Section 4.4: V4 Control Valve
V4 Control Valve Test
1.
Place V4 valve into a water bath at 98°F or above for five minutes.
2.
If you blow compressed air into the upper angled hose adapter the valve should be closed.
3. Place V4 into a water bath at 85°F or below for five minutes.
4.
If you blow compressed air into the lower straight hose adapter it should be closed.
5.
If the valve does not work correctly a replacement V4 Control Valve is required.
V4 Control Valve Replacement
Follow instructions provided with replacement part from ThermOmegaTech®
Lower Hose Adapter,
From Outside V3
Middle Hose Adapter,
Dumps To Outlet
Upper Hose Adapter,
From Inside V3
Page 10