background image

Installer’s Information Manual 

 

Page 25

 

SECTION 12.  GAS SUPPLY 
PRESSURE AND PILOT 
ADJUSTMENT  

You will need a 0 to 15 inch water manometer with 0.1 inch 
resolution and a 1/8" NPT manual shut-off valve to measure 
actual gas pressure. 

CHECKING GAS SUPPLY PRESSURE 

1.  Turn off gas at equipment shut-off valve in gas supply 

line just ahead of fu rnace. 

2.  Remove three screws holding burner access panel in 

place.  Remove burner access panel.  

3.  Remove inlet pressure plug from gas control.  See 

Figure 24. 

4.  Install 1/8" NPT manual shut-off valve in hole vacated 

by plug.  Make sure valve is in off position. 

5.  Attach manometer to 1/8" NPT manual shut-off valve 

just installed. 

6.  Slowly open equipment shut-off valve in gas supply line 

just ahead of fu rnace. 

7.  Slowly open 1/8" NPT manual shut-off valve leading to 

manometer. 

8.  Turn on all gas appliances attached to gas supply line. 

9.  With furnace operating, read gas supply pressure on 

manometer. 

??

Natural gas supply pressure must be between 5 
and 7 inches W.C. 

??

Propane gas (LP) supply pressure must be 
between 11 and 13 inches W.C.  

10.  If gas supply pressure is not within these limits, call gas 

supplier.  Tu rn off all gas appliances attached to gas 
supply line. 

11.  Shut off furnace. 

12.  Turn off gas at equipment shut-off valve in gas supply 

line just ahead of furnace.  Remove shut-off valve from 
gas -control inlet pressure tap.  Install pressure tap 
plug.  Turn on gas. 

13.  Replace burner access panel using three screws 

removed in step 2. 

PILOT FLAME ADJUSTMENT 

Before adjusting pilot flame, confirm that gas supply 
pressure is correct, as explained above. 

NOTE:  Pilot flame adjustment was checked at the factory 
and should not require adjustment.  However; pilot 
adjustment is possible if necessary.  

1.  Remove three screws holding burner access panel in 

place.  Remove burner access panel.  

2.  Start furnace following "Operating Instructions" on front 

door. 

3.  Pilot flame should cover 1/2 inch of tip of flame sensor 

as shown in Figure 29. 

4.  If you need to adjust pilot flame, remove pilot-

adjustment cover screw on gas control.  Save  cover 
screw for re-installation.  Tu rn inner adjustment screw 
clockwise to decrease pilot flame; counter-clockwise to 
increase pilot flame.  Install cover screw and tighten to 
torque of 5 inch-pounds to prevent gas leakage. 

 

Figure 29.  Pilot Flame Adjustment. 

5.  Check pilot-adjustment cover screw and gas -control 

inlet-pressure-tap plug for gas leaks.  Use a 
commercial soap solution made for leak detection. 

6.  Replace burner access panel using three screws 

removed in step 1. 

SECTION 13.  MANIFOLD 
PRESSURE ADJUSTMENT  

You will need a 0 to 15 inch water manometer with 0.1 inch 
resolution and a 1/8" NPT manual shut-off valve to measure 
actual manifold pressure. 

 

 

WARNING

: Correct manifold pressure is 

necessary for proper ignition and b urner operation.  Failure 
to accurately adjust pressure could cause heat exchanger 
failure. 

Check gas -supply pressure first.  Follow instructions in 
Section 12,  "Gas Supply Pressure and Pilot Adjustment." 

1.  Turn off gas at equipment shut-off valve in gas supply 

line just ahead of fu rnace. 

2.  Remove three screws holding burner access panel in 

place.  Remove burner access panel.  

3.  Remove plug from manifold pressure tap in gas 

control.  See Figure 24. 

4.  Install 1/8" NPT manual shut-off valve in hole vacated 

by plug.  Make sure shut-off valve is in off position. 

Содержание Thermo Pace Downflow/Horizontal Furnace

Страница 1: ...tion may arise For more information solutions to particular problems or clarification contact your local distributor or the manufacturer ATTENTION USER Your furnace installer should give you the docum...

Страница 2: ...o situations that could cause or result in minor or moderate injury or property damage For a safe and reliable installation be sure to read and follow all warnings and cautions We also use the words m...

Страница 3: ...e Figure 1 Figure 1 Furnace Installation Positions CAUTION Do not install furnace in an area subject to freezing temperatures Doing so could cause condensate to freeze This furnace operates best when...

Страница 4: ...rnace room When a cooling unit is installed with this furnace the furnace must be installed parallel with or on the upstream side of the cooling unit to avoid condensation in furnace heat exchanger Wi...

Страница 5: ...5 15 16 15 3 4 0 1 0 1 18 0 2 OR 3 72 000 3 4 20 1 2 18 15 16 18 3 4 0 1 0 1 18 0 2 OR 3 90 000 1 2 17 1 2 15 15 16 15 3 4 0 1 0 1 18 0 2 OR 3 90 000 3 4 20 1 2 18 15 16 18 3 4 0 1 0 1 18 0 2 OR 3 108...

Страница 6: ...right and maintain clearances as described previously Figure 7 Suspending Using Threaded Rod SECTION 4 PROVIDING VENTING AND COMBUSTION AIR This furnace must be connected to a plastic venting system...

Страница 7: ...thin 10 feet of an adjacent building Do not locate termination underneath a veranda porch or deck IN THE UNITED STATES Allow a minimum clearance of 4 feet from electric meters gas meters regulators an...

Страница 8: ...ON DIRECT VENTING instructions A non direct vented furnace takes all air for combustion from the room in which furnace is installed Non direct venting requires only one pipe for venting the flue gases...

Страница 9: ...Left Vent Top Vent Right Vent Downflow Position Top Vent Right Vent Horizontal Air Left Position Top Vent Left Vent Horizontal Air Right Position Figure 9 Venting Options Dashed lines show optional co...

Страница 10: ...reducer bushing in flue outlet See Table 1 or Table 2 for correct vent diameter for your application 11 Complete installation of venting system with field supplied parts 12 Support vent pipe at furna...

Страница 11: ...pending on altitude elevation of the installation gas input rating of furnace diameter of the air and vent pipes number of elbows Note that some of the larger furnace models may require a high altitud...

Страница 12: ...5 20 15 108 000 3 40 40 40 40 40 40 40 40 See Note 2 below 126 000 3 40 40 40 40 35 30 25 20 54 000 2 40 40 40 40 40 40 40 40 72 000 2 21 18 14 11 72 000 3 40 40 40 40 40 40 40 40 5001 6000 90 000 3 4...

Страница 13: ...burner enclosure Seal air pipe to collar with RTV silicone caulk See Figure 14 Note When venting with 3 inch pipe a 3 X 2 reducer must be used Locate reducer as close as possible to combustion air in...

Страница 14: ...60 55 50 108 000 3 85 80 75 70 65 60 55 50 See Note 2 126 000 3 55 50 45 40 35 30 25 20 54 000 2 43 40 37 33 30 27 24 20 72 000 2 21 18 14 11 72 000 3 150 150 150 150 150 150 150 150 5001 6000 90 000...

Страница 15: ...54 or Sections 7 2 7 3 or 7 4 of CAN CGA B149 Installation Codes or applicable provisions of local building codes WARNING Furnaces and any other fuel burning appliances must have enough fresh air for...

Страница 16: ...of the spaces meet the criteria above for an unconfined space not of unusually tight construction The total input of all gas appliances within the combined space must be considered in making this dete...

Страница 17: ...7 76 000 90 000 45 8 100 000 108 000 54 9 127 000 126 000 63 9 127 000 144 000 72 10 157 000 Example Furnace is 90 000 Btu per hour input and is to be installed in a confined space that contains no o...

Страница 18: ...TAL AIR LEFT POSITION 1 See Figure 22 for drain trap location for your installation In horizontal positions condensate drain trap must be mounted through bottom side of furnace 2 From parts package fi...

Страница 19: ...n furnace gas supply piping so it will not interfere with removal of burner assembly front door or blower door for servicing Make sure gas piping is large enough for all appliances connected to it to...

Страница 20: ...rounding by attaching grounding source to green wire in furnace junction box Follow local codes or in the absence of local codes the current National Electrical Code ANSI NFPA 70 or Canadian Electrica...

Страница 21: ...G terminals connected Fan Timer energizes main blower on heating speed A call for cooling while in constant fan mode causes main blower to change from heating to cooling speed Sixty seconds after the...

Страница 22: ...Page 22 Installer s Information Manual Figure 26 Furnace Wiring Diagram...

Страница 23: ...it passes through End ductwork outside furnace space See Figure 27 for floor cutout dimensions for combustible floor base Figure 27 Floor Cutout Dimensions Note A combustible floor base available from...

Страница 24: ...cooling system operation FILTER MOUNTING Use a downflow filter kit field fabricated filter cabinet or a return air filter grille Field fabricated filter cabinets should allow spacing between filter a...

Страница 25: ...as explained above NOTE Pilot flame adjustment was checked at the factory and should not require adjustment However pilot adjustment is possible if necessary 1 Remove three screws holding burner acces...

Страница 26: ...heck obtain gas heating value at your location from local supplier You will need a stopwatch to measure actual gas input 1 Gas supply pressure must be between 5 and 7 inches W C for natural gas See Se...

Страница 27: ...ve 2 000 feet the furnace must be derated 4 for each 1 000 foot above sea level It is the installer s responsibility to see that the furnace input rate is adjusted properly Derating must be achieved b...

Страница 28: ...urner carry overs Replace screws 9 Replace burner access panel using three screws removed in step 3 10 Open equipment shut off valve in gas supply line just ahead of furnace 11 Set room thermostat to...

Страница 29: ...e poor cooling performance or air conditioning coil freeze up High duct system static pressure is an indication of an overly restrictive duct system Static pressure in excess of 0 5 inches W C indicat...

Страница 30: ...instructions in Section 14 Checking Gas Input Rate If air temperature rise is still below temperature rise range specified less heating airflow is needed Change blower heating speed to a lower setting...

Страница 31: ...ee Return air duct must be physically sound sealed to furnace casing and ending outside the space containing furnace Supply air ducts and return air ducts must be clear and free and without air leaks...

Страница 32: ...ATURAL GAS CONVERSION KIT ABOVE 6000 FEET Includes natural gas regulator spring kit natural gas pilot orifice main burner orifices and high altitude pressure switch COMBUSTIBLE FLOOR BASE Required for...

Отзывы: