15

How to Enter the Step Value Manually?

    When you enter the Step Menu page, the Step Values   page 

is displayed on the screen first.
    Switch to the Manual Step Value Set page by pressing the 

UP button, then enter the Manual Step Value Set page by 

pressing the SET button.

     In this page, you can navigate between parameters (Step, 

Type and Value) with the RIGHT button, and change the value 

in the selected parameter with the UP/DOWN buttons.
    To change the current value, the relevant parameter must 

be selected with the RIGHT button. The selected parameter is 

indicated by the sign "

>

" on the left side.

MANUAL STEP

VALUE SET

Menu.2.6

Enter Step Value

 Type   : L123
 Value  : -10.00kvar

>Step   : 1

Menu.2.6.1

     After entering the step information manually, SET button is 

pressed to save. After the saving process, the step 

information recorded and “Step Approved” are displayed on 

the screen. 

    

    To exit without saving, pressing the ESC button will return 

to the Maneul Step Value Set page.

Enter Step Value

 Type   : L123
 Value  : -10.00kvar

>Step   : 1

Menu.2.6.1

Step Approved

    Example:

 On the screen above, the three-phase 10kVAr capacitor value has been entered in the 1st step.

    

    If the value to be entered is single phase, “L1, L2 or L3” should be selected from the phase part 

according to the phase to which it is connected. If the value to be entered is two phase, “L12, L23 or L31” 

should be selected from the phase part according to the phase to which it is connected. If the value to be 

entered is three phase, “L123” should be selected.

    Note:

 Capacitor values a  re entered as (-) signed with DOWN button. Shunt reactor values a  re entered 

unsigned with the UP button.

    When SET button is pressed on any measurement page, the 

PASSWORD page is displayed for entering the menu.

    While on this page, press the SET button to enter the menu.

    (The password value is “0000” by default. If the password 

has been changed by the user, the password determined by 

the user must be used to enter the menu.)

    After passing the password page, Current Transformer 

Menu page will be displayed on the screen.
     While on this page, press UP button to switch to the Step 

Menu page.
    The Step Menu page will appear on the screen. Press the 

SET button to enter the Step Menu page.

STEP MENU

Menu.2.0

Enter Password!
PASS : 0000

16

How is Step Control Done?

    It is a menu designed to control the connections and 

robustness of the shunt reactors, capacitors and contactors 

connected to the stages.
        When SET button is pressed on any measurement page, 

the PASSWORD page is displayed for entering the menu.

    While on this page, press the SET button to enter the menu.

    (The password value is “0000” by default. If the password 

has been changed by the user, the password determined by 

the user must be used to enter the menu.)

    After passing the password page, Current Transformer 

Menu page will be displayed on the screen.
     While on this page, press UP button to switch to the Step 

Menu page.
    The Step Menu page will appear on the screen. Press the 

SET button to enter the Step Menu page.

    When you enter the Step Menu page, the Step Values   page 

is displayed on the screen first.
    Switch to the Step Control page by pressing the UP button, 

then enter the Step Control page by pressing the SET button.

    In this page, you can navigate between the steps with UP / 

DOWN buttons, you can use the RIGHT button to control / 

activate the steps and passive the active steps.

    

    Active steps are indicated by the "*" sign.
    When you return to the measurements screen by pressing 

the ESC button, if there are any steps you have activated 

manually, the device will make these steps passive one by one.

Measurement Screen Introduction

Measurements

 

E

L1:220.0    L1:380.0
L2:220.0    L2:380.0
L3:220.0    L3:380.0

_____________________
TCR

 

%

  

R:23 S:23 T:23

Voltage(V)   Curr.(A)

1

2

3

1- The area where the name and unit 

of the measured value are specified.
2- The area where the measured values   

are displayed.

3- The area where the SVC (TCR) usage 

percentage and Alarm states are displayed.
NOTE.:

 While the generator in the system is 

activated, “GEN” * will appear on the screen 

instead of “TCR”. (*: It is valid when the 

generator is connected to the device.)

    While on any measurement screen, you can switch to other measurement screens by using 

UP / DOWN or RIGHT buttons.

STEP CONTROL

Menu.2.5

>01[*]  05[ ]  09[ ]

02[ ]  06[ ]  10[ ]
03[ ]  07[ ]  11[ ]

TCR[ ]     

 

04[ ]  08[ ]  12[ ]

Menu.2.5.1   Control

STEP MENU

Menu.2.0

Enter Password!
PASS : 0000

Содержание RGT-12SVC

Страница 1: ...ELEKTR K ELEKTRON K SAN T C A www tense com tr www tenseenerji com Banks Hotels Oil Stations Schools Malls Factories Main Usage Areas RGT 12SVC USER MANUAL...

Страница 2: ...e Measurement Screen Inroduction 17 17 Cosinus Page Total Powers Page 17 Ratios Page 17 Voltage and Current Page 18 Instant Powers Page 18 Total Energy Page 18 THD V and THD I page 17 Voltage and Freq...

Страница 3: ...0 31 32 33 34 34 27 28 28 29 Advanced Settings Menu Power Factor Correction Power Analysis Samples ModBus RS485 Communication Settings Operating Power Operating Harmonic Delete Logs Generator Settings...

Страница 4: ...D I values of Each Phase can be Observed Creating Power Analysis 20 samples 9999 min It Shows The Total Number of Uses of the Steps Encrypted Protection Same Aging in Steps 1 Features About RGT 12SVC...

Страница 5: ...ding to the power of the capacitor and reactor and point as connection removing member Use seperate automatic fuse for each feeding inductor of the step conductors Use compensation contactors and disc...

Страница 6: ...ust be in the same order Connect the k l terminals of the current transformer connected to the L1 phase to the k1 l1 terminals the k l terminals of the current transformer connected to the L2 phase to...

Страница 7: ...ter the Current Transformer Value in the system using the UP and DOWN buttons and then press the SET button to save The device will automatically start Current Transformer Test operation In case of an...

Страница 8: ...ing You can check the stored step values on the Step Values screen 2 1 1 in the Step Menu When current transformer test is successful this page will be displayed on the screen If the operation is conf...

Страница 9: ...e screen When the RIGHT button is pressed phase phase voltage values are displayed Figure 5 Phase Neutral voltage and current values are displayed on the screen Figure 6 Instantaneous power values of...

Страница 10: ...ure 4 In this menu you can see Step Values take Step Measurement change Step Time Settings make PFC settings Make Step Control Manually Enter Step Value and set Auto Step Measurement Period Advanced S...

Страница 11: ...ps Harmonic Filter Kondansat r Thermal A2 2A 6A A1 L C1 C2 C3 C4 C5 C6 2A Voltages Input Voltages Output SRL XXT 1 2 3 L1 N in1 in2 Thermal Shunt Reactors Coil Coil Coil Thermal Thermal Thermal in3 L2...

Страница 12: ...instantaneous rate less than 15 If it is low this led will light 4 Buttons They are used to monitor measurements and make adjustments ESC Button When pressed in the menu it returns to the upper menu...

Страница 13: ...een Press the UP button to switch to the Current Transformer Value page While in this page press the SET button to enter the Current Transformer Value in the system Current Transformer Value Entry pag...

Страница 14: ...his page press SET button to enter Current Transformer Menu The Current Transformer Test page will appear on the screen Press the UP button to switch to the Current Transformer Value page CURRENT TRAN...

Страница 15: ...links The device will fix these connections software wise During the step measurement this page will be displayed on the screen all steps will be measured in order and their values will be displayed...

Страница 16: ...The device will fix these connections software wise Current Trans Test Yes No Menu 1 1 1 CURRENT TRANSFORMER TEST Menu 1 1 Enter Password PASS 0000 Three phase capacitor equivalent to 1 40 of current...

Страница 17: ...is used to select all the steps and TCR is used to measure shunt reactors connected to the drive Menu 2 2 1 Measure 01 05 09 02 06 10 03 07 11 TCR ALL 04 08 12 After the selected steps are measured th...

Страница 18: ...6 1 Step Approved Example On the screen above the three phase 10kVAr capacitor value has been entered in the 1st step If the value to be entered is single phase L1 L2 or L3 should be selected from th...

Страница 19: ...button In this page you can navigate between the steps with UP DOWN buttons you can use the RIGHT button to control activate the steps and passive the active steps Active steps are indicated by the si...

Страница 20: ...e password page is displayed for entering the menu When ESC button is pressed Home Page Total Powers is displayed Ratios Ind Cap Instant 0 3 0 2 Hourly 0 3 0 2 Daily 0 3 0 2 Energy 0 3 0 2 ___________...

Страница 21: ...yed When the SET button is pressed the password page is displayed for entering the menu When ESC button is pressed Home Page Total Powers is displayed THD V THD I L1 100 0 L1 100 0 L2 100 0 L2 100 0 L...

Страница 22: ...Connection Learned If the operation is confirmed by pressing the SET button the device will automatically start the Step Measurement process After the test it indicates that the current transformer t...

Страница 23: ...ween the steps with UP DOWN buttons select the steps you want to measure with the RIGHT button and start the measurement process by pressing the SET button The stages selected for the measurement are...

Страница 24: ...steps at once it determines the time to wait between the steps Factory Setting 400msec Setting Range 100msec 3000msec KADEME OLCUMU Menu 2 2 SettingsE Step MenuE PFC Settings PFC SETTINGS Menu 2 4 PFC...

Страница 25: ...he Step Approved notification appear on the screen To exit without saving pressing the ESC button will return to the Manual Step Value Set page Example On the screen above the three phase 10kVAr capac...

Страница 26: ...2 7 1 Settings E Advanced Settings Menu It is the third menu that appears when you proceed by pressing the UP button after entering the settings page In this menu Compensation Target Value can be set...

Страница 27: ...ve powers drawn from each phase are recorded along with their duration capacitive powers are indicated by a sign If the power consumption remains constant over a certain period of time it is recorded...

Страница 28: ...ive Menu 3 4 1 Voltage V Curr A L1 220 0 L1 380 0 L2 220 0 L2 380 0 L3 220 0 L3 380 0 _____________________ ALR Low Voltage It is the fifth of the 8 different setting parameters in the advanced settin...

Страница 29: ...while the Generator Compensation page is on the screen In this page you can navigate between the parameters Control Set and Tolerance with the RIGHT button and change the value in the selected parame...

Страница 30: ...ontact is activated When the alarm mode is passive no warning is given Settings E Advanced Settings Menu E PF Correction Alarm Settings E Device Settings Menu It is the fourth menu that appears when y...

Страница 31: ...he default password value 0000 the new password will need to be entered each time it is desired to enter the Settings menu Settings E Device Settings Menu E Change Password It is the third of 4 differ...

Страница 32: ...the end of the set time It is the last of the 4 different setting parameters in the device settings menu To change the backlight off time press the SET button while the Backlight Settings page is on t...

Страница 33: ...ection Q 4 3 Phase Connection Q 3 2 Phase Connection Bridge Q 3 Capacitor Powers 0 16 KVAR 0 33 KVAR 0 5 KVAR 0 83 KVAR 1 66 KVAR 2 5 KVAR 3 33 KVAR 5 KVAR 6 66 KVAR 8 33 KVAR 10 KVAR 0 16 KVAR 0 33 K...

Страница 34: ...L1 Capacitor kvar Single phase L2 Capacitor kvar Single phase L3 Capacitor kvar Step Value Determination According to Power Analysis Samples Three Phase capacitors have the lowest 0 5kVAr and the hig...

Страница 35: ...99 00 0 1200 Even 1 1 5000 5 30 30 A sec sec 99 99 60 270 210 60 50 50 60 3000 99 00 26 19200 Odd 2 247 sec msec kVAr week bps sec V V sec Set Value Tolerance Value 0 50 1 0 50 10 0 It can be active...

Страница 36: ...33 Dimensions 138mm 147mm 114 5mm 147mm 138mm Back View 147mm Front View 147mm Left Side View 138mm 43mm 22mm Fixing apparatus Screw fixing apparatus 45mm 34mm 6mm 143mm...

Страница 37: ...ccuracy Reactive Power Accuraacy Harmonic Voltage Measuring Range Harmonic Current Measuring Range 100V 300V AC 50 60 Hz 12VA 20 C 55 C 30 C 80 C 90 5mA 5 5A 2 9 128x64 Graphic LCD and LEDs 1 5mm 2 5m...

Страница 38: ...ELEKTR K ELEKTRON K SAN T C A Document Number DK 094 2 Rev 1 10_200317 QUALITY SOLUTIONS MADE IN TURKEY Energy and Compensation Tracking System www tenseenerji com...

Отзывы: