6
The table below serves as general specification information for the TCM2 control
module.
Table 2.2:
TCM2 Module Specifications
Parameter
Description
Mains Supply
100 to 240 V~, 50/60 Hz, Overvoltage Category II
Max. Input Current
740 mA
Power Consumption
95 VA max
Control Points
Up to 2 Heat Tracing Circuits
Temperature Inputs
Up to Two per Control Point; Platinum RTD’s 100
Ω
@ 32 °F (0 °C)
Temperature Control
Range
-200 °F to 1112 °F (-129 °C to 600 °C)
Communication
RS-485, ModBus ASCII or RTU, up to 57600 Baud
Accessory Power Output
9 W @ 24 VDC
Digital Alarm Outputs
3 x 24 VDC, 100 mA
Control Outputs
2 x 24 VDC, 100 mA or 2 x 12 VDC, 100 mA (user
selectable)
Control Methods
On/Off MEC, On/Off SSR, Proportional, Ambient or
APCM
Display
4 Line, 20 Character, OLED
Operating Temperature
-40 °F to 140 °F (-40 °C to 60 °C)
Storage Temperature
-40 °F to 176 °F (-40 °C to 80 °C)
Dimensions (W x H x D)
4.7” x 4.65” x 3.25” (119mm x 118mm x 83mm)
Module should be mounted as seen in
Figure 2.1
and include a minimum 2” (50 mm) clearance above
the module and 1.5” (38 mm) clearance below the
module.
Figure 2.1:
TCM2 Module Dimensions