UPS input and output connections
Sizing of the cables at input, output and battery, please refer to the below table:
1) Switch Off all breakers before connecting cables..
2) Remove the cover of terminal blocks and connect the cables correspondingly.
3)
Connect the UPS output L, N, E to L, N, E of load via a PDU. Tighten the screws and
shelter the terminals
.
UPS
CABLES DIMENSION (mm
2
)
INPUT
OUTPUT
BATTERIES
GND
10KVA
4 x 10
2 x 10
3 x 16
10
15KVA
4 x 10
2 x 16
3 x 25
16
20KVA
4 x 16
2 x 25
3 x 25
25
A/B/C/Ni
INPUT section
Lo-No
OUTPUT
section
BAT+/BATN/BAT-
BATTERY
section
GND
GROUND
CONNECTION
Fig.3
Connections on terminal block
3.4
Connection of UPS communication cables
1) For local monitoring of UPS, a
USB cable provided in accessories can be used to connect
the UPS with PC
in order to install UPSilon2000 software.
2) For remote monitoring of UPS an SNMP card (optional) must be installed.
A.
Remove the cover of SNMP slot at UPS rear panel and keep it for further use.
B.
Insert the SNMP card and tighten the screws
C.
Connect the UPS with internet by network cable.
D.
Refer to the SNMP manual provided to do SNMP setting.
CAUTION!
Cables need terminal to ensure correct connection.
Don’t reverse input phase (L) and
Neutral (N).
Don’t connect the UPS to a wall outlet because may get burnt.
Connect to an electrical panel.
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK