9-24
Schematic Circuit Tracings
Electrical, Refrigeration and
µ
P-D Menu Flow Diagrams
CRR-20 & CRR-40, September 1999
1
Typical model shown with three evaporator fans.
2
Condenser fan will stop if condenser head pressure decreases to 1100 +/- 50 kPa, 11.00 +/- 0.5 bar, 160 +/- 7 psig.
Cool Mode
1
— Frozen Load (Setpoint at -10.0 C [14.0 F] or Below); Condenser Fan ON
2
; Container Return Air
Temperature Above -10.0 C (14.0 F); Power Monitor Limiting Unit Power Consumption; Economy Mode OFF