6.  Description and settings

removable, 

lockable (internal) 

button

bezel frame

lens

max. 3 potentiometers (LUX, TIME, 

MODE)

Setting options via potentiometer

Setting the brightness (LUX)

You can set different brightness values with the brightness 

potentiometer (factory setting 500 lx).

†

Set potentiometer to desired switch-on brightness 

(5 – 1000 lux/on).

On the 

on

 setting the detector always responds to move-

ment, regardless of the brightness.

†

Turn the potentiometer to 

Teach-in

; after 20 s (red LED 

fl ashes) the detector saves the current surrounding bright-

ness as the new switch-on brightness.

!

Teach-in at 2-wire motion detector 

(theMura S180-100 

2W)

†

Set the time delay at the staircase light timer switch to 

minimum.

†

Set the potentiometer to 

teach-in

 .

The detector saves the current surrounding bright-

ness after 75 s (red LED fl ickers) as the new switch-on 

brightness.

†

Set the desired time delay at the staircase lighting timer 

switch.

Setting the time delay (TIME)

If the detector detects no further movement, it switches off 

after the set time delay. If you want to change the preset time 

(factory setting 10 min)

†

Set the potentiometer to the desired time (10 s, 1 min, 

5 min, 10 min, 30 min).

If you wish to use the pulse function (e.g. for a staircase light 

timer switch)

†

Set the potentiometer to  . As long as motion is detected, 

the contact closes every 10 s for 0.5 s.

L

At the 2-wire motion detector (theMura S180-100 2W), no 
time delay can be set. The time delay set on the staircase 
lighting timer switch applies. The time delay of the stair-
case light timer switch is restarted at regular intervals in 
case of motion or when the light falls below the bright-
ness setpoint.

Test detection area (walking test)

The walking test is used to test the detection area and to 

restrict it if necessary.

†

Set the time potentiometer (TIME) to 

test

The detector always responds to movements (regard-

less of brightness and confi guration type).

After the detector has detected a movement, all con-
tacts switch on for 2 s.

L

At the 2-wire motion detector (theMura S180-100 2W), 
the contact does not switch during the detected motion.

If motion is detected the red LED on the master lights 
up.

Performing the walking test using the button (only for slave 

devices)

†

Press the button for 10 s

If motion is detected the red LED on the slave lights up.

Test mode is activated for 10 min.

†

Briefl y press the button

The test mode is ended and the detector returns to 
normal operation.

Содержание 2060650

Страница 1: ...es ponding theSenda Plug app iOS Android theSenda B app for short bezel frames adapted for different switch ranges can be ordered optionally theMura S180 100 bezel frames adapted for different switch ranges can be ordered optionally see www theben de theMura 2 Safety Assembly and installation should only be carried out by a qualified electrician somebody who has completed appropriate professional ...

Страница 2: ...A 1 3 6 6 plus 8 max 6 detectors with ELPA 041 047 LThe time delay is set at the staircase light timer switch Do not connect the lighting directly to the detector The 4 conductor switching must be used for the stair case light timer switch L N Master L L Master L L N L 4 3 e g ELPA 2 x theMura S180 100 2W UP onlyTheben devices max 12 pieces 5 Installation LFor installation in device housing concea...

Страница 3: ...he potentiometer to the desired time 10 s 1 min 5 min 10 min 30 min If you wish to use the pulse function e g for a staircase light timer switch Set the potentiometer to As long as motion is detected the contact closes every 10 s for 0 5 s LAt the 2 wire motion detector theMura S180 100 2W no time delay can be set The time delay set on the staircase lighting timer switch applies The time delay of ...

Страница 4: ... min theMura S180 101 When the button is pressed briefly the light switches on for a certain time depending on the duration of motion and the set time delay LWith theMura S180 101 the surrounding brightness is checked after 30 min If there is sufficient brightness the light is switched off despite the presence of persons Switching off manually 2 min 30 s 30 s 30 s 2 s 2 s t t t Normalbetrieb Norma...

Страница 5: ...te control Open the theSenda Plug app Press the Bluetooth symbol in the app on the top left hand side Briefly press the Bluetooth button on theSenda B LED flashes red devices are searched for Confirm with OK LED lights up red 9 Parameters and control commands via app 1 Parameters Brightness setpoint value A theSenda B app theSenda P Brightness actual value A Check of the current measured actual br...

Страница 6: ...vity The detector has 3 sensitivity levels Level Sensitivity 1 Very insensitive 2 Insensitive 3 Standard default theSenda B app theSenda P Time delay A theSenda B app theSenda P Short presence A If a room is only occupied briefly the channel A time delay is ended early 2 min provided that the set time delay is 2 min Channel function H Channel H presence isolated contact e g to control a fan in the...

Страница 7: ...n it can be switched on manually but not switched off The light will not be switched off again until after the set time delay Orientation light time delay The integrated orientation light conveys a sense of security and good orientation in dark rooms and corridors Time delay When the channel A time delay has expired the orientation light comes on for the set time delay On The orientation light alw...

Страница 8: ...enables use even in rooms with alcoves The function is activated as soon as the light channel A is switched on Each time an acoustic signal is detected the channel A time delay is restarted If the light goes out the microphone is only activated briefly LIf the set brightness target value A is exceeded the micro phone is switched off Level Sensitivity Off Deactivated default 1 Insensitive 2 Standar...

Страница 9: ... Acoustic sensor sensitivity Off LED display motion Off Switch on behaviour Start up phase 45 s after restoration of power The red LED flashes at one second intervals all switch contacts are closed The detector does not respond to push button com mands and remote control commands When no one is present all contacts open after 45 s Operation The detector is ready for operation LED off LED display L...

Страница 10: ...ad Compact fluorescent lamps LED lamps 2060650 2060653 2060750 2060655 2060755 2300 W 2060650 2060653 2060750 2060655 2060755 1150 VA 2060650 2060653 2060750 2060655 2060755 2 W type 40 W 2 W type 450 W 2060660 2060760 2060670 2060770 Switching capacity H 50 W 50 VA max 2 A 2060655 2060755 Contact type H µ contact Protection rating IP 20 in accordance with EN 60529 Protection class II in accordanc...

Страница 11: ...11 13 Contact Theben AG Hohenbergstr 32 72401 Haigerloch GERMANY Phone 49 7474 692 0 Fax 49 7474 692 150 Hotline Phone 49 7474 692 369 hotline theben de Addresses telephone numbers etc www theben de ...

Отзывы: