background image

Section 1.0: Introduction

This manual is designed to aid qualified personnel in troubleshooting and repairing of the  

Therm-O-Mix® Station. 

Qualified personnel assigned to troubleshoot or repair a Therm-O-Mix® 

Station should read the entire manual before proceeding. 

If you have any questions or concerns 

about the information found in this manual, please contact ThermOmegaTech® at 1-877-379-8258.

Section 1.1: Definitions and Terminology

• 

System = safety shower/eyewash station 

• 

Heater = Therm-O-Mix® Station tempered water unit 

• 

Normal Range = tepid/moderately warm/lukewarm not to exceed 100F 

• 

Flow Pressure = gauge pressure measured during flow (dynamic pressure) 

• 

HtEx = stainless steel brazed plate heat exchanger 

• 

V1 = primary mixing valve; mixes cold inlet water with heated water from V5 

• 

V2 = normally open; controls hot water temperature out of HtEx by regulating steam flow into HtEx 

• 

V3 = normally closed; pressure sensing diaphragm valve; opens in response to pressure            

differential across unit, allowing steam flow to HtEx 

• 

V4 = normally closed; senses water temp out of mixing valve V1; V4 will open if the water         

temperature is too high, short circuiting pressure differential across diaphragm, closing V3 and 

 

turning steam flow off 

• 

V5 = normally open; pre-mixes cold water with hot water from heat exchanger prior to mix entering 

the V1 mixing valve. 

• 

V6 = normally closed; starts to open when water temp at valve approaches 95F due to heat soak 

or heat migration. 

Page 2

Section 1.2: Checklist

Review the below checklist before troubleshooting. 

• 

Does the plant have adequate Steam Flow Pressure for the selected Therm-O-Mix® Station?

• 

Standard Pressure Steam Heater - Requires min. 45 PSIG/max. 60 PSIG. Above 60 PSIG 

requires pressure regulator. Above 75 PSIG requires pressure regulator and relief valve.

• 

Lower Pressure Steam (LPS) Heater - Requires min. 15 PSIG/max. 30 PSIG. Above 30 PSIG 

requires pressure regulator. Above 45 PSIG requires pressure regulator and relief valve.

• 

Is the station’s steam supply line properly sized? (Recommended min. 1” IPS)

• 

Does the plant have adequate Water Flow Pressure? (min. 55 PSIG while flowing 25 GPM.)

• 

Is the station’s water supply line properly sized? (Recommended min. 1-1/4” IPS)

• 

Is the station’s supplying tepid water to anything other than the Safety Shower Station?  

NOTE: Water flow from heater must be dedicated to safety shower/eyewash.

• 

Are freeze and scald protection valves installed correctly?

• 

Is the water supply line in contact with or being overheated by another source?

• 

Is the condensate properly sized? Is the condensate blocked?

Содержание THERM-O-MIX STATION

Страница 1: ...THERM O MIX STATION Troubleshooting Manual Technical Support 1 800 766 5612 Customer Service 1 888 640 4297 D...

Страница 2: ...ment 6 3 2 Decommissioning the unit for Troubleshooting 6 3 3 Decommissioning the unit for Repairs 6 3 4 Decommissioning Images 7 4 0 Adjustments and Repairs 4 1 V1 Mixing Valve 8 4 2 V2 Capillary Val...

Страница 3: ...iaphragm closing V3 and turning steam flow off V5 normally open pre mixes cold water with hot water from heat exchanger prior to mix entering the V1 mixing valve V6 normally closed starts to open when...

Страница 4: ...team flow based on water temperature from HtEx 4 Hot water from HtEx enters V5 pre mixing valve and mixes with cold inlet water 5 The hot water enters V1 mixing valve and mixes with more cold inlet wa...

Страница 5: ...runs in the normal range Note Steam will probably be coming out of the drain line while running the eyewash The V2 Capillary Valve needs to be adjusted See Section 4 2 If the valve cannot be ad justed...

Страница 6: ...control 80 F output assume V4 cannot close V3 so V4 has no effect Steam will leak from the drain line even when the shower eyewash unit is not activated Large water leaks over 1 GPM down stream would...

Страница 7: ...ommissioning The Unit for Troubleshooting 1 Close the unit s steam supply valve 2 Activate the shower and eyewash system for a minimum of two minutes to deplete the steam pressure trapped between the...

Страница 8: ...Page 7 V3 Indicator Open Position Closed Position V2 Capillary Valve O Ring O Ring Indicator Section 3 4 Decommissioning Images...

Страница 9: ...ide is fully closed Place valve into an 80 F water bath for five minutes 6 Use calibration screw to adjust the valve spool so that the inner spool hot water slots line up with outer housing hot water...

Страница 10: ...nt part from ThermOmegaTech Section 4 2 V2 Capillary Valve V2 Capillary Valve Adjustment 1 On the end of the heat dissipater nearest V2 valve body there are four setscrews holding the perforated heat...

Страница 11: ...a water bath at 85 F or below for five minutes 4 If you blow compressed air into the lower straight hose adapter it should be closed 5 If the valve does not work correctly a replacement V4 Control Val...

Страница 12: ...nto normal flow direction check valves will prevent reverse flow Cleaning solution must remain below 80 F The cleaning time needed depends on local water conditions and frequency of cleaning After the...

Страница 13: ...Page 12 Appendix 1 Station Schematic...

Страница 14: ...Appendix 2 Station Operating Logic Flow Chart Page 13...

Страница 15: ...Page 14 Appendix 3 Typical Installation Schematic...

Страница 16: ...Appendix 4 Labeled Station Line Drawing Page 15...

Страница 17: ...Page 16 Appendix 5 Hoses and Hose Fittings Line Drawing...

Страница 18: ...wn to the State of CA to cause cancer birth defects or reproductive harm For more information go to www P65Warnings ca gov ThermOmegaTech Inc 353 Ivyland Road 1 877 379 8258 Warminster PA 18974 www Th...

Отзывы: