5 Parameterizing, adjusting and analyzing software (P2A software)
60
Field
Explanation
Unit
Selection of the physical unit.
When changing the unit, standard values are
set for scale minimum and maximum.
Caution!
When changing the phys. unit, the relay limit
values are set to the assigned default values.
Signal delay
(graphic)
Curve changes according to the set signal
delay.
Signal delay
Time interval in stages 1 – 15:
1 = no delay
15 = longest delay.
The signal delay is added to the reaction time
of the sensor. The signal delay shows
averaging over the time interval of the
selected stage in seconds:
Example
Stage 10 = average of the readings from the
last 10 seconds.
The delay of the signal in relation to the change in the
process is also significantly influenced by the selection of
the particle filter.