Temp
Control
|
17
16
|
Temp
Control
THX-DL Operation
THX-DL Operation
4.5 Door On/Off
From the Main Screen, press the key to select Settings from the main menu.
Confirm selection using the key to reveal the Settings Menu. Select Door On/Off from the menu and press the key to confirm.
The status of 12 doors can be configured to be switched ON or OFF. As a factory default, all 12 doors are switched OFF.
To switch a door off, press the key. To switch a door back on, press the key.
4.6 Door Setup
From the Main Screen, press the key to select Settings from the main menu.
Confirm selection using the key to reveal the Settings Menu.
Scroll down using the key to the second page of the menu, select Door Setup from the menu and press key to confirm.
The Door Setup is purely for display/graphing purposes only.
It allows the user to associate any channel with any number of
digital inputs, e.g., doors.
The user can select any channel from screen 4.6 using and keys and pressing the key to confirm.
To set which door inputs are associated with each channel use the and keys to select a door input and use
the key to select and the key to deselect.
Indicates that the digital input is associated with the selected channel.
Indicates that the digital input is not associated with selected channel.
Indicates that the status of the door is OFF.
Note
The user cannot set the door input association if a door is turned off (see 4.5)
4.7 Relay Setup
From the Main Screen, press the key to select Settings from the main menu.
Confirm selection using the key to reveal the Settings Menu. Scroll down using the key to the second page of the menu,
select Relay Setup from the menu and press the key to confirm.
This feature allows the user to associate any channel with a number
of relay outputs, e.g., alarm relays. If channel 1 goes into fault
mode, each alarm associated with channel 1 will be triggered.
The user can select any channel from screen 4.7 using and keys and pressing the key to confirm.
To set which channel is associated with each relay use the and keys to select a channel and use the key to select
and the key to deselect.
Note:
Every channel can be configured to work with each relay.
4.8 Relay Normally Closed/Normally Open
From the Main Screen, press the key to select Settings from the main menu.
Confirm selection using the key to reveal the Settings Menu. Scroll down using the key to the second page of the menu,
select Relay N/C – N/O from the menu and press the key to confirm.
The default state of each relay is set to normally closed (N/C). The user can change the setting of individual relays to be N/O or N/C.
N/C
Normally Closed Operation. This is the default mode. The relay outputs will make contact in the event of an alarm or power failure.
N/O
Normally Open Operation. In this mode, the relay outputs will break contact (open circuit) in the event of an alarm and make contact
(closed circuit) in the event of power failure.
To change the setting of each relay to normally closed, press the key.
To change the setting back to normally open, press the key.
OK
OK
OK
▲
▼
OK
▲
▲
▼
▼
OK
OK
▼
▼
OK
OK
▼
▼
▲
▼
OK
▲
▼
OK
▼
▲
▼
▼
▼
▲
▼
▲
▼