950-0211revA - 14 - March 7, 2014
Energize the breaker to power up the system.
Compressor has a 3 minute time delay on startup
.
NOTE: Outdoor unit is
pre-charged
with enough R410A refrigerant for a line set up to 25 ft. long. For
longer line set lengths additional charge must be WEIGHED in per the following table.
Unit
Chart shows amount of additional refrigerant needed with different length line sets.
oz/ft
30ft
35 ft.
45 ft.
50 ft
60 ft.
70 ft.
80 ft.
9A45YMI
9H45YMI
0.161 oz 0.81 oz
1.61 oz
3.22 oz
4.03 oz
5.64 oz
7.25 oz
8.86 oz
12A45YMI
12H45YMI
0.161 oz 0.81 oz
1.61 oz
3.22 oz
4.03 oz
5.64 oz
7.25 oz
8.86 oz
12A45ZMI
12H45ZMI
0.161 oz 0.81 oz
1.61 oz
3.22 oz
4.03 oz
5.64 oz
7.25 oz
8.86 oz
18A45ZMI
18H45ZMI
0.161 oz 0.81 oz
1.61 oz
3.22 oz
4.03 oz
5.64 oz
7.25 oz
8.86 oz
24A45ZMI
24H45ZMI
0.322 oz
1.61 oz
3.22 oz
6.44 oz
8.05 oz
11.27 oz 14.49 oz 17.71 oz
DO NOT EXCEED THE SPECIFIED MAXIMUM LINE LENGTH.
EXAMPLE: 30 ft. total length
– 25 ft. pre-charge = 5 ft. x 0.161 oz per ft. = 0.81 oz. additional refrigerant.
Calculate your additional charge here:
____ - ____ = ____ X ____ = ______
CAUTION:
Capacity is based on standard length and maximum allowance length is base of reliability. Oil trap
should be installed per 17 - 23 feet.