THERMOBILE IMAC 2000 PELLET Скачать руководство пользователя страница 15

 

THERMOBILE INDUSTRIES BV 

INSTRUCTIONMANUAL PELLETHEATER                                                   

 15

 

TROUBLESHOOTING

 

Make sure the electric power supply is switched off and the fuel tank is full, before you start  
troubleshooting. 
  

Warning 

Switch off the power supply before carrying out any repairs!  

 

6.1 

Troubleshooting table 

 

Fault

 

 

Cause

 

Solution

 

Action

 

The convector 
heater does not 
start up.

 

1

 

The convector heater is not  live.

 

Check the electrical connections.

 

User

 

2

 

The burner is not working.

 

Press the reset button in the operating 
panel. See fig 4.

 

User

 

3

 

The thermostat has not been set 
correctly.

 

Correct the settings.

 

Dealer

 

4

 

The room thermostat is defective.

 

Replace the thermostat.

 

User

 

5

 

There is no cap on the thermostat 
connection.

 

Replace the cap if the room thermostat is 
not in use.

 

User

 

6

 

The pellet hose is not connected 
correctly 

Check Pellet hose 

User

 

7

 

The maximum thermostat is stopping 
the convector heater.

 

Check (and correct) the air flow. Reset 
the convector heater.

 

User

 

8

 

The digital combination thermostat is 
defective.

 

Replace the combination thermostat.

 

Dealer

 

9

 

The capacitor of the burner motor is 
defective.

 

Replace the capacitor.

 

Dealer

 

11

  The exhaust air fan is not working. 

Check and clean the exhaust air fan 

User 

12

 

The room thermostat has been 
placed in the hot-air flow.

 

Install the room thermostat away from the 
hot-air flow.

 

User

 

13  The dooron the burnerside is not 

closed correctly. 

Check and close the door. 

User 

14  The cleaning door in the 

heatexchanger is not closed 
correlctly . 

Check and close the door. 

User 

The fan is starting 
up immediately.

 

13

 

The fan thermostat has not been set 
correctly. Out 1.

 

Correct the settings. See malfunction 9.

 

Dealer

 

The convector 
heater is starting 
up, but no flame is 
forming.

 

14

  The pellet auger is not working 

Check and correct 

User 

15

 

The flame sensor is dirty or 
defective.

 

Check the flame sensor and replace if 
necessary. See Burner Manual.

 

Dealer

 

16  The exhaust air fan is not working 

correctly 

Check and clean the exhaust air fan 

User 

17

 

Exhaust opening or flue connection 
is in poor condition.

 

Connect the convector heater to a flue 
that is in good condition. Correct the 
connections.

 

User

 

18  The igniter is not working. 

Check and replace 

Dealer 

The burner is 
starting up poorly 
(stutters).

 

19

 

There are problems in the burner 
room or heat exchanger.

 

Clean the burner room and heat 
exchanger, if necessary.

 

User

 

The convector 
heater burns 
intermittently.

 

21

 

The burner thermostat has not 
been set correctly. Out 2.

 

Set the burner thermostat according to 
the manufacturer's specifications.

 

Dealer

 

The convector 
heater stops.

 

22

 

An overheating problem has occurred 
in the convector heater.

 

Reduce the resistance at the outlet.

 

User

 

Reset the thermostat.

 

User

 

Contact the dealer if the error is repeated.

 

Dealer

 

 

 

Содержание IMAC 2000 PELLET

Страница 1: ...bile co uk www thermobile co uk THERMOBILE FRANCE sarl 3 rue Denis Papin 45240 LA FERTÉ ST AUBIN Frankrijk T 33 0 2 38 76 59 25 F 33 0 2 38 76 58 93 info thermobile fr www thermobile fr THERMOBILE INDUSTRIES V Konijnenberg 80 4825 BD Breda Nederland Postbus 3312 4800 DH Breda Nederland Bedrijfsnummer 3502 T 31 0 76 587 34 50 F 31 0 76 587 27 89 info thermobile com www thermobile com THERMOBILE IMA...

