- 16 -
ALARM AND STATUS GROUP BIT MEANING (TX100 PROTOCOL)
Addr
Alarms
BIT
Description
100
inverter heatsink overtemp
7(128)
1=ALARM 0=NORMAL
100
inverter output voltage high
6(64)
1=ALARM 0=NORMAL
100
inverter output voltage low
5(32)
1=ALARM 0=NORMAL
100
output overload
4(16)
1=ALARM 0=NORMAL
100
battery voltage high
3(8)
1=ALARM 0=NORMAL
100
internal overcurrent
2(4)
1=ALARM 0=NORMAL
100
phase synchron bad
1(2)
0=SYNCHRON 1=FREE RUNNING
100
bypass voltage bad
0(1)
1=ALARM 0=NORMAL
101
General UPS alarm
7(128)
1=ALARM 0=NORMAL
101
Output off
6(64)
1=ALARM 0=NORMAL
101
fuse failure
5(32)
1=ALARM 0=NORMAL
101
battery CB open
4(16)
1=ALARM 0=NORMAL
101
replace batteries
3(8)
1=ALARM 0=NORMAL
101
performing boost charge
2(4)
1=ALARM 0=NORMAL
101
rotate rectifier input phases
1(2)
1=ALARM 0=NORMAL
101
Emergency stop
0(1)
1=ALARM 0=NORMAL
102
Maintenance bypass
7(128)
1=ALARM 0=NORMAL
102
Manual bypass
6(64)
1=ALARM 0=NORMAL
102
Rectifier fault
5(32)
1=ALARM 0=NORMAL
102
mains failure on rectifier input
4(16)
1=ALARM 0=NORMAL
102
battery voltage low
3(8)
1=ALARM 0=NORMAL
102
load on bypass
2(4)
1=ON BYPASS 0=ON INVERTER
102
UPS fault
1(2)
1=ALARM 0=NORMAL
102
performing battery test
0(1)
1=PERFORMING TEST O=NORMAL
103
waiting shutdown or UPS shutdown
7(128)
1=ALARM 0=NORMAL
103
beeper off/on
6(64)
1=OFF 0=ON
103
Fan failure
5(32)
Not used
103
End off backup time
4(16)
1=ALARM 0=NORMAL
103
3(8)
NU
103
2(4)
NU
103
1(2)
NU
103
0(1)
NU