failure is guaranteed within this period.
In the edit mode all timers can be set in turn .
Selectable are the daily starting time, and the minimum power-on-period.
33 - 56
021579/06/09
x = 1,2,3,4,5,6
TIMERx: HH:MM
ONLINE: NN min
„HH:MM“ indicates the starting time of the respective timer slot in the format hour:min.
The power-on-period is selectable in minute-increments from 5 to 31. When the power-on-time is
set to 0, the respective timer is deactivated.
Remark:
Only timer 1 is activated even if the discharge-protection for the accumulator is
active (voltage < 10.5V).