Operation
Programming
Figure 3–1.
Jumper selection
Table 3–1.
Uses this
Supply pressure
Jumper select switch position
Output
E-Pi
Input (mA)
Standard
High
pressure
Direct
Reverse Range
1:1
Range
1:2
Adjust
3–15 psig
3–15 psig
3–15 psig
SA45-1502-15
SA45-1502-15
SA45-1502-15
4–20 or 10–50
4–20 or 10–30
12–20 or 30–50
20 psig
20 psig
20 psig
35–100 psig
35–100 psig
35–100 psig
x
x
x
x
x
x
Zero
Zero
Zero
15–3 psig
15–3 psig
15–3 psig
SA45-1502-15
SA45-1502-15
SA45-1502-15
4–20 or 10–50
4–12 or 10–30
12–20 or 30–50
20 psig
20 psig
20 psig
35–100 psig
35–100 psig
35–100 psig
x
x
x
x
x
x
Zero
Zero
Zero
3–27 psig
1,2
27–3 psig
SA45-1502-27
SA45-1502-27
4–20 or 10–50
4–20 or 10–50
35 psig
35 psig
N/A
N/A
x
x
x
x
Zero
Zero
6–30 psig
1,3
30–6 psig
SA45-1502-30
SA45-1502-30
4–20 or 10–50
4–20 or 10–50
35 psig
35 psig
N/A
N/A
x
x
x
x
Zero
Zero
1–17 psig
1–17 psig
1–17 psig
SA45-1502-17
SA45-1502-17
SA45-1502-17
4–20 or 10–50
4–12 or 10–30
12–20 or 30–50
35 psig
35 psig
35 psig
N/A
N/A
N/A
x
x
x
x
x
x
Zero
Zero
Zero
17–1 psig
17–1 psig
17–1 psig
SA45-1502-17
SA45-1502-17
SA45-1502-17
4–20 or 10–50
4–12 or 10–30
12–20 or 30–50
35 psig
35 psig
35 psig
N/A
N/A
N/A
x
x
x
x
x
x
Zero
Zero
Zero
1
Units with output ranges of 3–27 or 6–30 psig are programmed for 1:2 mode to achieve output range.
2
Units factory calibrated for 3–27 psig can be converted to a 3–15 psig output range by changing mode selection from 1:2 to 1:1 and recalibrating.
However, reducing supply pressure to 20 psig may cause the pneumatic zero to drop; attempt to use the unit at 35 psig supply first.
3
Units factory calibrated for 6–30 psig may have a pneumatic zero too high to recalibrate to 3–15. You can attempt to recalibrate by changing mode
selection from 1:2 to 1:1. If this does not work, send the unit to Thermo Fisher for recalibration or replace the 6–30 psig E-Pi module with a 3–15 psig
module.
3-2
STD5000 & STD6000 User Guide
Thermo Fisher Scientific
Содержание STD5000
Страница 1: ...STD5000 STD6000 Current to Pressure Transducers User Guide P N MA45 5600 00 Revision...
Страница 2: ......
Страница 4: ...This page intentionally left blank...
Страница 6: ...This page intentionally left blank...
Страница 8: ...This page intentionally left blank...
Страница 18: ...This page intentionally left blank...
Страница 24: ...This page intentionally left blank...
Страница 32: ...This page intentionally left blank...
Страница 34: ...This page intentionally left blank...
Страница 40: ...Specifications Figure C 1 I S installation drawing C 4 STD5000 STD6000 User Guide Thermo Fisher Scientific...
Страница 43: ...Specifications Figure C 2 Thermo Fisher Scientific STD5000 STD6000 User Guide C 7...