1-4
Refrigeration System
Specifications
CRR-20 & CRR-40, September 1999
Refrigeration System
*When the compressor is removed from the unit, oil level should be noted or the oil removed from the compressor should be mea-
sured so that the same amount of oil can be maintained in the replacement compressor.
**DO NOT use or add standard synthetic or mineral oils to the refrigeration system. If Ester based oil becomes contaminated with
moisture or with standard oils, dispose of properly — DO NOT USE!
***Included with Water-Cooled Condenser-Receiver Tank option.
Compressor Model No.:
CRR-20SL
3DFT-075X-TFD, Semi-hermetic with Copeland Discus® Valve
CRR-40
3DST-075X-TFD, Semi-hermetic with Copeland Discus® Valve
Refrigerant Charge:
Standard Receiver Tank
4.9 Kg (10.8 lb) R-134a
Water-Cooled Condenser-Receiver Tank (Option)
5.45 Kg (12.0 lb) R-134a
Compressor Oil Capacity
1.77 liter (60 oz.)*
Compressor Oil Type
Polyol Ester Based Type (required), TK Part No. 203-433**
High Pressure Cutout Switch:
All models (Except CRR-20SL-63):
Cutout
2410 +/- 70 kPa, 24.10 +/- 0.70 bar, 350 +/- 10 psig
Cutin
1655 +/- 70 kPa, 16.55 +/- 0.70 bar, 240 +/- 10 psig
CRR-20SL-63:
Cutout
2240 +/- 70 kPa, 22.40 +/- 0.70 bar, 325 +/- 10 psig
Cutin
1590 +/- 70 kPa, 15.90 +/- 0.70 bar, 230 +/- 10 psig
Condenser Fan Pressure Switch:
Open
1380 +/- 50 kPa, 13.80 +/- 0.50 bar, 200 +/- 7 psig
Close
1100 +/- 50 kPa, 11.00 +/- 0.50 bar, 160 +/- 7 psig
Water Pressure Switch (Option):
Open
117 +/- 21 kPa, 1.17 +/- 0.20 bar, 17 +/- 3 psig
Close
35 +/- 21 kPa, 0.35 +/- 0.20 bar, 5 +/- 3 psig
High Pressure Relief:
Fusible Plug (Standard)
Relief Temp.
100 C (212 F)
Relief Valve (Option***):
Relief Pressure
3447 +345/-104 kPa, 34.47 +3.45/-1.04 bar, 500 +50/-15 psig
Reset
2758 kPa, 27.58 bar, 400 psig
Liquid Injection Control:
Compressor Start
Liquid injection valve opens for 5 minutes on each compressor start
Power Limit or Modulation Cool
Liquid injection valve opens continuously during Power Limit and
Modulation Cool modes
Compressor Discharge Temperature Control
Energizes (Opens) Liquid Injection Valve at 138 C (280 F)
De-energizes (Closes) Liquid Injection Valve at 132 C (270 F)
Compressor Shutdown (Auto Reset) at 148 C (298 F)
Liquid Injection Valve (Compressor):
Voltage
24 Vac
Cold Resistance
5.6 ohms
Evaporator Pressure Regulator (KVQ Valve):
EPR Circuit Voltage
24 Vdc
EPR Circuit Resistance
22 ohms
EPRTH (Thermistor) Circuit Resistance
22,000 ohms at 20 C (68 F)