ThermoFlex 5-1
Thermo Scientific
Auto Refill
The auto refill fluid must also meet water quality standards or the valve may
fail to operate as designed, see Section 3.
The auto refill valve input pressure must be < 80 PSI to ensure the valve
functions properly.
The auto refill operates when all of the following conditions are met:
• Fluid is available
• The chiller is turned on
• The fluid reaches a low level condition.
The auto refill shuts off when:
• The fluid reaches the correct operating level.
• The delay timer exceeds user fill time entered in the Setup Loop, see
Section 4. If
FLt
is selected in the Setup Loop the chiller also shuts
down. (If
indC
is selected the chiller continues to run.) In either case
the controller will display
rEFIL
.
• The chiller shuts down for any reason.
Setting the fill time to 0 disables auto refill. If a low level condition occurs
the chiller will:
• If
Indc
is selected, continue to run and the controller displays
Add
.
• If
FLt
is selected, shut down and the controller displays
LLF
.
Figure 5-1
Auto Refill Fitting
Section 5
Options/Accessories
The Auto Refill provides makeup fluid to replace any fluid lost to evaporation,
etc. It requires a pressurized fluid source connection to the ¼" Female Pipe
Thread fitting on the rear of the chiller. (If Teflon
®
tape is used, ensure the
tape does not cover the connection's starting-end thread.)
Note
ThermoFlex7500 through 24000s with a P3 or P5 or ThermoFlex7500s
and 10000s with a T5 pump have a ¼" Male brass plug installed in the
connection, remove the plug before connecting the makeup fluid.
Содержание ThermoFlex10000
Страница 2: ......
Страница 36: ...ThermoFlex900 5000 Thermo Scientific...
Страница 42: ...DI SDS 4 0 gpm 15 1 lpm ThermoFlex900 5000 Thermo Scientific...
Страница 79: ...517 2014 16 2014 ThemoFlex24000...
Страница 100: ...Section 2 2 20 ThermoFlex Thermo Scientific...
Страница 136: ...Section 4 4 14 ThermoFlex Thermo Scientific...
Страница 168: ...Section 7 7 14 ThermoFlex Thermo Scientific...
Страница 191: ...C 10 ThermoFlex Appendix C Thermo Scientific...
Страница 208: ......
Страница 209: ......
Страница 210: ...Thermo Fisher Scientific 168 Third Avenue Waltham Massachusetts 02451 United States www thermofisher com...