An anti-condensate pump operates during periods of no
heat request to avoid damage until the boiler returns to a
stable operating temperature. While the system is oper-
ating, this pump must guarantee a flow rate between 20
and 30% of maximum flow, must ensure a water return
temperature no lower than the minimum permissible (see
technical data) and must also delay shutting down for at
least 3 minutes at the beginning of extended periods of
boiler shutdown (overnight or weekend shutdown etc.).
b
A sensor socket must be positioned at a distance
of 3 to 5 times the diameter of the water return
pipe, upstream from the water fitting, to measure
effective water return temperature and control the
anti-condensate pump or the temperature controller
stabilisation function.
b
Any temperature controllers installed remotely from
the control panel must be compatible with the sys-
tem’s electrical connections and functioning logic.
0
30
60
90
Ø
H
The flue gas exhaust and its connection to the stack must be made in compliance with applicable laws and standards,
using heat resistant, condensate resistant and stress resistant rigid pipe and sealed joints.
THE/TG 3S
90
115
166
217
255
349
448
511
639
850
1160 1450
Ø - Diameter
180
200
250
250
250
250
300
300
350
350
400
450
mm
H
870
946
1005 1005 1130 1130 1290 1290 1405 1445 1580 1695 mm
23
ENGLISH
INSTALLER
COMBUSTION GAS EXHAUST