background image

Page 30 

 

Installer’s Information Manual 

11.  Remove jumper wire from 24-volt terminal strip.  

Remove pressure taps and seal holes in ductwork. 

SECTION 20.  MEASURING AIR 
TEMPERATURE RISE 

You will need 2 thermometers with 1-degree resolution 
capable of reading up to 175 degrees F. 

Air temperature rise (supply air temperature minus retu rn 
air temperature) must be within allowable air-temperature 
rise range specified on fu rnace rating plate and in Table 9. 

Follow this procedure: 

1.  Open supply-air registers and retu rn air grilles.  Make 

sure registers and grilles are free of obstruction from 
rugs, carpets, drapes or fu rniture. 

2.  Set balancing dampers  in supply duct system. 

3.  Check ductwork for obstructions or leaks. 

4.  Make sure filters are clean and in place.  

5.  Make sure that blower speed taps are set for proper 

heating and cooling.  Refer to Section 18, "Adjusting 
Blower Speed."  Heating speed should be  set 
according to Table 9.  Cooling speed should be set to 
meet cooling equipment requirements.  See Table 10 
for cooling airflow capacities at 0.5 inch W.C. 

6.  Place one thermometer in supply air plenum 

approximately 2 feet from furnace.  Locate 
thermometer  tip in center of plenum to ensure proper 
temperature measurement. 

7.  Place second thermometer in retu rn air duct 

approximately 2 feet from furnace.  Locate 
thermometer tip in center of duct to ensure proper 
temperature measurement. 

8.  Set room thermostat on highest temperature setting.  

Operate furnace 6 minutes.  Record supply air and 
return air temperatures. 

9.  Calculate air temperature rise by subtracting retu rn air 

temperature from supply air temperature. 

??

If air temperature rise is above temperature rise 
range s pecified in Table 9, fu rnace is overfired or 
has insufficient airflow.  Check gas input following 
the instructions in Section 14, "Checking Gas 
Input Rate."  If air temperature rise is still above 
temperature rise range specified, more airflow is 
needed.   Change blower heating speed to a 
higher setting following instructions in Section 18, 
"Adjusting Blower Speed." 

??

If air temperature rise is below temperature rise 
range specified in Table 9, fu rnace is underfired 
or has too much airflow.  Check gas input 
following the instructions in Section 14, "Checking 
Gas Input Rate."  If air temperature rise is still 
below temperature rise range specified, less 
heating airflow is needed.  Change blower 
heating speed to a lower setting following 
instructions in Section 18, "Adjusting Blower 
Speed." 

??

After making adjustments, you must check air 
temperature rise to verify that resulting air 
temperature rise is within allowable range.  If air 
temperature rise is still outside temperature rise 
range specified in Table 9, check duct system 
design with a qualified heating engineer.  It may 
be necessary to re-size duct work.  Recheck air 
temperature rise after revising duct systems.  

10.  Set room thermostat to desired setting. 

11.  Remove thermometers and seal ductwork holes. 

SECTION 21.  CHECKING 
CONTROLS 

Before leaving work site, check to see that all controls are 
functioning properly. 

You will need a 0 to 15 inch water manometer with 0.1 inch 
resolution and a 1/8" NPT manual shut-off valve. 

Follow this procedure: 

1.  Turn off electricity at electrical disconnect switch next 

to furnace. 

2.  Remove three screws holding burner access panel in 

place.  Remove burner access panel. 

3.  Turn gas control switch to OFF position. 

4.  Connect a manometer to gas control outlet (manifold) 

pressure tap. 

5.  Set room thermostat to its highest temperature. 

6.  Turn on electricity at electrical disconnect switch 

located next to furnace. 

7.  Diagnostic light on Fan Timer should be on and cycling 

bright-dim -bright-dim... 

8.  Draft inducer should run and pilot igniter should glow 

but pilot burner should not light.  Manifold pressure 
should remain at zero. 

9.  Turn gas control switch to ON position. 

10.  Pilot burner should light and ignite main burners.  It 

may take several minutes to purge gas line before pilot 
burner lights.  Wait 30 seconds after main burner 
ignition for main blower to start. 

11.  Cycle electrical disconnect switch next to furnace on 

and off.  Watch at least three ignition cycles.  Pilot 
should ignite main burners smoothly.  

12.  Burner flames should look the same with circulation 

blower on and off. 

13.  Remove manometer from gas control and replace 

outlet pressure tap 

14.  Use a commercial soap solution made to detect leaks 

and check all gas piping connections.  Bubbles indicate 
gas leakage.  Seal all leaks before proceeding. 

15.  Replace burner access panel using three screws 

removed in step 2. 

16.  Set room thermostat to desired setting. 

Содержание Thermo Pace Downflow/Horizontal Furnace

Страница 1: ...tion may arise For more information solutions to particular problems or clarification contact your local distributor or the manufacturer ATTENTION USER Your furnace installer should give you the docum...

Страница 2: ...o situations that could cause or result in minor or moderate injury or property damage For a safe and reliable installation be sure to read and follow all warnings and cautions We also use the words m...

Страница 3: ...e Figure 1 Figure 1 Furnace Installation Positions CAUTION Do not install furnace in an area subject to freezing temperatures Doing so could cause condensate to freeze This furnace operates best when...

Страница 4: ...rnace room When a cooling unit is installed with this furnace the furnace must be installed parallel with or on the upstream side of the cooling unit to avoid condensation in furnace heat exchanger Wi...

Страница 5: ...5 15 16 15 3 4 0 1 0 1 18 0 2 OR 3 72 000 3 4 20 1 2 18 15 16 18 3 4 0 1 0 1 18 0 2 OR 3 90 000 1 2 17 1 2 15 15 16 15 3 4 0 1 0 1 18 0 2 OR 3 90 000 3 4 20 1 2 18 15 16 18 3 4 0 1 0 1 18 0 2 OR 3 108...

