TX300 PROTOCOL HOLDING REGISTER map (for 3 phase UPS)
MEASUREMENT GROUP (TX300 PROTOCOL)
Addr
Parameter
Unit
PROTOCOL
Min-max
0
RECTIFIER INPUT VOLTAGE 1 phase-neutral ( * )
V
P1
0-511
1
RECTIFIER INPUT VOLTAGE 2 phase-neutral ( * )
V
P1
0-511
2
RECTIFIER INPUT VOLTAGE 3 phase-neutral ( * )
V
P1
0-511
3
Not used
4
Not used
5
Not used
6
BYPASS INPUT VOLTAGE 1 phase-phase
Not used
7
BYPASS INPUT VOLTAGE 2 phase-phase
Not used
8
BYPASS INPUT VOLTAGE 3 phase-phase
Not used
9
BYPASS INPUT VOLTAGE 1 phase-neutral
V
P2
0-511
10
BYPASS INPUT VOLTAGE 2 phase-neutral
V
P2
0-511
11
BYPASS INPUT VOLTAGE 3 phase-neutral
V
P2
0-511
12
INVERTER OUTPUT VOLTAGE 1 phase-phase
Not used
13
INVERTER OUTPUT VOLTAGE 2 phase-phase
Not used
14
INVERTER OUTPUT VOLTAGE 3 phase-phase
Not used
15
INVERTER OUTPUT VOLTAGE 1 phase-neutral
Not used
16
INVERTER OUTPUT VOLTAGE 2 phase-neutral
Not used
17
INVERTER OUTPUT VOLTAGE 3 phase-neutral
Not used
18
OUTPUT VOLTAGE 1 phase-phase
Not used
19
OUTPUT VOLTAGE 2 phase-phase
Not used
20
OUTPUT VOLTAGE 3 phase-phase
Not used
21
OUTPUT VOLTAGE 1 phase-neutral (Bypass)
V
P2
0-255
22
OUTPUT VOLTAGE 2 phase-neutral (Bypass)
V
P2
0-255
23
OUTPUT VOLTAGE 3 phase-neutral (Bypass)
V
P2
0-255
24
RECTIFIER INPUT FREQUENCY
Not used
25
BYPASS FREQUENCY
Hz * 10
P1
0-999
26
INVERTER FREQUENCY
Not used
27
OUTPUT FREQUENCY (Bypass Freq. if Bypass)
Hz * 10
P1
0-999
28
INPUT CURRENT PHASE 1 (if option board is used)
A
P2
0-511
29
INPUT CURRENT PHASE 2 (if option board is used)
A
P2
0-511
30
INPUT CURRENT PHASE 3 (if option board is used)
A
P2
0-511
31
OUTPUT CURRENT 1
Not used
32
OUTPUT CURRENT 2
Not used
33
OUTPUT CURRENT 3
Not used
34
OUTPUT LOAD% 1 percentage
% LOAD
P2
0-255
35
OUTPUT LOAD% 2 percentage
% LOAD
P2
0-255
36
OUTPUT LOAD% 3 percentage
% LOAD
P2
0-255
37
TOTAL BATTERY VOLTAGE
V
P1
0-511
38
BATTERY CHARGE CURRENT
Not used
39
BATTERY DISCHARGE CURRENT
Not used
40
UPS INSIDE TEMPERATURE
Deg*10
P1 (if sensor used)
0-255
41
DEVICE NOMINAL ACTIVE POWER
W/100
F2
0-65535
42
DEVICE INPUT PHASES
F2
1-3
43
DEVICE OUTPUT PHASES
F2
1-3
44
DEVICE NOMINAL INPUT VOLTAGE
V
F2
45
DEVICE NOMINAL INPUT FREQUENCY
Hz
F2
46
NOMINAL BYPASS VOLTS
V
F2
47
NOMINAL BYPASS FREQUENCY
Hz
F2
48
NOMINAL OUTPUT VOLTAGE
V
F2
49
NOMINAL OUTPUT FREQUENCY
Hz
F2
( * ) : If split by-pass used, Rectifier Input Voltage indicates phase – phase.
50
NUMBER OF 12 VOLT BATTERIES
F2
0-255
51
FAULT OR STATUS CODE
P1
0-255
52
DEVICE CONFIGURATION
F2
0-1
53
DEVICE TYPE
F2
0-1
54
BYPASS CONFIGURATION
F2
0-1
55
BATTERY CONFIGURATION
F2
0-1
56
UPS PROTOCOL
0:TX100, 1:TX300, 2:MC114 (I/VVV)
0-255
57
MODBUS adaptor revision number
0-255