Installation, use and maintenance guide
Mon Amour
8 – ROOM TEMPERATURE THERMOSTAT / CHRONOTHERMOSTAT (not supplied)
The appliance can be connected to an additional room temperature thermostat or to an additional chronothermostat:
-
Additional room temperature thermostat: connect the terminals directly to the terminal block on the circuit board, as
illustrated in the image below.
-
Additional Chronothermostat – Modem: connect the terminals directly to the terminal block on the circuit board, as
illustrated in the image below.
The contacts of the room temperature thermostat and of the chronothermostat modem, are defined as "potential
free" contacts and they must never be supplied with 230V. If the board is powered with 230 V or lower voltages,
the control board would be irreparably damaged and the warranty voided.
8.1 OPERATING WITH THE ADDITIONAL ROOM TEMPERATURE THERMOSTAT (NOT SUPPLIED)
An additional room temperature thermostat can be installed by connecting it to the inside of the electronic board compartment, using
contacts 9 and 10 on terminal block J5 as illustrated in the figure below. It has a “potential free” contact, that is a very low voltage
contact. The operating principle is as follows:
• When the room temperature reaches the set temperature, the room thermostat closes the contact, the appliance will operate at the
the minimum combustion power and the 1st power bar will flash on the display, any manual power change will be disabled.
• When the room temperature drops the thermostat opens the contact and the appliance returns to its original position in terms of
thermal power.
CAUTION: N.C. “Normally Closed” contacts must be used for the connection to the additional room temperature
thermostat. Do not power the contacts with mains voltage as this would seriously damage the control board, and is not
covered by warranty.
8.2 OPERATING WITH THE ADDITIONAL CHRONOTHERMOSTAT (NOT SUPPLIED)
An additional chronothermostat can be installed by connecting it to the inside of the electronic board compartment, using contacts 7
and 8 on terminal block J5 as illustrated in the figure below. Using this output when the chronothermostat contact closes the
START cycle begins, whereas when the contact opens the OFF cycle begins. When the chronothermostat is active the appliance
cannot be switched off manually but only from the additional chronothermostat.
CAUTION: The manufacturer denies all responsibility for the life of the electrical heater if subjected to excessive start
up cycles. Consequently, it is advisable to set the chronothermostat appropriately. If an external chronothermostat is
connected to the appliance it will not be possible to use the Chrono function on the panel.
CAUTION: Use N.O. (normally open) contacts for the connection to the chronothermostat. Do not supply direct power
of 230 V or lower voltages as this would seriously damage the control board, and is not covered by warranty.
CAUTION: In the event of connections to the chronothermostat Thermorossi shall not be held responsible for the appliance not
starting up, smoke leaks, breakage of the lighting component. The user must make sure that the brazier is always clean.
CAUTION: When using the chronothermostat program up to a maximum of 3 on-off cycles. The chronothermostat must have a
thermal hysteresis that is not less than 2°C.