background image

4

Recommended guide values

Transit zones (not work areas)

approx. 5 min

School rooms, basements

approx. 10 min

Work areas (offi ce, etc.), toilets

approx. 10 min

Setting the MODE (fully or semi-automatic) with 

staircase light function

Staircase light function  – corridor off/corridor on  

With the 

corridor off

 staircase light function the light can be 

switched on and off manually using the button at any time. 

With 

corridor on

 it can be switched on manually but not swit-

ched off. The light will not be switched off again until after 

the set time delay.

Configuration type – auto/man
auto

 = fully automatic

The lighting is switched on and off automatically (based on 

presence, absence and brightness)

man

 = semi-automatic

The lighting is always switched on manually. It is switched off 

by the detector.

7.  Manual operation using the button 

(internal or external)

The button can be used to manually switch the lighting at any 

time. The response varies depending on the detector type.

Switching on manually

> 30 s

< 30 s

< 2 s

< 2 s

t

t

t

> 30 s +  eingestellte 

 Nachlaufzeit

2 min  30 s

theMura S180-100

> 30 min

> 30 s

< 30 s

< 2 s

< 2 s

< 2 s

t

t

t

30 s + eingestellte 

 Nachlaufzeit

> 30 s +  eingestellte 

 Nachlaufzeit

Helligkeitsüberprüfung

nach 30 min

theMura S180-101

When the button is pressed briefl y, the light switches on for a 

certain time (depending on the duration of motion and the set 

time delay).

L

With theMura S180-101, the surrounding brightness is 

checked after 30 min. If there is suffi cient brightness, the 

light is switched off despite the presence of persons.

Switching off manually

2 min  30 s

> 30 s

< 30 s

< 2 s

< 2 s

t

t

t

Normalbetrieb

Normalbetrieb

> 30 s +  eingestellte 

 Nachlaufzeit

theMura S180-100

> 30 s

< 30 s

< 2 s

< 2 s

t

t

t

30 s + eingestellte 

 Nachlaufzeit, 

 

max. 2 min

Normalbetrieb

Normalbetrieb

> 30 s +  eingestellte 

 Nachlaufzeit

theMura S180-101

If the light is switched on, it can be switched off for a certain 

time by briefl y pressing the button (depending on the dura-

tion of the motion   and the set time delay). Afterwards, the 
detector returns to normal operation.

L

In the case of the 2-wire motion detector, when the button 
is pressed only a short pulse is sent to the staircase light 
timer switch.

integrated button 

activated

integrated button 

deactivated

8.  Parameters and control commands via 

remote control

L

Only with presence detectors (2060755)

The following parameters can be checked or changed via 

the remote control for support during start-up as well as 

servicing:

Parameter

theSenda B/

app check

Can be 

changed by 

theSenda B/

app

Can be 

changed by 

theSenda P

Brightness setpoint 

value A

X

X

X

Brightness actual 

value A

X

Содержание 2060650

Страница 1: ...es ponding theSenda Plug app iOS Android theSenda B app for short bezel frames adapted for different switch ranges can be ordered optionally theMura S180 100 bezel frames adapted for different switch ranges can be ordered optionally see www theben de theMura 2 Safety Assembly and installation should only be carried out by a qualified electrician somebody who has completed appropriate professional ...

Страница 2: ...A 1 3 6 6 plus 8 max 6 detectors with ELPA 041 047 LThe time delay is set at the staircase light timer switch Do not connect the lighting directly to the detector The 4 conductor switching must be used for the stair case light timer switch L N Master L L Master L L N L 4 3 e g ELPA 2 x theMura S180 100 2W UP onlyTheben devices max 12 pieces 5 Installation LFor installation in device housing concea...

Страница 3: ...he potentiometer to the desired time 10 s 1 min 5 min 10 min 30 min If you wish to use the pulse function e g for a staircase light timer switch Set the potentiometer to As long as motion is detected the contact closes every 10 s for 0 5 s LAt the 2 wire motion detector theMura S180 100 2W no time delay can be set The time delay set on the staircase lighting timer switch applies The time delay of ...

Страница 4: ... min theMura S180 101 When the button is pressed briefly the light switches on for a certain time depending on the duration of motion and the set time delay LWith theMura S180 101 the surrounding brightness is checked after 30 min If there is sufficient brightness the light is switched off despite the presence of persons Switching off manually 2 min 30 s 30 s 30 s 2 s 2 s t t t Normalbetrieb Norma...

Страница 5: ...te control Open the theSenda Plug app Press the Bluetooth symbol in the app on the top left hand side Briefly press the Bluetooth button on theSenda B LED flashes red devices are searched for Confirm with OK LED lights up red 9 Parameters and control commands via app 1 Parameters Brightness setpoint value A theSenda B app theSenda P Brightness actual value A Check of the current measured actual br...

Страница 6: ...vity The detector has 3 sensitivity levels Level Sensitivity 1 Very insensitive 2 Insensitive 3 Standard default theSenda B app theSenda P Time delay A theSenda B app theSenda P Short presence A If a room is only occupied briefly the channel A time delay is ended early 2 min provided that the set time delay is 2 min Channel function H Channel H presence isolated contact e g to control a fan in the...

Страница 7: ...n it can be switched on manually but not switched off The light will not be switched off again until after the set time delay Orientation light time delay The integrated orientation light conveys a sense of security and good orientation in dark rooms and corridors Time delay When the channel A time delay has expired the orientation light comes on for the set time delay On The orientation light alw...

Страница 8: ...enables use even in rooms with alcoves The function is activated as soon as the light channel A is switched on Each time an acoustic signal is detected the channel A time delay is restarted If the light goes out the microphone is only activated briefly LIf the set brightness target value A is exceeded the micro phone is switched off Level Sensitivity Off Deactivated default 1 Insensitive 2 Standar...

Страница 9: ... Acoustic sensor sensitivity Off LED display motion Off Switch on behaviour Start up phase 45 s after restoration of power The red LED flashes at one second intervals all switch contacts are closed The detector does not respond to push button com mands and remote control commands When no one is present all contacts open after 45 s Operation The detector is ready for operation LED off LED display L...

Страница 10: ...ad Compact fluorescent lamps LED lamps 2060650 2060653 2060750 2060655 2060755 2300 W 2060650 2060653 2060750 2060655 2060755 1150 VA 2060650 2060653 2060750 2060655 2060755 2 W type 40 W 2 W type 450 W 2060660 2060760 2060670 2060770 Switching capacity H 50 W 50 VA max 2 A 2060655 2060755 Contact type H µ contact Protection rating IP 20 in accordance with EN 60529 Protection class II in accordanc...

Страница 11: ...11 13 Contact Theben AG Hohenbergstr 32 72401 Haigerloch GERMANY Phone 49 7474 692 0 Fax 49 7474 692 150 Hotline Phone 49 7474 692 369 hotline theben de Addresses telephone numbers etc www theben de ...

Отзывы: