background image

Page 26 

 

Installer’s Information Manual 

5.  Attach manometer to 1/8" NPT manual shut-off valve 

just installed. 

6.  Slowly open equipment shut-off valve in gas supply line 

just ahead of fu rnace.  Start furnace following 
"Operating Instructions" inside front d oor. 

7.  Slowly open 1/8" NPT manual shut-off valve leading to 

manometer. 

8.  Read manifold pressure on manometer. 

9.  Adjust manifold pressure by tu rning gas control 

regulator adjusting screw clockwise to increase 
pressure or tu rning counter-clockwise to decrease 
pressure.  Manifold pressure must be within allowable 
range below: 

??

Natural gas manifold pressure must be between 
3.2 and 3.8 inches W.C.  

??

Propane gas (LP) manifold pressure must be 
between 9.7 and 10.3 inches W.C. 

NOTE:  For natural gas, if gas flow rate cannot be properly 

set within these pressure ranges then you must change 
main burner orifices to obtain proper gas flow rate. 

10.  Shut off furnace.  Turn off gas at equipment shut-off 

valve in gas supply line just ahead of fu rnace.  Install 
outlet-pressure-tap plug in gas control.  Tu rn on gas. 

11.  Check regulator-adjustment-cover screw and gas 

control plug for gas leaks.  Use a commercial soap 
solution made for leak detection. 

12.  Replace burner access panel using three screws 

removed in step 2. 

SECTION 14.  CHECKING GAS 
INPUT RATE 

It is the installer's responsibility to see that the Btu input 
rate of the furnace is properly adjusted.  Under-firing could 
cause inadequate heat, primary heat exchanger corrosion 
and/or ignition problems.  Over-firing could cause sooting, 
flame impingement and/or overheating of heat exchanger. 

 

 

WARNING

: Failure to adjust furnace to the proper 

firing rate could cause heat exchanger failure. 

Depending on your local gas heating value and elevation, 
you may need to adjust manifold pressure or change 
orifices to get proper gas input rate.  Check with your local 
gas supplier to determine heating value (Btu/cu.ft.) of 
natural gas in your area. 

NOTE: If furnace is being installed at an altitude of more 
than 2000 feet above sea level, you must derate the 
furnace.  See Section 15, "Derating For High Altitude." 

NATURAL GAS INPUT RATE 

Natural gas heating value (Btu/cu.ft.) can vary significantly.  
Before starting natural gas input check, obtain gas heating 
value at your location from local supplier.  You will need a 
stopwatch to measure actual gas input. 

1.  Gas supply pressure must be between 5 and 7 inches 

W.C. for natural gas.  See Section 12, "Gas Supply 
Pressure and Pilot Adjustment." 

2.  Turn off all other gas appliances.  You may leave pilots 

on. 

3.  Start furnace following "Operating Instructions" inside 

front door.  Let furnace warm up for 6 minutes. 

4.  Locate gas meter.  Determine which dial has the 

fewest cubic feet of gas and how many cubic feet per 
revolution it represents.  This is usually one-half, one or 
two cubic feet per revolution. 

5.  With stopwatch, measure time it takes to consume two 

cubic feet of gas. 

??

If dial is one cubic foot per revolution, measure 
time for two revolutions. 

??

If dial is two cubic feet per revolution, measure 
time for one revolution.  

6.  Divide this time by two.  This gives average time for 

one cubic foot of gas to flow through meter.  Example: 
If it took 58 seconds for two-cubic feet to flow, it would 
take 29 seconds for one-cubic foot to flow. 

7.  Calculate gas input using this formula: 

 

 

 

Gas Heating Value (Btu/cu.ft.) 

 

 

 

          X 3,600 sec/hr 

 

Gas input = 

 

 

 

      =  Btu/hour 

 

 

 

        Time (Seconds for 

 

 

 

      one cubic foot of gas) 

 
Example:  Assume it took 29 seconds for one cubic foot of 

gas to flow and heating value of 1,000 Btu/cu.ft. 

 

 

 

1,000 x 3,600 

Gas Input = 

 

 

= 124,138 Btu per hour 

 

 

29 

If you left no other pilots on, this is the fu rnace gas input. 

8.  If you left water heater, dryer or range pilots on, allow 

for them in calculating correct fu rnace gas input.  A 
quick way is to allow 1,000 Btu per hour for a water 
heater, 500 Btu per hour for dryer and 500 Btu per hour 
for each range burner pilot. 

Example: 

If you left gas water heater, dryer, two range burner pilots 
and one oven pilot on, allow: 

 

Water heater pilot 

1,000 Btu per hour 

 

Dryer pilot 

500 Btu per hour 

 

2 range burner pilots 

1,000 Btu per hour 

 

1 range oven pilot 

500 Btu per hour 

 

 

 

 

3,000 Btu per hour 

Subtracting 3,000 Btu per hour from 124,138 Btu per hour 
measured above equals 121,138 Btu per hour.  This would 
be the correct furnace gas input after allowing for pilots left 
on.  

9.  Manifold pressure may be adjusted within the range of 

3.2 inches W.C. to 3.8 inches W.C. to get rated input ± 
2 percent.  See Section 13, "Manifold Pressure 
Adjustment."  If you cannot  get rated input with 
manifold pressure within the allowable range, you must 
change orifices.  See Section 17, "Changing Main 
Burner Orifices." 

Содержание Thermo Pace Downflow/Horizontal Furnace

Страница 1: ...tion may arise For more information solutions to particular problems or clarification contact your local distributor or the manufacturer ATTENTION USER Your furnace installer should give you the docum...

Страница 2: ...o situations that could cause or result in minor or moderate injury or property damage For a safe and reliable installation be sure to read and follow all warnings and cautions We also use the words m...

Страница 3: ...e Figure 1 Figure 1 Furnace Installation Positions CAUTION Do not install furnace in an area subject to freezing temperatures Doing so could cause condensate to freeze This furnace operates best when...

Страница 4: ...rnace room When a cooling unit is installed with this furnace the furnace must be installed parallel with or on the upstream side of the cooling unit to avoid condensation in furnace heat exchanger Wi...

Страница 5: ...5 15 16 15 3 4 0 1 0 1 18 0 2 OR 3 72 000 3 4 20 1 2 18 15 16 18 3 4 0 1 0 1 18 0 2 OR 3 90 000 1 2 17 1 2 15 15 16 15 3 4 0 1 0 1 18 0 2 OR 3 90 000 3 4 20 1 2 18 15 16 18 3 4 0 1 0 1 18 0 2 OR 3 108...

Страница 6: ...right and maintain clearances as described previously Figure 7 Suspending Using Threaded Rod SECTION 4 PROVIDING VENTING AND COMBUSTION AIR This furnace must be connected to a plastic venting system...

Страница 7: ...thin 10 feet of an adjacent building Do not locate termination underneath a veranda porch or deck IN THE UNITED STATES Allow a minimum clearance of 4 feet from electric meters gas meters regulators an...

Страница 8: ...ON DIRECT VENTING instructions A non direct vented furnace takes all air for combustion from the room in which furnace is installed Non direct venting requires only one pipe for venting the flue gases...

Страница 9: ...Left Vent Top Vent Right Vent Downflow Position Top Vent Right Vent Horizontal Air Left Position Top Vent Left Vent Horizontal Air Right Position Figure 9 Venting Options Dashed lines show optional co...

Страница 10: ...reducer bushing in flue outlet See Table 1 or Table 2 for correct vent diameter for your application 11 Complete installation of venting system with field supplied parts 12 Support vent pipe at furna...

Страница 11: ...pending on altitude elevation of the installation gas input rating of furnace diameter of the air and vent pipes number of elbows Note that some of the larger furnace models may require a high altitud...

Страница 12: ...5 20 15 108 000 3 40 40 40 40 40 40 40 40 See Note 2 below 126 000 3 40 40 40 40 35 30 25 20 54 000 2 40 40 40 40 40 40 40 40 72 000 2 21 18 14 11 72 000 3 40 40 40 40 40 40 40 40 5001 6000 90 000 3 4...

Страница 13: ...burner enclosure Seal air pipe to collar with RTV silicone caulk See Figure 14 Note When venting with 3 inch pipe a 3 X 2 reducer must be used Locate reducer as close as possible to combustion air in...

Страница 14: ...60 55 50 108 000 3 85 80 75 70 65 60 55 50 See Note 2 126 000 3 55 50 45 40 35 30 25 20 54 000 2 43 40 37 33 30 27 24 20 72 000 2 21 18 14 11 72 000 3 150 150 150 150 150 150 150 150 5001 6000 90 000...

Страница 15: ...54 or Sections 7 2 7 3 or 7 4 of CAN CGA B149 Installation Codes or applicable provisions of local building codes WARNING Furnaces and any other fuel burning appliances must have enough fresh air for...

Страница 16: ...of the spaces meet the criteria above for an unconfined space not of unusually tight construction The total input of all gas appliances within the combined space must be considered in making this dete...

Страница 17: ...7 76 000 90 000 45 8 100 000 108 000 54 9 127 000 126 000 63 9 127 000 144 000 72 10 157 000 Example Furnace is 90 000 Btu per hour input and is to be installed in a confined space that contains no o...

Страница 18: ...TAL AIR LEFT POSITION 1 See Figure 22 for drain trap location for your installation In horizontal positions condensate drain trap must be mounted through bottom side of furnace 2 From parts package fi...

Страница 19: ...n furnace gas supply piping so it will not interfere with removal of burner assembly front door or blower door for servicing Make sure gas piping is large enough for all appliances connected to it to...

Страница 20: ...rounding by attaching grounding source to green wire in furnace junction box Follow local codes or in the absence of local codes the current National Electrical Code ANSI NFPA 70 or Canadian Electrica...

Страница 21: ...G terminals connected Fan Timer energizes main blower on heating speed A call for cooling while in constant fan mode causes main blower to change from heating to cooling speed Sixty seconds after the...

Страница 22: ...Page 22 Installer s Information Manual Figure 26 Furnace Wiring Diagram...

Страница 23: ...it passes through End ductwork outside furnace space See Figure 27 for floor cutout dimensions for combustible floor base Figure 27 Floor Cutout Dimensions Note A combustible floor base available from...

Страница 24: ...cooling system operation FILTER MOUNTING Use a downflow filter kit field fabricated filter cabinet or a return air filter grille Field fabricated filter cabinets should allow spacing between filter a...

Страница 25: ...as explained above NOTE Pilot flame adjustment was checked at the factory and should not require adjustment However pilot adjustment is possible if necessary 1 Remove three screws holding burner acces...

Страница 26: ...heck obtain gas heating value at your location from local supplier You will need a stopwatch to measure actual gas input 1 Gas supply pressure must be between 5 and 7 inches W C for natural gas See Se...

Страница 27: ...ve 2 000 feet the furnace must be derated 4 for each 1 000 foot above sea level It is the installer s responsibility to see that the furnace input rate is adjusted properly Derating must be achieved b...

Страница 28: ...urner carry overs Replace screws 9 Replace burner access panel using three screws removed in step 3 10 Open equipment shut off valve in gas supply line just ahead of furnace 11 Set room thermostat to...

Страница 29: ...e poor cooling performance or air conditioning coil freeze up High duct system static pressure is an indication of an overly restrictive duct system Static pressure in excess of 0 5 inches W C indicat...

Страница 30: ...instructions in Section 14 Checking Gas Input Rate If air temperature rise is still below temperature rise range specified less heating airflow is needed Change blower heating speed to a lower setting...

Страница 31: ...ee Return air duct must be physically sound sealed to furnace casing and ending outside the space containing furnace Supply air ducts and return air ducts must be clear and free and without air leaks...

Страница 32: ...ATURAL GAS CONVERSION KIT ABOVE 6000 FEET Includes natural gas regulator spring kit natural gas pilot orifice main burner orifices and high altitude pressure switch COMBUSTIBLE FLOOR BASE Required for...

Отзывы: