Unit Description
26
Zone 1 Cool, Zone 2 Cool, and
Zone 3 Heat
The CIS is closed so high pressure refrigerant
vapor leaves the compressor and flows through
the hot gas line and the open HGS3 into the
Zone 3 evaporator. There the refrigerant heats the
Zone 3 evaporator and condenses into high
pressure liquid. Because the SLS3 is closed, the
liquid refrigerant flows through the LRCV3 and
the remote liquid line to LLS and LLS2.
The LLS is open so some of the refrigerant flows
through the Zone 1 expansion valve into the
Zone 1 evaporator. There the liquid refrigerant
cools the Zone 1 evaporator as it evaporates into
low pressure vapor. The refrigerant returns to the
compressor through the SLCV, and the
accumulator.
The LLS2 is also open so some of the refrigerant
flows through the Zone 2 expansion valve into the
Zone 2 evaporator. There the liquid refrigerant
cools the Zone 2 evaporator as it evaporates into
low pressure vapor. The refrigerant returns to the
compressor through the SLS2, the suction line, the
SLCV2, and the accumulator.
Host Unit and Zone 1 Evaporator
1. Liquid Line Solenoid (LLS)—Open
2. Liquid Return Check Valve (LRCV)—Closed
3. Suction Line Check Valve (SLCV)—Open
4. Suction Line Solenoid (SLS)—Open
5. Hot Gas Solenoid (HGS)—Closed
6. Condenser Inlet Solenoid (CIS)—Closed*
7. Condenser Inlet Check Valve
(CICV)—Closed
8. Receiver Tank Pressure Solenoid
(RTPS)—Open*
9. Condenser Check Valve (CCV)—Closed
10. Bypass Hand Valve
11. Purge Valve (PV)—Open*
12. Purge Check Valve (PCV)—Open
* The microprocessor will open and close these
valves as required to control the head pressure or
compensate for high ambient temperatures.
Zone 2 Evaporator
1C. Zone 2 Liquid Line Solenoid (LLS2)—Open
2C. Zone 2 Liquid Return Check Valve
(LRCV2)— Closed
3C. Zone 2 Suction Line Check Valve
(SLCV2)— Open
4C. Zone 2 Suction Line Solenoid (SLS2)—Open
5C. Zone 2 Hot Gas Solenoid (HGS2)—Closed
Zone 3 Evaporator
1R. Zone 3 Liquid Line Solenoid (LLS3)—Open
2R. Zone 3 Liquid Return Check Valve
(LRCV3)— Open
3R. Zone 3 Suction Line Check Valve
(SLCV3)— Closed
4R. Zone 3 Suction Line Solenoid
(SLS3)—Closed
5R. Zone 3 Hot Gas Solenoid (HGS3)—Open
Содержание 002008
Страница 4: ...4 ...
Страница 25: ...Unit Description 25 Figure 3 Zone 1 Cool Zone 2 Cool and Zone 3 Cool Zone 3 Zone 2 Zone 1 AGA168 ...
Страница 27: ...Unit Description 27 Figure 4 Zone 1 Cool Zone 2 Cool and Zone 3 Heat Zone 3 Zone 2 Zone 1 AGA169 ...
Страница 30: ...Unit Description 30 Figure 9 Front View AJA920 ...
Страница 31: ...Unit Description 31 1 Access Panels 2 Defrost Damper Figure 10 Back View 1 2 ARA104 ...
Страница 114: ...Mechanical Diagnosis 114 ...
Страница 116: ...Electric Standby Diagnosis 116 ...
Страница 120: ...Remote Evaporator Specifications 120 ...
Страница 122: ...Remote Evaporator Maintenance Inspection Schedule 122 ...
Страница 128: ...Remote Evaporator Electrical Maintenance 128 ...
Страница 132: ...Remote Evaporator Refrigeration Service Operations 132 ...
Страница 134: ...Remote Evaporator Structural Maintenance 134 ...
Страница 136: ...Remote Evaporator System Diagnosis 136 ...
Страница 140: ...Index 140 ...
Страница 142: ......
Страница 143: ...143 Model 30 Schematic Diagram Page 1 of 2 ...
Страница 144: ...144 Model 30 Schematic Diagram Page 2 of 2 ...
Страница 145: ...145 Model 30 Wiring Diagram Page 1 of 4 ...
Страница 146: ...146 Model 30 Wiring Diagram Page 2 of 4 ...
Страница 147: ...147 Model 30 Wiring Diagram Page 3 of 4 ...
Страница 148: ...148 Model 30 Wiring Diagram Page 4 of 4 ...
Страница 149: ...149 Model 50 Schematic Diagram Page 1 of 2 ...
Страница 150: ...150 Model 50 Schematic Diagram Page 2 of 2 ...
Страница 151: ...151 Model 50 Wiring Diagram Page 1 of 5 ...
Страница 152: ...152 Model 50 Wiring Diagram Page 2 of 5 ...
Страница 153: ...153 Model 50 Wiring Diagram Page 3 of 5 ...
Страница 154: ...154 Model 50 Wiring Diagram Page 4 of 5 ...
Страница 155: ...155 Model 50 Wiring Diagram Page 5 of 5 ...