CL-B101D40HZ Manual (d0098)

Page 9

STEP M

STEP N

STEP O

STEP P

STEP Q

STEP R

STEP S

STEP T

STEP U

[orAn]

[rEd]

NOTE: Will only 

appear if a tricolor 

display is installed

[orAn]

[rEd]

[orAn]

[rEd]

[orAn]

[rEd]

[orAn]

[rEd]

BARGRAPH COLOR 

PROGRAMMING MODE

Operational Display

Operational Display

From From Step L of

Setpoint Setting and Relay

Configuration Page 8

L or h

L or h

L or h

L or h

To comply with the latest safety requirements, the tri-color bargraph is designed like a traffic light, to 

display either red, orange or green, but only one color at a time.  When the bar reaches a selected 

color change point, the entire bar will change to the color designated for that zone.  This eliminates any 

ambiguity as to the signal status, especially just after transitioning to a new zone.

First (Step Q) is to select the color to be displayed, when the bar is “below*”, whichever set point is set 

to the lowest position.

Second (Steps R, S, T, and U) is to select the color to be displayed when the bar is above each specific 

set point, regardless of the order or position to which the set points are set.

However, if two or more setpoints with differently specified colors are positioned at the same set point 

value, the color specified for the set point with the highest identifying number will be displayed. When 

set points are set to the same value, the SP4 color overrides the SP3 color, the SP3 color overrides the 

SP2 color, and the SP2 color overrides the SP1 color.

STEP Q  Select Bargraph Color when the bar is BELOW* the Setpoint that is set to the lowest 

position

 

1)  Using the   and   

buttons, select the desired bargraph color [grn], [oran] or [red]

 

2)  Press the 

P

 button. Display toggles between [CSP1] and the previous color setting.

STEP R  Select Bargraph Color when the bar is ABOVE* SP1 Setpoint

 

1)  Using the   and 

 buttons, select the desired bargraph color [grn], [oran] or [red]

 

2)  Press the 

P

 button. Display toggles between [CSP2] and the previous color setting.

STEP S  Select Bargraph Color when the bar is ABOVE* SP2 Setpoint

 

1)  Using the   and 

 buttons, select the desired bargraph color [grn], [oran] or [red]

 

2)  Press the 

P

 button. Display toggles between [CSP3] and the previous color setting.

STEP T  Select Bargraph Color when the bar is ABOVE* SP3 Setpoint

 

1)  Using the   and 

 buttons, select the desired bargraph color [grn], [oran] or [red]

 

2)  Press the 

P

 button. Display toggles between [CSP4] and the previous color setting.

STEP U  Select Bargraph Color when the bar is ABOVE* SP4 Setpoint

 

1)  Using the   and 

 buttons, select the desired bargraph color [grn], [oran] or [red]

 

2)  Press the 

P

 button. The meter exits the setpoint mode and returns to the operational 

display.

The Bargraph Color programming mode is now complete.

STEP M  Set Relay Activation mode [rLYS] for SP1

 

(h) High the relay energizes when the setpoint is exceeded. (L) Low the relay energizes below 

the setpoint. The setpoint is indicated from left to right SP1, SP2, SP3, SP4.

 

1)  Using the   and   buttons, select (L) or (h) for the first digit, which corresponds to SP1.

 

2)  Press the 

P

 

button.  The SP2 Relay Activation digit begins to flash, and its decimal point is lit.

STEP N  Set High (h) or Low (L) for SP2

 

1)  Using the   and   buttons, select (L) or (h) for the second digit, which corresponds to SP2.

 

2)  Press the 

P

 

button.  The SP3 Relay Activation digit begins to flash, and its decimal point is lit.

STEP O  Set High (h) or Low (L) for SP3

 

1)  Using the   and   buttons, select (L) or (h) for the third digit, which corresponds to SP3.

 2) 

Press the 

P

 

button.  The SP4 Relay Activation digit begins to flash, and its decimal point is lit.

STEP P  Set High (h) or Low (L) for SP4

 1) 

Using the   and   buttons, select (L) or (h) for the fourth digit, which corresponds to SP4. 

2)  Press the 

P

 button. 

 

If a mono-color red or green display is installed then the Setpoint Relay Programming Mode is now complete and the 

meter returns to the operational display. 

If a tricolor bargraph display is installed then the Bargraph Color Programming Mode will be entered and 

display toggles between [CoL] and the previous setting. Color selection menu will be displayed. 

Setpoint Setting and Relay Configuration Mode Continued

Bargraph Color Programming Mode

Содержание CL-B101D40HZ

Страница 1: ...Mode Selection 6 Bargraph Color Programming Mode 9 Case Dimensions 13 Component Layout 11 Connector Pinouts and Pin Descriptions 10 11 Controls and Indicators 2 Decimal Point and Brightness Selection...

Страница 2: ...irection indicated by the arrow When an alternative dotted line is shown this indicates that an alternative logic branch will be followed when a particular option is present When two buttons are shown...

Страница 3: ...See Page 5 Goes directly to Zero setting if Analog Output is not installed 4 00 20 00 Range 99 99 9999 999 9 Select one of three Ranges 99 99Hz 999 9Hz or 9999Hz PROGRAMMABLE OFFSET AND SCALE FACTOR...

Страница 4: ...6 meter may be rescaled without applying an external signal by changing the Offset and Scale factor Offset is the reading that the meter will display for a zero input The Offset may be set to any valu...

Страница 5: ...this point the display skips directly to STEP G and toggles between Cto and oFF the software is detecting that the optional analog output hardware is NOT installed Digital Span Selection For Bargraph...

Страница 6: ...h and AnLo analog low can be reversed to provide a 20 to 4mA output The digital span selected can be as small as two counts when using the analog output to function as a Control or Alarm Driver Small...

Страница 7: ...volt output selected However the output of cLo must always be less than the value selected for chi If a reversed analog output is desired the values selected to establish the Digital Span can be reve...

Страница 8: ...ress the P button Display toggles between PUM and on or oFF STEP F Select Pump PUM on or oFF 1 Using the and buttons select the Pump to be ON or OFF When PUM is selected ON and SP2 is set at a value h...

Страница 9: ...argraph Color when the bar is ABOVE SP2 Setpoint 1 Using the and buttons select the desired bargraph color grn oran or red 2 Press the P button Display toggles between CSP3 and the previous color sett...

Страница 10: ...mp Form A relays An analog output module is also shown as installed The CL B101D40HZ uses plug in type screw terminal connectors for all input and output connections The power supply connec tions pins...

Страница 11: ...A SP4 SP3 SP2 SP1 SP1 SP2 SP3 SP4 Relay Modules with 4 Isolated 5A Form A Relays Output Carrier Board Output Carrier Board Relay Module Relay Module Input Signal Conditioner Analog Output Module Main...

Страница 12: ...ditioning Modules COUPLING INPUT SIGNAL FILTER MAG NAMUR SOURCE SINK LOAD AC 20KHz 2KHz 200Hz OFF DC MAG AC LOGIC GND 24V INPUT High Accuracy Digital Measurement NPN Open Collector Proximity Switch No...

Страница 13: ...t the meter from external noise Input output leads should be routed as far away as possible from contactors control relays transformers and other noisy components Shielding cables for input output lea...

Страница 14: ...y 50 POWER SUPPLY PS1 85 265VAC 95 300VDC N C PS2 18 48VAC 10 72VDC 40 INPUT MODULES Partial List See www texmate com Unless otherwise specified Texmate will ship all modules precalibrated with factor...