5
During the step measurement, this
page will be displayed on the screen, all
steps will be measured in order and
their values will be displayed on the
screen.
Capacitor values are shown with “-”
sign, shunt reactors are unsigned.
When the step measurement is finished, a confirmation page will be displayed on the
screen. When the SET button is pressed, all the measured steps are saved and when you
return to the measurements screen with the ESC button, the device starts to intervene.
Pressing the ESC button cancels the step measurements and returns to the Step
Measurement page without saving.
You can check the stored step values on the Step Values screen (2.1.1) in the Step
Menu.
When current transformer test is
successful, this page will be displayed on
the screen.
If the operation is confirmed by pressing
the SET button, the device will automatically
start the Step Measurement process.
After the test, it indicates that the
current transformer terminals indicated
with “(-)” are connected reversely. You
don't need to fix the links. The device will
fix these connections software-wise.
Step Measure. (kVAr)
1.Step
Esc:Cancel
L1:-3.333
L2:-3.333
Please Wait!
L3:-3.333
Step Measure. (kVAr)
TCR
Esc:Cancel Set:Ok
L1: 3.333
L2: 3.333
Step Meas. Finished!
L3: 3.333
Step Measure. (kVAr)
Step Values
Approved!
Please Wait!
7
8
9
Current Trans.Test(A)
Contacts Learned
k1-l1:(-)
k2-l2:(+)
k3-l3:(+)
Esc:Cancel Set:Ok
6
Measuring Screens
Cosinus(Cos)
L1: -1.000
L2: 1.000
L3: -1.000
_____________________
TCR
%
R:23 S:23 T:23
Offset
0.0
Figure-2
Active P Reactive Q
kW kVAr
L1:500.0 L1:-005.0
L2:500.0 L2: 002.0
L3:500.0 L3:-003.0
_____________________
TCR
%
R:23 S:23 T:23
Figure-3
Ratios(%) Ind. Cap.
Instant: 0.3 0.2
Hourly : 0.3 0.2
Daily : 0.3 0.2
Energy : 0.3 0.2
_____________________
TCR
%
R:23 S:23 T:23
Figure-4
Voltage-V Freq.-Hz
L1:220.0 L1:50.00
L2:220.0 L2:50.00
L3:220.0 L3:50.00
_____________________
TCR
%
R:23 S:23 T:23
Figure-5
THD-V(%) THD-I(%)
L1: 100.0 L1: 100.0
L2: 100.0 L2: 100.0
L3: 100.0 L3: 100.0
_____________________
TCR
%
R:23 S:23 T:23
Voltage(V) Curr.(A)
L1:220.0 L1:380.0
L2:220.0 L2:380.0
L3:220.0 L3:380.0
_____________________
TCR
%
R:23 S:23 T:23
Figure-6
Figure-7
Total Energy (²)
+P: 0234565100.0kWh
+Q: 1213215100.0kVArh
-Q: 0235115500.0kVArh
-P: 0235115500.0kWh
_____________________
TCR
%
R:23 S:23 T:23
Figure-8
Figure-1:
Total power factor, active power, capacitive power, inductive power, apparent power, offset
and active / reactive ratio values a re displayed on the screen.
Figure-2:
Cosine values o f each phase are displayed on the screen. Pressing the RIGHT button
displays the Power Factor values.
Figure-3:
Instant, hourly, daily and total active consumption / reactive consumption rates are
displayed on the screen.
Figure-4:
Phase-Neutral voltage and frequency values a re displayed on the screen. When the RIGHT
button is pressed, phase-phase voltage values a re displayed.
Figure-5:
Phase-Neutral voltage and current values a re displayed on the screen.
Figure-6:
Instantaneous power values o f each phase are displayed on the screen. Pressing the
RIGHT button displays the Apparent Power values.
Figure-7:
Total energy values a re displayed on the screen. Active Energy, Inductive Energy,
Capacitive Energy, Export Active Energy and Apparent Energy values a re displayed respectively by
pressing the RIGHT button.
Figure-8:
THD-V and THD-I values a re displayed on the screen. When pressing the RIGHT button,
Voltage Harmonic (L1, L2, L3) and Current Harmonic (L1, L2, L3) values a re shown respectively.
Figure-1
_____________________
TCR
%
R:23 S:23 T:23
PF:
P :
+Q:
-Q:
S :
Off:
1.000
0.000kW
0.000kVar
0.000kVar
0.000kVA
0.0kVar
Ind(%)
Cap(%)
0.0
0.0
When the device is energized, figure-1 is displayed on the screen.
When you press the UP button, figure-2 is displayed on the screen.
When you press the UP button, figure-3 is displayed on the screen.
When you press the UP button, figure-4 is displayed on the screen.
When you press the UP button, figure-5 is displayed on the screen.
When you press the UP button, figure-6 is displayed on the screen.
When you press the UP button, figure-7 is displayed on the screen.
When you press the UP button, figure-8 is displayed on the screen.
When you press the UP button, figure-1 is displayed on the screen again.
Figure-1
_____________________
TCR
%
R:23 S:23 T:23
PF:
P :
+Q:
-Q:
S :
Off:
1.000
0.000kW
0.000kVar
0.000kVar
0.000kVA
0.0kVar
Ind(%)
Cap(%)
0.0
0.0