- 10 -
ALARM AND STATUS GROUP BIT MEANING (TX300 PROTOCOL)
Addr
Alarms
BIT
Description
100
inverter heatsink overtemp ( >85
o
C )
7(128)
1=ALARM 0=NORMAL
100
inverter output voltage high ( >242V )
6(64)
1=ALARM 0=NORMAL
100
inverter output voltage low ( <170V )
5(32)
1=ALARM 0=NORMAL
100
output overload (>%150)
4(16)
1=ALARM 0=NORMAL
100
battery voltage high
3(8)
1=ALARM 0=NORMAL
100
IGBT overcurrent
2(4)
1=ALARM 0=NORMAL
100
Phase synchron bad
1(2)
0=SYNCHRON 1=FREE RUNNING
100
Bypass voltage bad ( 198V - 242V )
0(1)
1=ALARM 0=NORMAL
101
General UPS alarm
7(128)
1=ALARM 0=NORMAL
101
Output off
6(64)
1=ALARM 0=NORMAL
101
fuse failure
5(32)
1=ALARM 0=NORMAL
101
battery cicuit breaker open (S5)
4(16)
1=ALARM 0=NORMAL
101
replace batteries
3(8)
1=ALARM 0=NORMAL
101
performing boost charge ( +432Vdc )
2(4)
1=ALARM 0=NORMAL
101
rotate rectifier input phases
1(2)
1=ALARM 0=NORMAL
101
Emergency stop (Output OFF)
0(1)
1=ALARM 0=NORMAL
102
Maintenance bypass
7(128)
1=ALARM 0=NORMAL
102
Manual static bypass
6(64)
1=ALARM 0=NORMAL
102
Rectifier fault
5(32)
1=ALARM 0=NORMAL
102
mains failure on rectifier input
4(16)
1=ALARM 0=NORMAL
102
battery voltage low
3(8)
1=ALARM 0=NORMAL
102
load on bypass
2(4)
1=ON BYPASS 0=ON INVERTER
102
UPS fault
1(2)
1=ALARM 0=NORMAL
102
performing battery test
0(1)
1=PERFORMING TEST O=NORMAL
103
waiting shutdown or UPS shutdown
7(128)
1=ALARM 0=NORMAL
103
beeper off/on
6(64)
1=OFF 0=ON
103
Fan failure
5(32)
Not used
103
End off backup time (Battery out end)
4(16)
1=ALARM 0=NORMAL
103
3(8)
NU
103
2(4)
NU
103
1(2)
NU
103
0(1)
NU