Condenser Filter
Failure to clean/replace the condenser filter will cause a loss of
cooling capacity and lead to premature cooling system failure .
ThermoFlex900 - 5000
Clean the filter through the grill using a vacuum with a soft-bristle brush.
When it is time for a more thorough cleaning, remove the one-piece grill
assembly by first pulling the bottom of the assembly away from the chiller
and then pulling it away from the top.
The condenser framing and fins located behind the grill assembly
are very sharp. Use caution when removing the assembly.
Note
ThermoFlex900 - 5000 water-cooled chillers have an embedded
screw(s) located at the top (and bottom) of the grill. Loosen the screw(s)
to remove the grill.
Water-cooled chillers also have a fan with sharp blades, ensure the
chiller is off before removing the assembly.
Shake off as much of the excess water as possible before reinstalling. Press
the grill back into place.
For water-cooled chillers, tighten the screw(s) at the top (and bottom) of
the grill.
Replacement grill assemblies are available from Thermo Fisher.
Screw
(Water-cooled
chillers)
CAUTION
- Sharp edges
Figure 6-3
ThermoFlex900 - 5000 Condenser Grill Removal
ThermoFlex3500 - 5000 water-cooled chillers have
two screws securing the condenser. One screw on
the top and one on the bottom.
WARNING
WARNING
CAUTION
Содержание ThermoFlex10000
Страница 2: ......
Страница 36: ...ThermoFlex900 5000 Thermo Scientific...
Страница 42: ...DI SDS 4 0 gpm 15 1 lpm ThermoFlex900 5000 Thermo Scientific...
Страница 79: ...517 2014 16 2014 ThemoFlex24000...
Страница 100: ...Section 2 2 20 ThermoFlex Thermo Scientific...
Страница 136: ...Section 4 4 14 ThermoFlex Thermo Scientific...
Страница 168: ...Section 7 7 14 ThermoFlex Thermo Scientific...
Страница 191: ...C 10 ThermoFlex Appendix C Thermo Scientific...
Страница 208: ......
Страница 209: ......
Страница 210: ...Thermo Fisher Scientific 168 Third Avenue Waltham Massachusetts 02451 United States www thermofisher com...