Страница 2: ...THERMOBILE INDUSTRIES BV INSTRUCTIONMANUAL PELLETHEATER 2 A B C Fig 1 Fig 2 Fig 3 Fig 4 ...

Страница 3: ...THERMOBILE INDUSTRIES BV INSTRUCTIONMANUAL PELLETHEATER 3 ...

Страница 4: ...ERMOBILE INDUSTRIES BV INSTRUCTIONMANUAL PELLETHEATER 4 MAX OPERATING DISTANCE 20M 1 CONTAINER 10ft 2 MAULWURF 3 PELLET SUCTION HOSE 4 HEATER 7 PELLETSTORAGE 6 ASHCONTAINER 5 EXHAUST FAN 8 AIR HOSE Fig 6 ...

Страница 5: ...STRUCTIONMANUAL PELLETHEATER 5 Fig 8 Installation exhaust fan In case no external thermostat is used the cap must be placed in the connector as shown Mounting the ash auger Positioning and mounting the ash bin Fig 7 Fig 10 Fig 11 ...

Страница 6: ...container Connecting the 10ft container to the temporary pellet storage Power to maulwurf Pellets from 10ft container Air to 10ft container Power Mounting the Pellet slide Power pellet auger Pellet Installation temporary pellet storage connecting the Maulwurf mounting the Pelletslide Fig 12 Fig 13 Fig 14 ...

Страница 7: ...HEATER 7 Contents Safety instructions 8 Introduction 9 Preparations and main components 10 Operation 11 Maintenance 11 Troubleshooting 12 Spareparts 13 Technical information 13 Installation of accessories 13 EC Declaration of conformity 13 APENDIX 14 ...

Страница 8: ...the convector heater Warranty and liability For warranty and liability please refer to the general warranty conditions Environment Note The heater is made of various metals and synthetic materials The heater also contains electronic parts which must be treated as electronic waste Please contact your dealer for further information Only applicable to the European Union Waste disposal of electric ele...

Страница 9: ...ns Warning Make sure to read this manual carefully before using the convector heater Keep this document near the convector heater Follow the procedures described Do not lean on the convector heater Keep at least 2 meters away from the exhaust opening of the convector heater Make sure there is sufficient air for proper combustion Make sure there is no highly flammable material near the convector he...

Страница 10: ...reached After that burner stops safely burning procedure and goes to waiting stand by status Main supply interruptions blackouts are taken care of by the control system After a main supply interruption burner stops safely burning and goes to stopped status When a blackout occurs the burner ends safely burning process If there is a safety risk the burner switches off 2 3 Main components of the conv...

Страница 11: ...at will switch on the main ventilator as soon as the convector heater has reached the preset temperature After switching off the convector heater the ventilator will continue to run The ventilator will cool down the convector heater to prevent damage by overheating The ventilator will automatically stop Burner thermostat The thermostat will stop the burner as soon as the temperature of the hot air...

Страница 12: ... of 25 cm2 is required 8 Check the connection of the room thermostat 9 Make sure the convector heater is switched off See fig 4 10 Check the power supply refer to the identification plate 11 Connect the convector heater to the socket of the electric power supply The indicator light Panel live is on white 12 If necessary press pushbutton Reset burner See fig 4 13 Reset the thermostat See fig 4 Caut...

Страница 13: ...he plug from the socket until the fan has stopped completely 2 Remove the electrical plug To switch off the ventilation 1 Switch the rotary switch to position 0 See fig 4 2 Remove the electrical plug 4 3 Transport after use 1 Switch off the convector heater and wait until the fan has stopped completely 2 Switch off the power supply 3 Remove the connection from the room thermostat and place the cap...

Страница 14: ...hamber and heat exchanger 2 times a week 2000 kg pellets Check and clean exhaust air fan 2 times a week 2000 kg pellets Check ash container and if necessary empty it Weekly Check burner and clean burner Every two months Hot Do not touch the flue and air outlet Wait until the flue and the air outlet have cooled down sufficiently before carrying out any maintenance General Warning Switch off the pow...

Страница 15: ...stall the room thermostat away from the hot air flow User 13 The dooron the burnerside is not closed correctly Check and close the door User 14 The cleaning door in the heatexchanger is not closed correlctly Check and close the door User The fan is starting up immediately 13 The fan thermostat has not been set correctly Out 1 Correct the settings See malfunction 9 Dealer The convector heater is st...

Страница 16: ...to the Pelletstorage The maximum distance between them is 20meters It is important that the Pellet storage is leveled correctly 9 3 Ashcontainer Fig 11 Set the Ashcontainer correctly 9 4 Pellet transport hose and Pellet connection hose Fig 12 13 14 Between the 10ft container and the pellet storage the Pellet transport hose is connected This is a firm hose that can t be blocked easily The Pellet st...

Страница 17: ...ncy Fréquence Hz 50 Fan thermostat Ventilator Thermostat du ventilateur C 40 Brander thermostaat Burner Thermostat du brûleur C 100 Maximaal thermostaat Maximal Thermostat maximal C 110 Dust mg m 30 CO ppm 129 Length Länge Lengte Longueur Longitud Lengde mm 2400 Width Breite Breedte Largeur Ancho Bredde mm 800 Height Höhe Hoogte Hauteur Alto Høyde mm 1370 Outlet mm Ø 500 Weight kG 550 Fan Ventilat...

Страница 18: ...Parameters adjustment Thermobile Warning These settings are pre programmed by Thermobile It is very unwise to change them PAR 05 45 PAR 06 48 PAR 21 85 PAR 22 80 PAR 23 92 PAR 27 250 PAR 30 1 PAR 34 45 PAR 35 50 PAR 36 55 PAR 38 125 Restore Factory Settings Go to Par 99 select type of burner PV 100 and confirm with OK Then select burner PV 180 and confirm with OK Burner is now put back to factory ...

Страница 19: ...urner out at 100 C fan still on wait till temperature is below 80 C than burner start automatically Burner goes on and off cause is mostly too much resistance in the outlet 3 1 3 leds high temperatur lamp on okè 2 High temperature 3 Burner out and does not start automatically 4 Wait till the temperature is below 80 C and than reset 1 1 led high temperature lamp on okè 2 High temperature Reset Jumo...

Страница 20: ...raction motor direction 2 1 1 8 Sec Pause time extraction motor direction 2 1 1 9 Number of repetition cycle 2 3 3 10 h min Time unit of parameter pause time in hours or minutes 0 min 1 hours 1 0 Par 2 must be set according to the length of the extraction system If this time is set to long there will be too much pellets in the cyclone separator In that case the filter will be blocked This can lead...

Страница 21: ...THERMOBILE INDUSTRIES BV INSTRUCTIONMANUAL PELLETHEATER 21 APPENDIX E ...

Страница 22: ...THERMOBILE INDUSTRIES BV INSTRUCTIONMANUAL PELLETHEATER 22 ...

Страница 23: ...e Fecha Dato Omschrijving Onderhoud of Storing Description Maintenance or Failure Beschreibung Wartung oder Fehler Description Entretien ou Erreur Descripcíon Mantenimiento o fallo Beskrivelse Vedlikehold eller feil Actie door Action by Aktion durch Action par Accíon por Handling foretas av ...

Страница 24: ...noch in irgendeiner Weise durch Drucken elektronisch oder mechanisch veröffentlicht werden 2016 Thermobile Industries B V Tous les droits réservés L ensemble des informations disponibles a été préparé avec un soin extrême Cependant Thermobile Industries B V décline toute responsabilité à l égard des erreurs possibles ou de leurs conséquences Les informations fournies ici ne peuvent être reproduite...

Отзывы: