Electrical Maintenance
50
Auto Phase System
The Auto Phase system automatically adjusts the
phase sequence of the power supply to correspond
with the wiring of the electric motor. The main
components of the system are the phase selection
module (PSM), its two relays, and the two motor
contactors (MC1 and MC2). Contactor MC1 is
wired to retain the phase sequence. Contactor
MC2 is wired to change the phase sequence. The
PSM senses the phase sequence at the heater
contactor and energizes the appropriate motor
contactor by energizing one of the relays.
Troubleshooting the Auto Phase System
If the Electric Motor Runs Backwards (Unit Airflow
Incorrect):
1. Turn the electric power supply Off and check
the unit wiring. Refer to the appropriate
wiring diagrams, schematics, and to Figure 22
on page 51.
a. The three wires from the PSM should be
connected to the heater contactor terminals
as follows: Brown wire to terminal L1,
Blue wire to terminal L2, and Black wire
to terminal L3.
b. Wires L1, L2, and L3 should be connected
respectively to terminals L1, L2, and L3
on the heater contactor and both motor
contactors.
c. Wires T1A, T2A, and T3A should be
connected respectively to terminals T1,
T2, and T3 on MC1.
d. Wires T1A, T2A, and T3A should be
connected respectively to terminals T3,
T2, and T1 on MC2.
e. Wires T1A, T2A, and T3A should be
connected respectively to terminals L1,
L2, and L3 on the overload relay.
f.
Wires 1, 2, and 3 should be connected
respectively to terminals T1, T2, and T3
on the overload relay.
g. Wires Brown, Blue, and Black should be
connected respectively to terminals X, Y,
and Z in the power receptacle.
h. Wires Brown, Blue, and Black should be
connected respectively to terminals L1,
L2, and L3 on MC1.
i.
Wires 7EC, 7EB, and CH should be
connected to the corresponding terminals
on the PSM. The 7EH wires should be
connected to the 7EA and 8 terminals on
the PSM.
j.
The electric motor must be wired
correctly.
2. Check the relays on the PSM to make sure that
one of them is not faulty (contacts stuck
closed).
3. Check MC1 and MC2 to make sure that one of
them is not faulty (contacts stuck closed).
1.
Condenser Air Out
3.
Evaporator Air Out
2.
Condenser Air In
4.
Evaporator Air In
Figure 21: Host Unit Air Flow
1
3
4
2
AJA920
ARA104
Содержание 002008
Страница 4: ...4 ...
Страница 25: ...Unit Description 25 Figure 3 Zone 1 Cool Zone 2 Cool and Zone 3 Cool Zone 3 Zone 2 Zone 1 AGA168 ...
Страница 27: ...Unit Description 27 Figure 4 Zone 1 Cool Zone 2 Cool and Zone 3 Heat Zone 3 Zone 2 Zone 1 AGA169 ...
Страница 30: ...Unit Description 30 Figure 9 Front View AJA920 ...
Страница 31: ...Unit Description 31 1 Access Panels 2 Defrost Damper Figure 10 Back View 1 2 ARA104 ...
Страница 114: ...Mechanical Diagnosis 114 ...
Страница 116: ...Electric Standby Diagnosis 116 ...
Страница 120: ...Remote Evaporator Specifications 120 ...
Страница 122: ...Remote Evaporator Maintenance Inspection Schedule 122 ...
Страница 128: ...Remote Evaporator Electrical Maintenance 128 ...
Страница 132: ...Remote Evaporator Refrigeration Service Operations 132 ...
Страница 134: ...Remote Evaporator Structural Maintenance 134 ...
Страница 136: ...Remote Evaporator System Diagnosis 136 ...
Страница 140: ...Index 140 ...
Страница 142: ......
Страница 143: ...143 Model 30 Schematic Diagram Page 1 of 2 ...
Страница 144: ...144 Model 30 Schematic Diagram Page 2 of 2 ...
Страница 145: ...145 Model 30 Wiring Diagram Page 1 of 4 ...
Страница 146: ...146 Model 30 Wiring Diagram Page 2 of 4 ...
Страница 147: ...147 Model 30 Wiring Diagram Page 3 of 4 ...
Страница 148: ...148 Model 30 Wiring Diagram Page 4 of 4 ...
Страница 149: ...149 Model 50 Schematic Diagram Page 1 of 2 ...
Страница 150: ...150 Model 50 Schematic Diagram Page 2 of 2 ...
Страница 151: ...151 Model 50 Wiring Diagram Page 1 of 5 ...
Страница 152: ...152 Model 50 Wiring Diagram Page 2 of 5 ...
Страница 153: ...153 Model 50 Wiring Diagram Page 3 of 5 ...
Страница 154: ...154 Model 50 Wiring Diagram Page 4 of 5 ...
Страница 155: ...155 Model 50 Wiring Diagram Page 5 of 5 ...