11
current (about 50 mA~) through the GFI CT to verify functionality on
command or at a user configurable interval.
CTRL OUT 1 & 2: These output signals control the power SSRs or
mechanical relays which energize the heat trace. Signal voltage defaults
to 12 VDC but can be changed to 24 VDC in the Factory Menu. Each
output is current limited to 100 mA.
REMOTE ACK: This isolated input allows acknowledgement of alarms
without opening the panel. It may be connected to a pushbutton switch or
to the contacts of a relay driven by a remote signal. The positive side
provides an isolated 5 VDC signal. When switched, the negative side
drives the diode of an opto-coupler to signal to the TCM2
acknowledgement of the alarm or trip.
RS-485 DATA HWY: D+ & D- are the differential bus lines for
communications. S is the common leg and is often connected to the
shield in a 2-wire twisted pair cable. Though this configuration is
common, ideally, S is connected to another wire within the cable and the
shield is grounded on one side only. See
Section 8
for more information.