10.

 

Firmware update 

TCW110 

supports remote firmware update. To do this please follow the steps below: 

 

-

 

Download the latest firmware version from  

www.teracom.cc

 . The extension of 

the update file is .cod .  

-

 

Open Command Prompt window. In the example below in 

blue

 are the 

commands that must be entered, and in 

red

 are the descriptions of these 

commands : 

 

 

C:\>  --  

go to the directory where the update file is located ( .cod extension)

 

C:\>

ftp 212.73.154.53

   

--  

FTP connection to the controller is made

  

Connected to 212.73.154.53.  

220 Ready  

User (212.73.154.53:(none)): 

admin

  -- 

enter username

  

331 Password required  

Password: 

*****

      -- 

enter password 

230 Logged in  

ftp> 

put tera_ipv1.32a.cod

   --  

the update file is sent for update

  

200 Ok  

150 Transferring data...  

File is OK. Restarting Device...    – 

2 minutes after this message appears, the device will be 

successfully updated 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

ftp: 329798 bytes sent in 92.44Seconds 3.57Kbytes/sec 

ftp> 

 

 

 

 

 

 

 

Rev. 3 – January, 2011 

 

 

DO NOT TURN OFF THE POWER SUPPLY DURING THESE 2 MINUTES! 

TURNING OFF THE POWER SUPPLY WILL DAMAGE THE DEVICE! 

Содержание TCW110

Страница 1: ...rial process automation control and management of computer networks etc High precision digital temperature sensor is option 2 Features 10 Mbit Ethernet connectivity Password protected web based config...

Страница 2: ...nnectors is shown in the figure below The following indicators show the status of the controller Relay green this LED is illuminated whenever the relay is closed the Normally Open contact is closed an...

Страница 3: ...TCW110 using a web browser or by using custom SNMP applications 5 2 Remote monitoring A relay output from the monitored device is connected to digital input of TCW110 When an event occurs the control...

Страница 4: ...he web interface of the controller you should type the following URL into the browser http 192 168 1 2 If the network settings are correct the Login page will appear 7 Web based setup The web interfac...

Страница 5: ...ature if temperature sensor is connected to the controller 7 3 I O setup page The input and output settings are made in I O Setup page The following parameters can be set Description brief description...

Страница 6: ...input Digital Input 1 is changed To do this the following parameters must be set Description brief description of the input maximum 11 characters should be used Subject message subject maximum 11 cha...

Страница 7: ...factory default IP address at the same time It may be necessary to clear the arp cache each time you connect new device to the network This is done by typing arp d in the command prompt of a Windows...

Страница 8: ...ng conditions when event occurs on Digital Input 1 the signal changes its state measured voltage on Analog Input 1 is outside the predefined range measured temperature Is outside the predefined range...

Страница 9: ...ead write maximum number SNMP TRAP messages INTEGER 0 255 x 2 1 6 0 digitalInput1State read write Digital input 1 trap status INTEGER ON 1 OFF 0 x 2 1 8 1 0 voltage1minimum read write Voltage1 lower r...

Страница 10: ...0 VLANStatus read write VLAN status INTEGER ENABLED 1 DISABLED 0 x 4 8 2 0 VlanId read write VLAN ID INTEGER 0 4095 8 5 inputs OID Name Access Description Syntax x 5 1 1 0 input1description read writ...

Страница 11: ...estoring Factory Default Settings If the IP address or password are forgotten TCW110 can be restored to its original factory default settings To do this please follow the steps below remove the power...

Страница 12: ...od extension C ftp 212 73 154 53 FTP connection to the controller is made Connected to 212 73 154 53 220 Ready User 212 73 154 53 none admin enter username 331 Password required Password enter passwor...

Отзывы: