background image

Temp

Control

 

|

 19 

18 

|

 

Temp

Control

THX-DL Operation

THX-DL Operation

4.9 Calibration

From the Main Screen, press the           key to select Settings from the main menu. 
 
Confirm selection using the           key to reveal the Settings Menu. Scroll down using the           key to the second page of the menu, 
 
select Calibration from the menu and press the           key to confirm.

To enter the Calibration Trimming screen, press and hold the           key for 8 seconds.

Calibration trimming allows qualified personnel to adjust the Sensor Measurement by ±3°C / ±3%rH. A known reference value 
should be used. 
 
Use the                     keys to move to the channel that requires calibration trimming. Then use the           or           key to adjust the current 
temperature reading to the reference value read at the input. 

4.10 Network

From the Main Screen, press the           key to select Settings from the main menu. 
 
Confirm selection using the           key to reveal the Settings Menu. Scroll down using the           key to the second page of the menu, 
 
select Network from the menu and press the           key to confirm.

Please enter your network details or choose DHCP for Automatic Network Configuration. 
 
To set Automatic Network Configuration, use the           key to select DHCP and use the           key to select or deselect this option.

 

Indicates that the DHCP is OFF.

 

Indicates that the DHCP is ON.

Select                      and use the           key to save the settings.

5.0 PLOT

5.1  Current Day

From the Main Screen, press the           key to select Plot from the main menu. 
 
Confirm selection using the           key to reveal the Plot Menu. Select Current Day from the menu and press the           key to confirm.

This screen displays the plot of the temperature / humidity readings 
logged for the current day.

The user can select any channel from screen 5.1, using the          
 
and           keys and pressing the           key to confirm. 
 
The user can read sample information using the           and           keys.

OK

OK

OK

OK

OK

OK

OK

OK

OK

Содержание THX-DL

Страница 1: ...USER INSTALLATION MANUAL V3 2016 www thermomax refrigeration com THX DL Data Logger Refrigeration...

Страница 2: ...sentation SUMMARY OF FEATURES Datalogger Temperature humidity from each Channel can be set to sample every 1 5 15 30 60 minutes and stored to an internal databank Up to 12 channels of data logging can...

Страница 3: ...of lengths If the sensors need to be extended but factory made extenders are not available they can be extended using a suitable 3 or 4 core cable according to the diagram shown below Please note howe...

Страница 4: ...tied in it It will not be possible to push the cord into the device to such an extent that it will cause a hazard Should the cord insulation fail in an anchorage that has metal parts none of the expo...

Страница 5: ...so be sent in the event of loss of power from the THX DL It is the customers responsibly to keep power to the network infrastructure March 2015 3 How do I test the new Email feature Brief Set up summa...

Страница 6: ...mmary Screen This screen displays the current temperature humidity readings of each of the connected channels and indicates if that channel is in alarm or not The key will return the user to the previ...

Страница 7: ...daily maximum and minimum temperature which are reset at midnight 3 0 ALARM SETTINGS From the Main Screen press the key to select Alarms Settings from the main menu Confirm selection using the key to...

Страница 8: ...se press key If a channel is switched off the alarm parameters will automatically revert back to the default factory settings to prevent an alarm occurrence These parameters cannot be changed until th...

Страница 9: ...ain Screen press the key to select Settings from the main menu Confirm selection using the key to reveal the Settings Menu Scroll down using the key to the second page of the menu select Relay Setup f...

Страница 10: ...om the main menu Confirm selection using the key to reveal the Settings Menu Scroll down using the key to the second page of the menu select Network from the menu and press the key to confirm Please e...

Страница 11: ...ct the date and press the key to confirm Display the door information by selecting SHOW DOOR from the pop up menu and pressing the key to confirm View the information of any door by using the keys 6 0...

Страница 12: ...m the main menu Confirm selection using the key The language used by the THX to communicate the information may be selected here i e English German or French Use the or key to select the required lang...

Страница 13: ...urrently selected channel The MODULE window shows the number of the currently selected module The INPUT TYPE window shows which type of sensor is being used The CALIB DATA window shows calibration val...

Страница 14: ...ey to start upload previously downloaded settings from the memory stick Do not remove the memory stick until the progress bar disappears 4 Service For use only by authorised personnel and trained inst...

Страница 15: ...ontrol Web Server Web Server 1 Live Data Live data screen displays the current temperature humidity readings of each of the connected channels and indicates if that channel is in alarm or not The stat...

Страница 16: ...e To change the date and time use the and click on the button to save the changes 6 Graph Graph screen allow user to generate multiple channel graph To generate the graph set the date choose the chann...

Страница 17: ...t 100mm depth 180mm weight 1 4kg sensor each 0 13kg Box Material Plastic Display Large LCD with backlight SENSORS Type SX PT 100 Platinum Film Compensation 3 wire compensated Cable Length A variety of...

Страница 18: ......

Страница 19: ...ght to alter specifications and drawings without prior notice Issue No 3 July 2016 019264 Head Office Kingspan Environmental 180 Gilford Road Portadown Co Armagh BT63 5LF Tel 44 0 28 3836 4400 UK Sale...

Отзывы: