Installer Supplied Items 

 

The following items are necessary for the installation of the ductless mini splits.  

 

Refrigerant line set: Flared connection only, suitable for R410A with both lines insulated, max length for 
connection see specification

 

pages 17 to 21.

 

 

High voltage interconnect wiring: 16 AWG stranded wiring from outdoor unit to indoor unit for power and 
control. 

 

Condensate tubing: Per local codes to remove condensate from the indoor unit. 

 

5/8" drain tubing as necessary. 

 

Wall Sleeve 

 

Sealant 

 

2

” wide tape 

 

Main system breaker: Sized per unit requirements (see specification pages 15 to 19), to be mounted 
adjacent to outdoor unit. 

 

Refrigerant: R410A required for additional line set charge - see specification pages 13. 

 

Mounting hardware, condenser pad, etc. 

 

Parts Included with Unit 

 

Indoor unit 

Outdoor Unit 

 

Mounting Plate 

 

Installation Manual 

 

Remote Control 

 

Installation Quick Guide 

 

Remote Control Holder 

 

Plastic drain connection (Heat Pump unit only) 

 

Batteries for Remote Control (2 AAA) 

 

 

Operation Manual 

 

 

Wall Anchors  

 

 

Items for Consideration 

Application 

Check the application of the unit prior to installation. Certain applications require additional components or 
installation parameters. 
 

The below data is for the Northeast section of the US. Increase capacity by 25% for the East, 30% for 
the South and 40% for the West. 

 
 

Computer or Data Server Rooms  

These require ballpark sizing of approximately 12,000 BTU/H Capacity per 250 sq. ft. of room size. 
 
The system will be running 24/7. If winter temperatures fall below 32°F, a Wind Baffle (Field Supplied) should 
be

 

installed. 

 

Offices and Commercial Spaces, Churches etc 

These require ballpark sizing of approximately 12,000 BTU/H Capacity per 400 sq. ft. of room size.

 

 

Residential, Bedrooms, Family Rooms etc 

These require ballpark sizing of approximately 12,000 BTU/H capacity per 600 sq. ft. of room size.  
 

NOTICE: 

Heat Pumps are a great application; however the unit may not provide adequate heat. It is not recommended 
for use as a primary source of heat in areas where the winter temperatures fall below 30°F. 
 

Installation 

Determine the best location for mounting the Indoor unit. It must be located a minimum of 4 ft. from the floor. 
Pay close attention to the air circulation in the room. 9,000 &12,000 BTU units throw air approximately 15ft., 
18,000 & 24,000 BTU units throw air approximately 25 ft. Ensure there are no obstacles to airflow. 
Locate the indoor and outdoor units as close together as possible, maximum line set run and lift CANNOT BE 
EXCEEDED. Determine how the Interconnect piping, wiring and condensate hose is to be run. 

 
 

Содержание 12A45YIMI

Страница 1: ...Inc MINI SPLIT INSTALLATION AND MAINTENANCE MANUAL A C HEAT PUMP 9A45YIMI 9H45YIMI 12A45YIMI 12H45YIMI 12A45ZIMI 12H45ZIMI 18A45ZIMI 18H45ZIMI 24A45ZIMI 24H45ZIMI 9A45YOMI 9H45YOMI 12A45YOMI 12H45YOM...

Страница 2: ...Items for Considerations 3 Unit Installation 5 Unit Installation indoor 6 Unit Installation outdoor 9 Main Power Wiring 10 Controls Wiring 10 Wiring Diagram 11 Unit Start Up 13 Refrigerant Charge 14...

Страница 3: ...m voltage before installing the unit installing and operating a unit with the incorrect voltage may result in malfunction or other issues and will void the warranty 2 Units must be connected to a corr...

Страница 4: ...lation parameters The below data is for the Northeast section of the US Increase capacity by 25 for the East 30 for the South and 40 for the West Computer or Data Server Rooms These require ballpark s...

Страница 5: ...d for the new refrigerant R410A units For connecting pipes use new and clean piping materials with high pressure fittings made for R410A only The best and recommended solution is not to use the existi...

Страница 6: ...door unit closer to the indoor unit and also for a convenient installation We offer wall brackets Our Catalog BR 440L for up to 440 lbs as an accessory UNIT INSTALLATION CAUTION Follow Instructions fa...

Страница 7: ...nit must be located a minimum of 4 ft from the floor and 6 from the ceiling Choose an area where the wall is plumb and determine how to best run the unit interconnects ALL VIEWED FROM FRONT SIDE L R H...

Страница 8: ...n the left and right sides of the unit to route the piping and wiring connections Drill a 3 diameter hole through the wall for line set If using the installation kit measure the diameter of the sleeve...

Страница 9: ...d the 16 AWG interconnect wiring between indoor and outdoor maximum of wires required is 4 through the unit electrical connection if required by local codes an electrical connector can be attached to...

Страница 10: ...le may be required Ensure location does not impede access around unit and pose a disturbance to neighboring areas Step 8 Refrigerant Line Set Piping Interconnecting line set between the outdoor unit a...

Страница 11: ...alled must have a separate branch circuit with an individual breaker fuse A local disconnect should be installed adjacent to the outdoor unit in accordance with National and Local Electrical Codes The...

Страница 12: ...L1 L2 S L1 L2 S L1 L2 L1 L2 S L1 L2 S L1 L2 24K 230VAC Green wire for GND Green wire for GND Green wire for GND Note 1 When connecting terminals wire color is not important except green which should a...

Страница 13: ...ilding codes Remember water only flows downhill to ensure positive draining from the unit Check using water for a positive flow of condensate Route the condensate hose on the bottom of the bundle maki...

Страница 14: ...tems Remove brass caps from the service valves Open the SUCTION line valve first to prevent any possibility of oil clogged in the capillary tube This can occur if the liquid line valve is opened first...

Страница 15: ...7 25 oz 8 86 oz 12A45YMI 12H45YMI 0 161 oz 0 81 oz 1 61 oz 3 22 oz 4 03 oz 5 64 oz 7 25 oz 8 86 oz 12A45ZMI 12H45ZMI 0 161 oz 0 81 oz 1 61 oz 3 22 oz 4 03 oz 5 64 oz 7 25 oz 8 86 oz 18A45ZMI 18H45ZMI...

Страница 16: ...ure should match the charts readings Cooling chart COOLING MODE Outdoor Temp Indoor Temp v 75 F 85 F 95 F 105 F 115 F 70 F 119 0 113 0 117 0 125 0 147 0 PSI 75 F 124 0 120 0 126 0 132 0 155 0 PSI 80 F...

Страница 17: ...p v 57 F 47 F 37 F 27 F 17 F 55 F 439 0 413 0 367 0 330 0 302 0 PSI 65 F 471 0 435 0 386 0 368 0 339 0 PSI 75 F 489 0 457 0 403 0 381 0 362 0 PSI Pressure PSI Outdoor Temperature It is recommended to...

Страница 18: ...uF 3 0 3 0 Speed H M L RPM 1200 1050 800 1200 1050 850 Indoor air flow H M L CFM 480 420 320 480 420 320 Indoor noise level H M L dB A 39 35 28 39 35 28 Indoor unit Dimension W D H IN 26 77x7 01x10 04...

Страница 19: ...apacitor uF 3 0 3 0 Speed H M L RPM 1200 1050 800 1200 1050 800 Indoor air flow H M L CFM 580 500 400 580 500 400 Indoor noise level H M L dB A 39 35 29 39 35 29 Indoor unit Dimension W D H IN 30 31X7...

Страница 20: ...ut W 43 43 Capacitor uF 1 5 1 5 Speed H M L RPM 1200 1050 800 1200 1050 800 Indoor air flow H M L CFM 600 530 400 600 530 400 Indoor noise level H M L dB A 39 35 31 39 35 31 Indoor unit Dimension W D...

Страница 21: ...5 Capacitor uF 1 5 1 5 Speed H M L RPM 1250 1100 800 1250 1100 800 Indoor air flow H M L CFM 750 660 480 750 660 480 Indoor noise level H M L dB A 42 39 31 42 39 31 Indoor unit Dimension W D H IN 35 6...

Страница 22: ...W 80 5 80 5 Capacitor uF 3 0 3 0 Speed H M L RPM 1200 1100 900 1200 1100 900 Indoor air flow H M L CFM 1250 1150 950 1250 1150 950 Indoor noise level H M L dB A 47 45 39 49 45 39 Indoor unit Dimensio...

Страница 23: ...ace outdoor temperature sensor and or replace indoor PCB F2 Condenser coil temperature sensor T3 open circuit or short circuit Replace condenser coil temperature sensor and or replace indoor PCB F3 Co...

Страница 24: ...line in a fine mist with ice crystals forming at the point of expansion Freeze up is not the only problem caused by moisture It can also result in corrosion the effects of which are not apparent until...

Страница 25: ...a reasonable time after the unit is returned This warranty does not cover Damage accidental or otherwise to the unit while in possession of the consumer that is not a result of a defect in material in...