THERMOBILE INDUSTRIES BV
INSTRUCTIONMANUAL PELLETHEATER
15
6
TROUBLESHOOTING
Make sure the electric power supply is switched off and the fuel tank is full, before you start
troubleshooting.
Warning
Switch off the power supply before carrying out any repairs!
6.1
Troubleshooting table
Fault
Cause
Solution
Action
The convector
heater does not
start up.
1
The convector heater is not live.
Check the electrical connections.
User
2
The burner is not working.
Press the reset button in the operating
panel. See fig 4.
User
3
The thermostat has not been set
correctly.
Correct the settings.
Dealer
4
The room thermostat is defective.
Replace the thermostat.
User
5
There is no cap on the thermostat
connection.
Replace the cap if the room thermostat is
not in use.
User
6
The pellet hose is not connected
correctly
Check Pellet hose
User
7
The maximum thermostat is stopping
the convector heater.
Check (and correct) the air flow. Reset
the convector heater.
User
8
The digital combination thermostat is
defective.
Replace the combination thermostat.
Dealer
9
The capacitor of the burner motor is
defective.
Replace the capacitor.
Dealer
11
The exhaust air fan is not working.
Check and clean the exhaust air fan
User
12
The room thermostat has been
placed in the hot-air flow.
Install the room thermostat away from the
hot-air flow.
User
13 The dooron the burnerside is not
closed correctly.
Check and close the door.
User
14 The cleaning door in the
heatexchanger is not closed
correlctly .
Check and close the door.
User
The fan is starting
up immediately.
13
The fan thermostat has not been set
correctly. Out 1.
Correct the settings. See malfunction 9.
Dealer
The convector
heater is starting
up, but no flame is
forming.
14
The pellet auger is not working
Check and correct
User
15
The flame sensor is dirty or
defective.
Check the flame sensor and replace if
necessary. See Burner Manual.
Dealer
16 The exhaust air fan is not working
correctly
Check and clean the exhaust air fan
User
17
Exhaust opening or flue connection
is in poor condition.
Connect the convector heater to a flue
that is in good condition. Correct the
connections.
User
18 The igniter is not working.
Check and replace
Dealer
The burner is
starting up poorly
(stutters).
19
There are problems in the burner
room or heat exchanger.
Clean the burner room and heat
exchanger, if necessary.
User
The convector
heater burns
intermittently.
21
The burner thermostat has not
been set correctly. Out 2.
Set the burner thermostat according to
the manufacturer's specifications.
Dealer
The convector
heater stops.
22
An overheating problem has occurred
in the convector heater.
Reduce the resistance at the outlet.
User
Reset the thermostat.
User
Contact the dealer if the error is repeated.
Dealer
Содержание IMAC 2000 PELLET
Страница 2: ...THERMOBILE INDUSTRIES BV INSTRUCTIONMANUAL PELLETHEATER 2 A B C Fig 1 Fig 2 Fig 3 Fig 4 ...
Страница 3: ...THERMOBILE INDUSTRIES BV INSTRUCTIONMANUAL PELLETHEATER 3 ...
Страница 21: ...THERMOBILE INDUSTRIES BV INSTRUCTIONMANUAL PELLETHEATER 21 APPENDIX E ...
Страница 22: ...THERMOBILE INDUSTRIES BV INSTRUCTIONMANUAL PELLETHEATER 22 ...