Installation & Wiring
Pneumatic Connections
Figure 2–3.
Pneumatic
Connections
neumatic
Connections
Note
Note the following PRIOR TO making any pneumatic connections:
●
Blow out lines thoroughly.
●
Soap test all joints and fittings for leaks.
●
Do not use pipe thread tapes on pneumatic piping.
▲
Refer to the dimensional drawings and the following:
1.
One ¼-inch FNPT port is provided for supply air connections. Each
unit has a filter screen installed in this port.
2.
Two ¼-inch FNPT ports are provided for pneumatic output
connections. Either port may be used and one may be used for the
mounting of an output gauge. Plug the unused port with the pipe plug
included with the unit. Note that the pipe plugs are certified and
suitable for the maintenance of the product’s certification rating and
protection concept.
Thermo Fisher Scientific
STD5000 & STD6000 User Guide
2-3