Refrigeration Maintenance
83
3. Raise the discharge pressure of the
compressor first by blocking the condenser
coil air flow by covering the roadside
condenser grille with apiece of cardboard. If
this does not raise the discharge pressure to
the cutout level of the HPCO, increase the
engine speed by overriding the throttle
solenoid. This should increase the discharge
pressure enough to cause the HPCO to cut out.
The cut out pressure should be 470 ± 7 psig
(3241 ± 48 kPa).
4. If the HPCO does not open to de-energize the
fuel solenoid and stop the engine, it must be
replaced.
High Pressure Switch (HPSW)
Test
The high pressure switch (HPSW) is located on
the compressor discharge manifold. This switch is
used by the microprocessor to confirm the
operation of the receiver tank pressure solenoid
and the purge valve. It is connected to the 7K1
and HP wires in the main wire harness. The
HPSW opens when the discharge pressure rises
above 300 psig (2068 kPa). The HPSW closes
when the discharge pressure drops below 200 psig
(1379 kPa).
Use the following procedure to test the HPSW:
1. Install a gauge manifold on the compressor.
2. Disconnect the HPSW from the 7K1 and HP
wires in the main wire harness.
3. Check the HPSW for continuity. It should be
closed when the unit is not running.
4. Use the Service Test mode to run the host unit
in High Speed Cool. Refer to the appropriate
Diagnosis Manual for specific information
about the Service Test Mode.
5. Cover the condenser to raise the discharge
pressure.
6. Monitor the discharge pressure. When the
discharge pressure reaches 300 +25/-0 psig
(2068 +172/-0 kPa), the HPCI should open.
7. Uncover the condenser to lower the discharge
pressure.
8. Monitor the discharge and suction pressures.
When the discharge pressure reaches 200 ±
20 psig (1379 ± 138 kPa), the HPSW should
close.
9. Replace the HSW if it does not function
properly.
10. Reconnect the HPSW to the main wire harness
and remove the gauge manifold.
CAUTION: If the discharge pressure
reaches 477 psig (3289 kPa), shut the unit
off immediately. Do not allow the
discharge pressure to exceed 477 psig
(3289 kPa).
1.
Relief Valve (66-6543)
2.
O-Ring (33-1015)
3.
Adapter Tee Weather Head (No. 552X3)
Figure 56: High Pressure Cutout Manifold
Содержание 002008
Страница 4: ...4 ...
Страница 25: ...Unit Description 25 Figure 3 Zone 1 Cool Zone 2 Cool and Zone 3 Cool Zone 3 Zone 2 Zone 1 AGA168 ...
Страница 27: ...Unit Description 27 Figure 4 Zone 1 Cool Zone 2 Cool and Zone 3 Heat Zone 3 Zone 2 Zone 1 AGA169 ...
Страница 30: ...Unit Description 30 Figure 9 Front View AJA920 ...
Страница 31: ...Unit Description 31 1 Access Panels 2 Defrost Damper Figure 10 Back View 1 2 ARA104 ...
Страница 114: ...Mechanical Diagnosis 114 ...
Страница 116: ...Electric Standby Diagnosis 116 ...
Страница 120: ...Remote Evaporator Specifications 120 ...
Страница 122: ...Remote Evaporator Maintenance Inspection Schedule 122 ...
Страница 128: ...Remote Evaporator Electrical Maintenance 128 ...
Страница 132: ...Remote Evaporator Refrigeration Service Operations 132 ...
Страница 134: ...Remote Evaporator Structural Maintenance 134 ...
Страница 136: ...Remote Evaporator System Diagnosis 136 ...
Страница 140: ...Index 140 ...
Страница 142: ......
Страница 143: ...143 Model 30 Schematic Diagram Page 1 of 2 ...
Страница 144: ...144 Model 30 Schematic Diagram Page 2 of 2 ...
Страница 145: ...145 Model 30 Wiring Diagram Page 1 of 4 ...
Страница 146: ...146 Model 30 Wiring Diagram Page 2 of 4 ...
Страница 147: ...147 Model 30 Wiring Diagram Page 3 of 4 ...
Страница 148: ...148 Model 30 Wiring Diagram Page 4 of 4 ...
Страница 149: ...149 Model 50 Schematic Diagram Page 1 of 2 ...
Страница 150: ...150 Model 50 Schematic Diagram Page 2 of 2 ...
Страница 151: ...151 Model 50 Wiring Diagram Page 1 of 5 ...
Страница 152: ...152 Model 50 Wiring Diagram Page 2 of 5 ...
Страница 153: ...153 Model 50 Wiring Diagram Page 3 of 5 ...
Страница 154: ...154 Model 50 Wiring Diagram Page 4 of 5 ...
Страница 155: ...155 Model 50 Wiring Diagram Page 5 of 5 ...