Страница 6: ...right and maintain clearances as described previously Figure 7 Suspending Using Threaded Rod SECTION 4 PROVIDING VENTING AND COMBUSTION AIR This furnace must be connected to a plastic venting system...

Страница 7: ...thin 10 feet of an adjacent building Do not locate termination underneath a veranda porch or deck IN THE UNITED STATES Allow a minimum clearance of 4 feet from electric meters gas meters regulators an...

Страница 8: ...ON DIRECT VENTING instructions A non direct vented furnace takes all air for combustion from the room in which furnace is installed Non direct venting requires only one pipe for venting the flue gases...

Страница 9: ...Left Vent Top Vent Right Vent Downflow Position Top Vent Right Vent Horizontal Air Left Position Top Vent Left Vent Horizontal Air Right Position Figure 9 Venting Options Dashed lines show optional co...

Страница 10: ...reducer bushing in flue outlet See Table 1 or Table 2 for correct vent diameter for your application 11 Complete installation of venting system with field supplied parts 12 Support vent pipe at furna...

Страница 11: ...pending on altitude elevation of the installation gas input rating of furnace diameter of the air and vent pipes number of elbows Note that some of the larger furnace models may require a high altitud...

Страница 12: ...5 20 15 108 000 3 40 40 40 40 40 40 40 40 See Note 2 below 126 000 3 40 40 40 40 35 30 25 20 54 000 2 40 40 40 40 40 40 40 40 72 000 2 21 18 14 11 72 000 3 40 40 40 40 40 40 40 40 5001 6000 90 000 3 4...

Страница 13: ...burner enclosure Seal air pipe to collar with RTV silicone caulk See Figure 14 Note When venting with 3 inch pipe a 3 X 2 reducer must be used Locate reducer as close as possible to combustion air in...

Страница 14: ...60 55 50 108 000 3 85 80 75 70 65 60 55 50 See Note 2 126 000 3 55 50 45 40 35 30 25 20 54 000 2 43 40 37 33 30 27 24 20 72 000 2 21 18 14 11 72 000 3 150 150 150 150 150 150 150 150 5001 6000 90 000...

Страница 15: ...54 or Sections 7 2 7 3 or 7 4 of CAN CGA B149 Installation Codes or applicable provisions of local building codes WARNING Furnaces and any other fuel burning appliances must have enough fresh air for...

Страница 16: ...of the spaces meet the criteria above for an unconfined space not of unusually tight construction The total input of all gas appliances within the combined space must be considered in making this dete...

Страница 17: ...7 76 000 90 000 45 8 100 000 108 000 54 9 127 000 126 000 63 9 127 000 144 000 72 10 157 000 Example Furnace is 90 000 Btu per hour input and is to be installed in a confined space that contains no o...

Страница 18: ...TAL AIR LEFT POSITION 1 See Figure 22 for drain trap location for your installation In horizontal positions condensate drain trap must be mounted through bottom side of furnace 2 From parts package fi...

Страница 19: ...n furnace gas supply piping so it will not interfere with removal of burner assembly front door or blower door for servicing Make sure gas piping is large enough for all appliances connected to it to...

Страница 20: ...rounding by attaching grounding source to green wire in furnace junction box Follow local codes or in the absence of local codes the current National Electrical Code ANSI NFPA 70 or Canadian Electrica...

Страница 21: ...G terminals connected Fan Timer energizes main blower on heating speed A call for cooling while in constant fan mode causes main blower to change from heating to cooling speed Sixty seconds after the...

Страница 22: ...Page 22 Installer s Information Manual Figure 26 Furnace Wiring Diagram...

Страница 23: ...it passes through End ductwork outside furnace space See Figure 27 for floor cutout dimensions for combustible floor base Figure 27 Floor Cutout Dimensions Note A combustible floor base available from...

Страница 24: ...cooling system operation FILTER MOUNTING Use a downflow filter kit field fabricated filter cabinet or a return air filter grille Field fabricated filter cabinets should allow spacing between filter a...

Страница 25: ...as explained above NOTE Pilot flame adjustment was checked at the factory and should not require adjustment However pilot adjustment is possible if necessary 1 Remove three screws holding burner acces...

Страница 26: ...heck obtain gas heating value at your location from local supplier You will need a stopwatch to measure actual gas input 1 Gas supply pressure must be between 5 and 7 inches W C for natural gas See Se...

Страница 27: ...ve 2 000 feet the furnace must be derated 4 for each 1 000 foot above sea level It is the installer s responsibility to see that the furnace input rate is adjusted properly Derating must be achieved b...

Страница 28: ...urner carry overs Replace screws 9 Replace burner access panel using three screws removed in step 3 10 Open equipment shut off valve in gas supply line just ahead of furnace 11 Set room thermostat to...

Страница 29: ...e poor cooling performance or air conditioning coil freeze up High duct system static pressure is an indication of an overly restrictive duct system Static pressure in excess of 0 5 inches W C indicat...

Страница 30: ...instructions in Section 14 Checking Gas Input Rate If air temperature rise is still below temperature rise range specified less heating airflow is needed Change blower heating speed to a lower setting...

Страница 31: ...ee Return air duct must be physically sound sealed to furnace casing and ending outside the space containing furnace Supply air ducts and return air ducts must be clear and free and without air leaks...

Страница 32: ...ATURAL GAS CONVERSION KIT ABOVE 6000 FEET Includes natural gas regulator spring kit natural gas pilot orifice main burner orifices and high altitude pressure switch COMBUSTIBLE FLOOR BASE Required for...

Отзывы: