Troubleshooting & Support
Replacing the CCB
Replacing the CCB
Caution
If this procedure is performed in the field, ensure no contaminates
enter the unit.
▲
1.
Refer to Figure 6–1. Cut off the air supply.
2.
Remove the cover. Remove the E-Pi according to
“Replacing the E-Pi.”
3.
Disconnect the input leads.
4.
Remove the four screws holding the CCB in the manifold.
Note
The replacement CCB should have an O-ring around the pressure
sensor mounted to the CCB. Another O-ring is in the recessed hole where
the pressure sensor plugs in. Do not discard.
▲
5.
Mount the new CCB by reversing these steps.
Figure 6–1.
CCB assembly
6-2
STD5000 & STD6000 User Guide
Thermo Fisher Scientific
Содержание STD5000
Страница 1: ...STD5000 STD6000 Current to Pressure Transducers User Guide P N MA45 5600 00 Revision...
Страница 2: ......
Страница 4: ...This page intentionally left blank...
Страница 6: ...This page intentionally left blank...
Страница 8: ...This page intentionally left blank...
Страница 18: ...This page intentionally left blank...
Страница 24: ...This page intentionally left blank...
Страница 32: ...This page intentionally left blank...
Страница 34: ...This page intentionally left blank...
Страница 40: ...Specifications Figure C 1 I S installation drawing C 4 STD5000 STD6000 User Guide Thermo Fisher Scientific...
Страница 43: ...Specifications Figure C 2 Thermo Fisher Scientific STD5000 STD6000 User Guide C 7...