Ver02
17.11.2014
12
Press “On” on the front panel to start the UPS and in
the meantime, the LCD display will light
up. You may view the data and set parameters on the LCD display and the LED display of
the UPS will show the latest status of the UPS. Display will show NOR Cod. 6 message,
Yellow LED will be on and an acoustic signal will be emitted every 2 sec. (Battery will be
discharging).
4.2.2 Turn Off operation
1) Turn off the UPS in line mode:
a)
Press and hold the OFF key for 2 seconds to turn off the inverter and the UPS is in
Bypass mode now; on the contrary, you may press the hold the OFF key for 2 seconds
in order to Change over back to inverter mode
).
b)
To shut down (turn off) the UPS completely, you need to turn off the input switch.
2) Turn off the UPS with connecting batteries (no mains):
a)
Press and hold the OFF key for 2 seconds to turn off the UPS.
b)
After UPS is turned off, all LED and LCD will be extinguished and there is no output.
Nota: When the UPS is turned off from the inverter mode, it will discharge DC Bus and then shut
down completely; therefore, sometimes, it takes more several seconds to complete.
4.3 Control Panel
4.3.1 LED and control panel display
1)
ALARM LED (red)
2)
BYPASS LED
(yellow)
3)
BATTERY LED
(yellow)
4)
INVERTER LED
(green)
5)
Display LCD
6)
ENTER (Scroll button)
7)
OFF button
8)
ON button
4.3.2 LCD
display
NOTE! The display provides more functions than those described in this manual. There are 11
interface available in the LCD display:
ITEM
DESCRIPTION
CONTENT DISPLAYED
01
Code
Operational mode and status
02
Input Phase A
Voltage and Frequency
03
Input Phase B
Voltage and Frequency
04
Input Phase C
Voltage and Frequency
05
B
Voltage and Current
06
Battery -
Voltage and Current
07
Output
Voltage and Frequency
08
Load
Load
09
Temperature
PFC/Internal temperature and Ambient temperature
10
DC Bus Voltage
± DC Bus Voltage
11
Software version &
model
DSP verson of inverter software version and UPS model
8
7
6
5
1
2
3
4
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK