background image

Mains supply failure 

The heater switches off in the event of a mains supply failure and the upper bar of the  
display flashes. The device resumes its previous operation if the mains voltage is restored within 
approx. 1 to 1 ½ days. If the mains supply failure is longer, the time and weekday must be reset and 
the 'E' user program may have to be re-entered. The set-back temperature must also be 
reprogrammed if this was altered. 

 

Short-circuit or interruption in the sensor line: 

The heating system is disconnected and the LED 

flashes. 

CAUTION:

 In the event of a fault, the mains voltage may still be present on the sensor line 

 

Special master controllers for connecting satellites  

All controllers listed can be supplied as master controllers for connecting satellites. The TA output can 
be used to connect virtually any number of clockless temperature controllers, e.g. commercially 
available bimetal controllers with their L set-back input TA as satellites. If the master controller with its 
timer switches to set-back operation, all satellites do the same.  
 

Troubleshooting 
Diagnosis 

Possible cause 

Solution 

No display visible

  

 

 

Heating system not switched on 

 
 

 
Heating system does not switch 

on, the entire display flashes 
 

Heating system does not switch 
on, LED flashes 

 
Device is not working correctly 

Mains voltage not connected 
 

 
Device possibly on setback mode or 

floor monitor has responded 
 

 
Mains supply failure 

 
 

Floor temperature sensor faulty 
 

 
Device fault caused by lightning or 

overvoltage 

Switch on mains voltage 
 

 
Check setback mode or wait until 

the floor has cooled down 
 

 
Check mains voltage 

 
 

Replace floor temperature sensor 
 

 
Press Reset button, reset the 

device 
 

 

Your personal 'E' user program 

 
 

 

Mon ... Fri 

Sat, Sun  

 

 

 
No. E 

 

......................... 

......................... 

 

 
 
 

 

Содержание HRT 6015-50

Страница 1: ...ntroller 10 to 60 C Room temperature controller 5 to 30 C Room temperature controller 5 to 30 C with floor temperature monitoring Room temperature controller 5 to 30 C Floor temperature controller 10...

Страница 2: ...floor or convectors supplementary heating for floor background heating in bathrooms electrical perimeter heating or warm water heating with control valves The controlled variable is either the room te...

Страница 3: ...duit box When using additional intermediate terminals the use of a deep conduit box is recommended Mounting height Approx 1 5 m above floor Avoid exposure to water When used as a room temperature cont...

Страница 4: ...tion Figure 3 and 4 L N PE T A F F NL 1NL Heating NTC 230V mains supply Floor temperature sensor Master output optional L N PE TA F F NL 1N L NTC 230V mains Floor temperature sensor Heating mat Master...

Страница 5: ...ler 10 to 60 C For changes see Changing controller options If you have moved a jumper or changed the rotary switch setting on the universal controller the Reset button must be pressed after the und co...

Страница 6: ...constant by the controller At the other times the device regulates the temperature to the setback temperature value i e the heating is switched back on if it goes below the defined setback temperatur...

Страница 7: ...on the display Hold down the C button and press the button You can now release the C button and set the time with the or buttons Holding the button down for a long time first changes the setting slowl...

Страница 8: ...ashing quickly by pressing the or button Change the bar by pressing the C button The next bar will then flash and can likewise be changed In this way all the bars can be switched from setback to heati...

Страница 9: ...am is changed Turn the adjustment dial back to the required heating temperature and if necessary move up the slide switch to the clock position Min set back temperature on floor temperature controller...

Страница 10: ...a controller option is changed The change is activated automatically after approx 60 to 90 secs If necessary reset the personal E user program and the set back temperature Reset button Pressing the Re...

Страница 11: ...ellites The TA output can be used to connect virtually any number of clockless temperature controllers e g commercially available bimetal controllers with their L set back input TA as satellites If th...

Страница 12: ...Reservation of right Subject to technical modifications Compensation cannot be claimed on account of modifications errors or print errors...

Отзывы: