Table 6.1:
Main Menu Options (Continued)
Menu Option
Applies To Set-Point/Settings Available
Range/Options
Precision
LOW CURRENT ALARM
Individual
Circuit
ALARM
0.0 A to HIGH CURRENT ALARM -1.0A
0.1 A
HEATER ENABLE
Individual
Circuit
HEATER
ENABLED, FORCED ON or DISABLED
CONTROL (Control Method)
ON/OFF MEC, ON/OFF SSR,
PROPORTIONAL, AMBIENT, AMBIENT
APCM (See
Section 7.1
for Control Method )
CONFIGURATION
Both
Circuits
GROUND CUR TRIP
ON or OFF
HEATER CUR TRIP
ON or OFF
HIGH TEMP TRIP
ON or OFF
ALARM ON (Digital Outputs
Activate On…)
ALL ALARMS or TEMP ONLY
ALARM OUTPUT NRM (Alarm
Outputs Normally)
ON or OFF
RTD UNITS (Temperature Units)
°C or °F
APCM CYCLE TIME
20, 25 or 33 min
AUTO SELF TEST
OFF or every 2 – 99 hours
1 hour
START UP DELAY
0-30 min
1 min
SOFT START
1 – 8 min
1 min
FIRST CIRCUIT NUMBER
0-99
1
SCREEN SAVER
ON or OFF
LANGUAGE
English, Spanish, Russian
SELF TEST
for Self-test,
for Ground Test