22
6
Accessing Control
Settings
6.1 Password Protection
The TCM2 module features password protection for settings. The user has the
option to set a four-digit numerical password which must be entered in order to
authorize changes to any set-point or setting. Without the password, all setting
and set-points may be viewed, alarms/trips may be acknowledged and circuits
may be reset but no settings or set-points may be modified. When the correct
password is entered, the TCM2 enters Program Mode where changes are
authorized for 30 minutes. After the 30 minutes has passed, the password will
again be required. The default password is 0000.
Figure 6.1:
Enter Password to enter Program Mode
By default, password protection is disabled. The first line of the Main Menu
displays whether the control module is in View Mode or Program Mode (See
Figure 6.1
). To enable the password, enter the Main Menu and select
PASSWORD SETTINGS. Change PASSWORD from OFF to ON and enter a
password using
&
to change each number and
to select the number
and confirm.
Figure 6.2:
Enable/Disable Password or Change Password
6.2 Adjusting Set-points
To adjust the control parameters of the TCM2 module, be sure first, to enter
Program Mode by entering the correct password or by disabling password
protection as per the previous section. Then, using
&
, navigate to the
desired submenu and press
.
Table 6.1
shows a complete listing of all
submenus as well as each set-point and setting contained within and their valid
ranges. For set-points or settings which apply only to one circuit, for example
MAINTAIN TEMP, the desired circuit must be selected upon entering the