Section 4.0: Adjustments and Repairs
V1 Mixing Valve Adjustment Outside of the Unit
1.
Unscrew entire main valve cap from V1 mixing valve with a 1-1/2” wrench. The entire internal
assembly will pull out of the valve body in one piece.
2.
Remove mixing valve cap nut with 1” wrench.
3. Loosen calibration lock nut with a 7/16” wrench.
4.
Place valve into a 90°F water bath for five minutes.
5.
Use calibration screw to adjust the valve spool so that the inner spool cold water slots line up with
outer housing cold water slots so that cold side is fully open and hot side is fully closed. Place
valve into an 80°F water bath for five minutes.
6.
Use calibration screw to adjust the valve spool so that the inner spool hot water slots line up with
outer housing hot water slots so that hot side is fully open and cold side is fully closed.
7.
Tighten the calibration jam nut.
8.
Screw the mixing valve assembly back into the V1 mixing valve body.
Section 4.1: V1 Mixing Valve
Prior to beginning any repairs, follow all steps in section 3.3 to decommission the station. Test the unit
after all repairs have been completed to confirm full functionality.
V1 Mixing Valve Internal Assembly Replacement
Follow instructions provided with replacement part from ThermOmegaTech®
Remove Cap Screw
Remove Lock Nut
Adjust Calibration Screw
Page 8
Содержание THERM-O-MIX STATION
Страница 13: ...Page 12 Appendix 1 Station Schematic...
Страница 14: ...Appendix 2 Station Operating Logic Flow Chart Page 13...
Страница 15: ...Page 14 Appendix 3 Typical Installation Schematic...
Страница 16: ...Appendix 4 Labeled Station Line Drawing Page 15...
Страница 17: ...Page 16 Appendix 5 Hoses and Hose Fittings Line Drawing...