29 - 66
021341/07/11
Command SB
<id>SB
Request of the bootloader version.
Description:
Output of the bootloader version (example reply: „!00SB00110“ -> V1.10), if
supported by the bootloader.
Value range:
-
Initial value:
-
Command SN
<id>SB
Request of the serial number.
Description:
Output of the serial number.
Note: If the serial number is 0 the system parameters are adjusted wrongly.
In this case, please have the instrument checked by the manufacturer.
Value range:
1…9999
Initial value:
set in the factory
7.2.3 Data telegrams commands
Command TM
<id>TM<para5>
Telegram selection measuring data (automatically send without request,
automatic mode).
Description:
Setting the telegram, telegram 3 to 10 (see CH.
7.3
).
Telegram 1 and 2 are for internal test purpose.
Telegram 0 means no automatic sending, and is recommended when using
the polling command “TR”.
Value range:
0...10
Initial value:
4 (5.4110.0x.xxx) resp. 5 (5.4110.1x.xxx)
Command TR
<id>TR<para5>
Command for requesting a telegram (polling mode).
Description:
Request of telegrams 4 to 10 (see CH.
7.3
). If you want to get the data by
polling, you should switch off the automatic mode with the command
“<id>TM00000”. Otherwise the “TM” parameter will be set only internally to 0. If
you wish to use the automatic mode again send the command “TM” or power
up the sensor.
When a telegram is not available, the sensor answers “!<id>TR00001”.
Depending of the baudrate and the internal sensor clock a telegram is
available
Availability:
Telegrams 6 to 10:
•
1200Bd:
0...57s
•
>= 2400Bd:
0...58s
Telegrams 4 and 5:
•
1200Bd:
0...38s
•
2400Bd:
0...49s
•
9600Bd/19.2kBd: 0...57s
•
>= 38.4kBd:
0...58s
Value range:
4...10
Initial value:
-
Содержание 5.4110 00 Series