CL-B101D40HZ Manual (d0098)

Page 5

Example

Example

From Two Point

Digital Calibration 

Mode See Page 4

STEP A

STEP B

STEP C

STEP D

See Example Above

of Bargraph Display 

Scale Range

To Digital Span Selection

for Analog Range Output or

Bargraph Center Point

Display Mode Selection

on Page 6 or 7

DIGITAL SPAN SELECTION

FOR BARGRAPH DISPLAY

[X•XXX]

[XX•XX]

[XXX•X]

[XXXX•]

[XXXX]

DECIMAL POINT AND

BRIGHTNESS SELECTION

STEP A  Enter the Calibration Sub Menu Mode

 

1)  Press the 

P

 and   buttons at the same time. Display toggles 

between [CAL] and [oFF]. 

 

2)  Press the 

P

  button.  Display  toggles  between  [bhi]  and  the 

p re v i o u s 

setting.

                            

STEP B  Set the Digital Span of the Bargraph Display (See example 

above)

 

1) Using the   and   buttons, adjust the display to the 

desired  

high parameter reading, e.g. 6000 counts.

 

2)  Press the 

P

 button. Display toggles between [bLo] and the 

previous setting.

 

3) Using the   and   buttons, adjust the display to the 

desired  

low parameter reading, e.g. 4000 counts.

 

4)  Press the 

P

 button. Display changes from [4000] to [dP].  

STEP C  Set the Decimal Point

 

1)  Using the   and   buttons, adjust the display to the   

  

     desired decimal point setting.

 

2)  Press the 

P

 button. Display toggles between [br] and the 

 

  previous brightness setting.

STEP D  Set the Bargraph and Digital Display Brightness

 

1)  Using the   and   buttons, adjust the display to the 

 

     desired brightness setting (4 is the brightest setting).

 

2)  Press the 

P

 button. Display toggles between [Anhi] and  

 

     the previous [Anhi] setting.

Note:  If  at  this  point,  the  display  skips  directly  to  STEP  G  and  toggles 

between [Cto] and [oFF], the software is detecting that the optional analog 

output hardware is NOT installed.

Digital Span Selection For Bargraph Display

Decimal Point and Brightness Selection

Bargraph does not light 

up for Input Signals up to 

3999 counts 

Bargraph lights up for 

Input Signals above 

4000 counts

Bar

High

Bar

Low

Bar

High

Bar

Low

0

25

75

100

50

0

25

75

100

50

No bargraph display

Digital display

No bargraph display

Digital display

An example of setting the 

digital span of the bargraph 

display to be different than 

the digital display range

The bargraph can be set to display full scale (0-101 bars) any portion 

of the digital reading from a minimum of 100 counts to a maximum of 
12,000  counts. This provides higher resolution bargraph indication for 

those applications where the normal operating input signal range is less 
than the desired full scale display range of the digital display.

For Example:

If the full scale range of the meter has been set from -1999 to 
9999 (0-12,000 counts), but the normal operating range of the 
input signal is between 4000 & 6000. The bargraph high parame-
ter [bhi] can be set to 6000 and the bargraph low parameter [bLo] 
can be set to 4000. 

This means that although the meter could digitally display a signal 
from -1999 to 9999 (0-12,000 counts), the bargraph display only 
begins to function at a reading of 4000, and reaches full scale 
indication at a reading of 6000. Although the digital display will 
continue reading up to 9999 before indicating overrange, the bar-
graph display will indicate its overrange by flashing for readings 
above 6000.

Содержание CL-B101D40HZ

Страница 1: ...Mode Selection 6 Bargraph Color Programming Mode 9 Case Dimensions 13 Component Layout 11 Connector Pinouts and Pin Descriptions 10 11 Controls and Indicators 2 Decimal Point and Brightness Selection...

Страница 2: ...irection indicated by the arrow When an alternative dotted line is shown this indicates that an alternative logic branch will be followed when a particular option is present When two buttons are shown...

Страница 3: ...See Page 5 Goes directly to Zero setting if Analog Output is not installed 4 00 20 00 Range 99 99 9999 999 9 Select one of three Ranges 99 99Hz 999 9Hz or 9999Hz PROGRAMMABLE OFFSET AND SCALE FACTOR...

Страница 4: ...6 meter may be rescaled without applying an external signal by changing the Offset and Scale factor Offset is the reading that the meter will display for a zero input The Offset may be set to any valu...

Страница 5: ...this point the display skips directly to STEP G and toggles between Cto and oFF the software is detecting that the optional analog output hardware is NOT installed Digital Span Selection For Bargraph...

Страница 6: ...h and AnLo analog low can be reversed to provide a 20 to 4mA output The digital span selected can be as small as two counts when using the analog output to function as a Control or Alarm Driver Small...

Страница 7: ...volt output selected However the output of cLo must always be less than the value selected for chi If a reversed analog output is desired the values selected to establish the Digital Span can be reve...

Страница 8: ...ress the P button Display toggles between PUM and on or oFF STEP F Select Pump PUM on or oFF 1 Using the and buttons select the Pump to be ON or OFF When PUM is selected ON and SP2 is set at a value h...

Страница 9: ...argraph Color when the bar is ABOVE SP2 Setpoint 1 Using the and buttons select the desired bargraph color grn oran or red 2 Press the P button Display toggles between CSP3 and the previous color sett...

Страница 10: ...mp Form A relays An analog output module is also shown as installed The CL B101D40HZ uses plug in type screw terminal connectors for all input and output connections The power supply connec tions pins...

Страница 11: ...A SP4 SP3 SP2 SP1 SP1 SP2 SP3 SP4 Relay Modules with 4 Isolated 5A Form A Relays Output Carrier Board Output Carrier Board Relay Module Relay Module Input Signal Conditioner Analog Output Module Main...

Страница 12: ...ditioning Modules COUPLING INPUT SIGNAL FILTER MAG NAMUR SOURCE SINK LOAD AC 20KHz 2KHz 200Hz OFF DC MAG AC LOGIC GND 24V INPUT High Accuracy Digital Measurement NPN Open Collector Proximity Switch No...

Страница 13: ...t the meter from external noise Input output leads should be routed as far away as possible from contactors control relays transformers and other noisy components Shielding cables for input output lea...

Страница 14: ...y 50 POWER SUPPLY PS1 85 265VAC 95 300VDC N C PS2 18 48VAC 10 72VDC 40 INPUT MODULES Partial List See www texmate com Unless otherwise specified Texmate will ship all modules precalibrated with factor...

Отзывы: