Ver02
17.11.2014
10
3.5
External battery connection (for extended autonomy time
only)
Make sure that battery quantity complies with the spec. (16/18/20 blocks at 12V in series). Make
sure that the voltage of battery bank is 192/216/240Vdc.
CAUTION
:
1)
Don’t mix batteries with different
capacity & brands and do
n’t mix bra
nd new and old
batteries
.
2)
Standard configuration is made by 16 blocks with a max. capacity of 65Ah (battery charger
at 6A). When using a configuration with 18 or 20 blocks, then switch On the UPS with
mains is present and configure the exact number of blocks in order to split correctly the
charging current.
3)
The breaker on battery cabinet should be off.
4)
Take out the connection box and remove the cover of terminals, make sure there is no DC
voltage at the
battery terminals of UPS.
5)
Connect battery pole with positive pole, common pole and negative pole to battery
connector (BAT+,BATN,BAT-
㸧
,
don’t reverse battery
connection
(Fig. 5).
Fig.5 External battery cabinet
connection
CAUTION:
x
Make sure the UPS is Off and battery breaker is Off before installing the batteries..
Don’t
wear any watch, rings or similar, to avoid any accidental shortcircuit.
x
Don’t reverse nor shortcircuit the cables. Red cable must be connected to “+”
positive pole
and black cable must be connected to
“
-
”
.negative pole
x
Use tools with isolated handle.
don’t put any object on top of batteries.
CAUTION:
x
Connection cables section must be compliant to the Standard when using an external
battery cabinet.
x
When connecting the load to the UPS, make sure that UPS and load are Off. In case of
multiple loads, then connect them once a time.
x
Don’t connect to Ups load such as copier machine, inductive load (engine), fluorescent
lamps, to avoid any damage to UPS.
x
It is recommended to connect the UPS to the mains by means of an input breaker. Make
sure that ground connection is implemented.
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK