TX301 PROTOCOL HOLDING REGISTER  map  (for 3 phase UPS) 

MEASUREMENT GROUP (TX301 PROTOCOL)

 

Addr

  Parameter 

Unit 

PROTOCOL 

Min-max 

Rectifier module status codes

 

 

D1 

0-999 

Inverter module status codes

 

 

D1 

0-999 

Not used

 

 

 

Not used

 

 

 

10 

Not used

 

 

 

11 

Not used 

 

 

12 

Not used 

 

 

13 

Not used 

 

 

14 

INPUT VOLTAGE 1 phase-neutral 

D2 

0-511 

15 

INPUT VOLTAGE 2 phase-neutral

 

V

 

D2

 

0-512 

16 

INPUT VOLTAGE 3 phase-neutral

 

V

 

D2

 

0-512 

17 

INPUT VOLTAGE L1-L3 phase-phase 

D2 

0-511 

18 

INPUT VOLTAGE L2-L1 phase-phase

 

D2 

0-511 

19 

INPUT VOLTAGE L3-L2 phase-phase

 

D2 

0-511 

20 

INPUT CURRENT PHASE 1 (if option board is used) 

D2 

0-511 

21 

INPUT CURRENT PHASE 2 (if option board is used) 

D2 

0-511 

22 

INPUT CURRENT PHASE 3 (if option board is used) 

D2 

0-511 

23 

BYPASS VOLTAGE 1 phase-neutral 

D2 

0-511 

24 

BYPASS VOLTAGE 2 phase-neutral

 

V

 

D2

 

0-512 

25 

BYPASS VOLTAGE 3 phase-neutral

 

V

 

D2

 

0-512 

26 

BYPASS VOLTAGE L1-L3 phase-phase 

D2 

0-511 

27 

BYPASS VOLTAGE L2-L1 phase-phase

 

D2 

0-511 

28 

BYPASS VOLTAGE L3-L2 phase-phase

 

D2 

0-511 

29 

INPUR FREQUENCY 

Hz * 10 

D2 

0-999 

30 

BYPASS FREQUENCY 

Hz * 10 

D2 

0-999 

31 

Not used

 

 

 

32 

Not used 

 

 

33 

Not used 

 

 

34 

Not used 

 

 

35 

Not used 

 

 

36 

Not used 

 

 

37 

TOTAL BATTERY VOLTAGE 

D3 

0-999 

38 

POSITIVE BATTERY VOLTAGE 

D3 

0-512 

39 

NEGATIVE BATTERY VOLTAGE 

D3 

0-512 

40 

POSITIVE BATTERY CURRENT 

A * 10 

D3 

0-512 

41 

NEGATIVE BATTERY CURRENT 

A * 10 

D3 

0-512 

42 

BATTERY TEMPERATURE 

C * 10 

D3 

 

43 

BATTERY BACKUP TIME 

D3 

 

44 

POSITIVE DC BUS VOLTAGE 

D3 

 

45 

NEGATIVE DC BUS VOLTAGE 

D3 

 

46 

BATTERY GROUPS NUMBER 

 

D3 

 

47 

BATTERY RATING 

A/H 

D3 

 

48 

Not used 

 

 

49 

Not used 

 

 

50 

Not used 

 

 

51 

Not used 

 

 

52 

Not used 

 

 

53 

Not used 

 

 

54 

INVERTER VOLTAGE 1 phase-neutral 

D4 

0-511 

55 

INVERTER VOLTAGE 2 phase-neutral

 

V

 

D4

 

0-512 

56 

INVERTER VOLTAGE 3 phase-neutral

 

V

 

D4

 

0-512 

57 

OUTPUT VOLTAGE 1 phase-neutral 

D4 

0-511 

58 

OUTPUT VOLTAGE 2 phase-neutral

 

V

 

D4

 

0-512 

59 

OUTPUT VOLTAGE 3 phase-neutral

 

V

 

D4

 

0-512 

60 

OUTPUT VOLTAGE L1-L3 phase-phase 

D4 

0-511 

61 

OUTPUT VOLTAGE L2-L1 phase-phase

 

D4 

0-511 

62 

OUTPUT VOLTAGE L3-L2 phase-phase

 

D4 

0-511 

63 

OUPTUT FREQUENCY 

Hz * 10 

D4 

 

Содержание i-com Series

Страница 1: ...1 i com SERIES EXTERNAL UPS MODBUS TCP IP COMMUNICATION ADAPTER MDX NET INSTALLATION AND USER MANUAL...

Страница 2: ......

Страница 3: ...are correctly recycled in compliance with all applicable regulations Special precautions If the adaptor must be stored prior to installation storage must be in a dry place The admissible storage tempe...

Страница 4: ...1...

Страница 5: ...ata states and measures to be sent a computer system The system provides a communication channel between ethernet PC side and RS232 UPS side interface 1 4 Technical Specifications Function Parameter V...

Страница 6: ...r during power on please select device number from 1 to 255 by setting device number dip switches Where Dn is the nth dip switch For example if we need to set the device s address to 183 then we need...

Страница 7: ...232 Data Cable Max Length 25 meters parts pcs 9 pins D type connector male 1 9 pins D type connector female 1 3 wired shielded cable Max 25 meters 2 3 MDX NET Network connection UPS connector Pin Nr P...

Страница 8: ...staller This utility program finds all network connected MDX NET adaptor devices If it fails please change your network settings IP address and subnet mask as static IP to the following values t is on...

Страница 9: ...guration window and click on NEXT button NOTE The new IP address is different from 10 0 0 xxx or subnet mask is different from 255 0 0 0 value the adaptor connection may be lost in this case please re...

Страница 10: ...evice installer program window For detailed configuration we must connect to adaptor as WEB page to do this from device installer program click on WEB configuration Than click on GO button and device...

Страница 11: ...king checked Click on OK button for update settings at the end of page For MDX NET Ethernet configuration from the left side manu click on Connection related configuration page comes to screen Connect...

Страница 12: ...tor Lamp The indicator lamps on the MODBUS adaptor shows the status of communication Indicator lamp functions Lamp status Description RS232 led green Always on Adaptor power on and UPS RS232 connectio...

Страница 13: ...255 24 RECTIFIER INPUT FREQUENCY Not used 25 BYPASS FREQUENCY Hz 10 P1 0 999 26 INVERTER FREQUENCY Not used 27 OUTPUT FREQUENCY Bypass Freq if Bypass Hz 10 P1 0 999 28 INPUT CURRENT PHASE 1 if option...

Страница 14: ...r open S5 4 16 1 ALARM 0 NORMAL 101 replace batteries 3 8 1 ALARM 0 NORMAL 101 performing boost charge 432Vdc 2 4 1 ALARM 0 NORMAL 101 rotate rectifier input phases 1 2 1 ALARM 0 NORMAL 101 Emergency...

Страница 15: ...VOLTAGE L2 L1 phase phase V D2 0 511 28 BYPASS VOLTAGE L3 L2 phase phase V D2 0 511 29 INPUR FREQUENCY Hz 10 D2 0 999 30 BYPASS FREQUENCY Hz 10 D2 0 999 31 Not used 32 Not used 33 Not used 34 Not use...

Страница 16: ...ATURE SENSOR C 10 D6 92 TH2 TEMPERATURE SENSOR C 10 D6 93 TH3 TEMPERATURE SENSOR C 10 D6 94 FAN MAINTENANCE COUNTER D6 95 BATTERY MAINTENANCE COUNTER D6 96 GENERAL MAINTENANCE COUNTER D6 97 OPTIONAL M...

Страница 17: ...verter Overtemperature 4 16 1 ALARM 0 NORMAL 1 Output off warning 5 32 1 ALARM 0 NORMAL 1 Load on by pass 6 64 1 ALARM 0 NORMAL 1 Reverse inverter output current 7 128 1 ALARM 0 NORMAL 1 nverter modul...

Страница 18: ...ge limit 6 64 1 ALARM 0 NORMAL 4 Waiting DC BUS 7 128 1 ALARM 0 NORMAL 4 Battery failure 8 256 1 ALARM 0 NORMAL 4 Batt TEMP sensor failure 9 512 1 ALARM 0 NORMAL 4 Battery temperature high 10 1024 1 A...

Страница 19: ...neutral Bypass Not used 23 OUTPUT VOLTAGE 3 phase neutral Bypass Not used 24 RECTIFIER INPUT FREQUENCY Not used 25 BYPASS FREQUENCY Hz 10 P1 26 INVERTER FREQUENCY Not used 27 OUTPUT FREQUENCY Bypass...

Страница 20: ...y CB open 4 16 1 ALARM 0 NORMAL 101 replace batteries 3 8 1 ALARM 0 NORMAL 101 performing boost charge 2 4 1 ALARM 0 NORMAL 101 rotate rectifier input phases 1 2 1 ALARM 0 NORMAL 101 Emergency stop 0...

Страница 21: ...TABLE 18 REFER TO ALARM TABLE 19 REFER TO ALARM TABLE 20 Not used Not used 21 Not used Not used 22 Not used Not used 23 Not used Not used 24 OUTPUT LOAD PERCENTAGE L1 LOAD OPL 0 255 25 OUTPUT LOAD PER...

Страница 22: ...128 1 ALARM 0 NORMAL 17 SOURCE 2 Bad 6 64 1 ALARM 0 NORMAL 17 Synchron BAD 5 32 1 ALARM 0 NORMAL 17 Overload 4 16 1 ALARM 0 NORMAL 17 Non synchron inhibit 3 8 1 INHIBIT 0 NORMAL 17 Transfer inhibit 2...

Страница 23: ...19...

Отзывы: